Discharge thermal protector
The discharge thermal protector (Q*D) is activated when the
temperature of the refrigerant leaving the compressor becomes
too high. When the temperature returns to normal, the protector
resets automatically, but the controller needs to be reset
manually.

Freeze up sensor
The outlet water temperature sensor (R4T) measures the
temperature of the water at the water heat exchanger outlet. The
protection device shuts down the circuit when the temperature of
the chilled water becomes too low in order to prevent freezing of
the water during operation. 
When the outlet water temperature returns to normal, the
protector resets automatically, but the controller needs to be
reset manually.

Fuse for control circuit (F1U)
The fuse for control circuit protects cables of control circuit and
controller components in case of short circuit.

Fuse for control circuit (F4)
The fuse for the control circuit protects cables of the control
circuit in case of a short circuit.

Fuse for digital controller (F3U)
The fuse protects cables of digital controller and digital controller
in case of short circuit.

Flow switch (delivered with the unit, installed in the field)
The flow switch measures the flow in the water circuit. In case
the flow does not reach the minimum allowed water flow, the unit
will be shut down.

Ball valve (delivered with the unit, installed in the field)
A ball valve is installed in front of and behind the water filter to
allow filter cleaning without having to drain the water circuit.

Water filter (delivered with the unit, installed in the field)
The filter installed in front of the unit removes dirt from the water
to prevent damage to the unit or blockage of the evaporator or
condenser. The water filter should be cleaned on a regular base.

Air purge valve (delivered with the unit, installed in the field)
Remaining air in the chiller water system will be automatically
removed via the air purge valve.

Internal wiring - Parts table

Refer to the internal wiring diagram supplied with the unit. The
abbreviations used are listed below:

A1P ........................ PCB: controller PCB

A2P ........................ PCB: I/O PCB (input/output)

A3P ..............** ...... PCB: Address card for BMS

(1)

A5P,A6P.......** ...... PCB: Softstarter for circuit 1, circuit 2

(1)

A7P ..............** ...... PCB: Remote user interface

(1)

A71P ...................... PCB: power supply card

A72P ...................... PCB: remote user interface

F1,F2,F3 .......# ...... Main fuses for the unit

(2)

F4 ................. * ...... Fuse I/O PCB

F5 ...............## ...... Surge proof fuse

F6 .................# ...... Fuse for pumpcontactor

(2)

F1U ........................ Fuse I/O PCB

F3U ........................ Fuse for controller PCB

H3P............... * ...... Indication lamp alarm

(2)

H4P............... * ...... Indication lamp operation compressor 1

(2)

H5P............... * ...... Indication lamp operation compressor 2

(2)

H6P............... * ...... Indication lamp general operation

(2)

K1M,K2M ............... Compressor contactor circuit 1, circuit 2

K4S,K5S ................ Overcurrent relay circuit 1, circuit 2

K6S ............... * ...... Overcurrent relay pump

(2)

K1P ............... * ...... Pumpcontactor

M1C,M2C............... Compressor motor circuit 1, circuit 2

PE .......................... Main earth terminal

Q1D,Q2D ............... Discharge thermal protector circuit 1, circuit 2

R3T ........................ Evaporator inlet water temperature sensor

R4T ........................ Evaporator outlet water temperature sensor

R5T ........................ Condenser inlet temperature sensor

S1HP,S2HP............ High pressure switch circuit 1, circuit 2

S4LP,S5LP............. Low pressure switch circuit 1, circuit 2

S7S ............... * ...... Switch for remote cooling/heating selection or 

dual setpoint

(2)

S9S ............... * ...... Switch for remote start/stop or dual setpoint

(2)

S10L ...................... Flow switch

S12M ..................... Main isolator switch

TR1 ........................ Transfo 230 V 

 24 V for supply of controller 

PCB

TR2 ........................ Transfo 230 V 

 24 V for supply of I/O PCB 

(A2P)

Y3R........................ Reversing valve

X1~3,X1~82A ........ Connectors

(1) optional
(2) field supply

Not included with standard unit

Not possible as option

Possible as option

Obligatory

#

##

Not obligatory

*

**

Summary of Contents for EWWP014KBW1N

Page 1: ...OPERATION MANUAL EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N Packaged water cooled water chillers...

Page 2: ...1 EWWP014KBW1N EWWP045KBW1N EWWP022KBW1N EWWP055KBW1N EWWP028KBW1N EWWP065KBW1N EWWP035KBW1N Packaged water cooled water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE U...

Page 3: ...led Model EWWP 045 055 065 Power supply Phase 3N Frequency Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal runn...

Page 4: ...O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected o...

Page 5: ...t from the water to prevent damage to the unit or blockage of the evaporator or condenser The water lter should be cleaned on a regular base Air purge valve delivered with the unit installed in the el...

Page 6: ...your local dealer 9 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identi cation label of the unit Water supply Fill...

Page 7: ...n page 8 Resetting alarms on page 8 Resetting warnings on page 8 Keys digital controller Keys remote interface Main display Sensor readout menu Parameter selection menu Parameter setting menu A T Pres...

Page 8: ...the setting of the selected parameter Only valid for read write parameters 7 Press the B key to con rm the modi ed setting OR Press the A key to cancel the modi ed setting 8 Press the A key to return...

Page 9: ...ror communication failure between the digital controller of the unit and the remote user interface Con rm the correct selection of parameter code h23 This should be default setting 0 and con rm the co...

Page 10: ...hreshold for maintenance warning c10 and c11 0 0 100 x100 hours R W U 241 I c15 Total running hours of pump x100 hours R D 126 A d No user or direct parameters accessible f No user or direct parameter...

Page 11: ...ss the A key to cancel the modi ed setting 11 Press the A key to return to the parameter group 12 Press 2 times the A key to return to the main display If during the procedure no buttons are pressed f...

Page 12: ...te on off switch installed by the customer allows the user to switch the unit on without using the D or C key on the controller When user parameter h07 is set to 0 not active the unit can only be swit...

Page 13: ...able with read only status the command will not be executed at all Variables requested by the supervisory system that are not available in a chiller with an address card are sent from the address card...

Page 14: ...s a user parameter refer to How to consult and modify the user parameters on page 10 Variables database The BMS or supervisory system and the chiller unit communicate through a xed set of variables al...

Page 15: ...s activated Refer to the explanation of the digital controller in the chapter Resetting alarms on page 8 The remote ON OFF input is enabled and the remote switch is off Put the remote switch on or dis...

Page 16: ...e electrical components are not damaged or loose Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened Refrigerant circuit Check for l...

Page 17: ...ect parameter setting values s p or levels l p a a l p function is not used Select parameter group Select parameter Read and modify parameter D C 2 D C 2 2 C B A A C D B C D C D C D C D C D C D C D C...

Page 18: ......

Page 19: ......

Page 20: ...4PW61660 1A 2012 04 Copyright 2010 Daikin...

Reviews: