Daikin EWWP014KBW1N Operation Manual Download Page 2

Operation manual

1

EWWP014~065KBW1N

Packaged water-cooled water chillers

4PW61660-1A – 04.2012

C

ONTENTS

Page

Introduction ....................................................................................... 1

Technical specifications ............................................................................. 1
Electrical specifications ............................................................................. 2

Description ........................................................................................ 2

Function of the main components.............................................................. 3
Safety devices............................................................................................ 3
Internal wiring - Parts table ........................................................................ 4

Before operation................................................................................ 5

Checks before initial start-up ..................................................................... 5
Water supply .............................................................................................. 5
General recommendations ........................................................................ 5

Operation .......................................................................................... 5

Digital controller ......................................................................................... 5
Working with the units................................................................................ 6
Advanced features of the digital controller................................................. 9

BMS connection modbus ................................................................ 12

General description of Modbus................................................................ 12
Implemented error code........................................................................... 13
Defining the BMS setting ......................................................................... 13
Variables database .................................................................................. 13

Troubleshooting ............................................................................... 14

Maintenance.................................................................................... 15

Important information regarding the refrigerant used .............................. 15
Maintenance activities ............................................................................. 15
Disposal requirements ............................................................................. 15

Menu overview ................................................................................ 16

The English text is the original instruction. Other languages are
translations of the original instructions.

This appliance is not intended for use by persons, including children,
with reduced physical, sensory or mental capabilities, or lack of
experience and knowledge, unless they have been given supervision
or instruction concerning use of the appliance by a person
responsible for their safety.
Children should be supervised to ensure that they do not play with
the appliance.

I

NTRODUCTION

This operation manual concerns packaged water-cooled water
chillers of the Daikin EWWP-KB series. These units are provided for
indoor installation and used for cooling and/or heating applications.
The units can be combined with Daikin fan coil units or air handling
units for air conditioning purposes. They can also be used for
supplying water for process cooling.

This manual has been prepared to ensure adequate operation and
maintenance of the unit. It will tell you how to use the unit properly
and will provide help if problems occur. The unit is equipped with
safety devices, but they will not necessarily prevent all problems
caused by improper operation or inadequate maintenance. 

In case of persisting problems contact your local Daikin Dealer.

Technical specifications

(1)

EWWP014KBW1N

EWWP045KBW1N

EWWP022KBW1N

EWWP055KBW1N

EWWP028KBW1N

EWWP065KBW1N

EWWP035KBW1N

Packaged water-cooled water chillers

Operation manual

READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW THIS MANUAL AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
Read the chapter 

"Operation" on page 5

 before changing

the parameters. 

Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
carefully read the installation manual supplied with the unit
and the recommendations listed in "Before starting".

(1) Refer to the engineering data book for the complete list of specifications.

General EWWP

014

022

028

035

Nominal cooling 

capacity

(a)

(kW)

13.0

21.5

28.0

32.5

Nominal input

(b)

(kW)

3.71

5.96

7.76

9.10

Dimensions HxWxD

(mm)

600x600x600

Machine weight

(kg)

113

150

160

167

Connections

• water inlet

G 1

• water outlet

G 1

General EWWP

045

055

065

Nominal cooling 

capacity

(a)

(a) The nominal cooling capacity is based on:

- entering water temperature of 12°C
- chilled water temperature of 7°C
- condenser in/out 30/35°C

(kW)

43.0

56.0

65.0

Nominal input

(b)

(b) The nominal input includes total input of the unit: compressor control circuit and 

water pumps.

(kW)

12.1

16.0

18.3

Dimensions HxWxD

(mm)

600x600x1200

Machine weight

(kg)

300

320

334

Connections

• water inlet

G 1-1/2

• water outlet

G 1-1/2

Compressor

014

022

028

035

Model

JT140BF-YE

JT212DA-YE JT300DA-YE JT335DA-YE

Speed

(rpm)

2900

Oil type

FVC68D

Oil charge volume

(l)

1.5

2.7

2.7

2.7

Refrigerant type

R407C

Refrigerant charge

(kg)

1.2

2

2.5

3.1

Evaporator

014

022

028

035

Type

brased plate heat exchanger

Min. water volume

(l)

62

103

134

155

Water flow range

(l/min)

31~75

53~123

65~161

76~186

Condenser

014

022

028

035

Type

brased plate heat exchanger

Water flow range

(l/min)

24~95

39~157

51~203

59~237

Compressor

045

055

065

Model

2x 

JT212DA-YE

2x 

JT300DA-YE

2x 

JT335DA-YE

Speed

(rpm)

2900

Oil type

FVC68D

Oil charge volume

(l)

2x 2.7

2x 2.7

2x 2.7

Refrigerant type

R407C

Refrigerant charge

(kg)

4.6

4.6

5.6

Evaporator

045

055

065

Type

brased plate heat exchanger

Min. water volume

(l)

205

268

311

Water flow range

(l/min)

101~247

131~321

152~373

Condenser

045

055

065

Type

brased plate heat exchanger

Water flow range

(l/min)

79~314

102~410

118~474

Summary of Contents for EWWP014KBW1N

Page 1: ...OPERATION MANUAL EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N Packaged water cooled water chillers...

Page 2: ...1 EWWP014KBW1N EWWP045KBW1N EWWP022KBW1N EWWP055KBW1N EWWP028KBW1N EWWP065KBW1N EWWP035KBW1N Packaged water cooled water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE U...

Page 3: ...led Model EWWP 045 055 065 Power supply Phase 3N Frequency Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal runn...

Page 4: ...O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected o...

Page 5: ...t from the water to prevent damage to the unit or blockage of the evaporator or condenser The water lter should be cleaned on a regular base Air purge valve delivered with the unit installed in the el...

Page 6: ...your local dealer 9 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identi cation label of the unit Water supply Fill...

Page 7: ...n page 8 Resetting alarms on page 8 Resetting warnings on page 8 Keys digital controller Keys remote interface Main display Sensor readout menu Parameter selection menu Parameter setting menu A T Pres...

Page 8: ...the setting of the selected parameter Only valid for read write parameters 7 Press the B key to con rm the modi ed setting OR Press the A key to cancel the modi ed setting 8 Press the A key to return...

Page 9: ...ror communication failure between the digital controller of the unit and the remote user interface Con rm the correct selection of parameter code h23 This should be default setting 0 and con rm the co...

Page 10: ...hreshold for maintenance warning c10 and c11 0 0 100 x100 hours R W U 241 I c15 Total running hours of pump x100 hours R D 126 A d No user or direct parameters accessible f No user or direct parameter...

Page 11: ...ss the A key to cancel the modi ed setting 11 Press the A key to return to the parameter group 12 Press 2 times the A key to return to the main display If during the procedure no buttons are pressed f...

Page 12: ...te on off switch installed by the customer allows the user to switch the unit on without using the D or C key on the controller When user parameter h07 is set to 0 not active the unit can only be swit...

Page 13: ...able with read only status the command will not be executed at all Variables requested by the supervisory system that are not available in a chiller with an address card are sent from the address card...

Page 14: ...s a user parameter refer to How to consult and modify the user parameters on page 10 Variables database The BMS or supervisory system and the chiller unit communicate through a xed set of variables al...

Page 15: ...s activated Refer to the explanation of the digital controller in the chapter Resetting alarms on page 8 The remote ON OFF input is enabled and the remote switch is off Put the remote switch on or dis...

Page 16: ...e electrical components are not damaged or loose Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened Refrigerant circuit Check for l...

Page 17: ...ect parameter setting values s p or levels l p a a l p function is not used Select parameter group Select parameter Read and modify parameter D C 2 D C 2 2 C B A A C D B C D C D C D C D C D C D C D C...

Page 18: ......

Page 19: ......

Page 20: ...4PW61660 1A 2012 04 Copyright 2010 Daikin...

Reviews: