Daikin EWWP014KBW1N Operation Manual Download Page 14

Operation manual

13

EWWP014~065KBW1N

Packaged water-cooled water chillers

4PW61660-1A – 04.2012

Data representation of the Modbus protocol

Digital
All digital data is coded by a single bit:

"0" for OFF

"1" for ON.

All digital variables are assigned to bits of consecutive registers,
each one having:

the lower-address variable assigned to the less significant bit

the higher-address variable assigned to the most significant
bit.

Analogue and integer data
An analogue and integer value is represented by a 16-bit WORD
register in binary notation. For each register, the first byte
contains the high order bits and the second byte contains the
low order bits.

The analogue variables are represented in tenths:
for example, the value 10.0 is transmitted as 0064h=100d
for example, the value –10.0 is transmitted as FF9Ch=–100d

The integer variables are transferred using the effective
value:
for example, the value 100 is transmitted as 0064h=100d

The address card operates on registers where one register must
be considered at 16-bit.

In case the BMS or supervisory system tries to write a value of a
parameter that is out of range, the writing will be ignored.

Implemented error code

Defining the BMS setting

Activating the Modbus protocol

The Modbus protocol is activated by setting the 

h23

 parameter to 

1

.

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

Defining the unit's serial address

To define each unit's unique serial address required for
communication with the supervisionary system, set parameter 

h10

.

This is a user parameter, refer to 

"How to consult and modify the user

parameters" on page 10

.

Variables database

The BMS or supervisory system and the chiller unit communicate
through a fixed set of variables, also called address numbers.
Hereafter, you will find the information you need about the digital,
integer and analogue variables that the BMS or supervisory system
can read from or write to the address card of the chiller.

For addresses of all the direct and user parameters refer to

"Overview of the direct and user parameters" on page 9

.

Overview of all variables which are not direct or user 
parameters

Code

Modbus interpretation

Condition

1

Illegal function

Message is not supported or the 
number of variables required is greater 
than the allowed limit (length 

20)

Description

Modbus 
address

Parameter 

type

(a)

(a) D=digital.

Circuit alarm

1=A1, HP1, or LP1 
alarm codes active

0=no alarm code active

Read 

only

41

D

General alarm

1=FL alarm code

0=no alarm code active

Read 

only

45

D

NTC Probe alarm

1=E1, E2, or E3 alarm 

codes

0=no alarm code active

Read 

only

46

D

Input of flowswitch 

alarm

1=closed

0=open

Read 

only

53

D

Input of 

changeable digital 

S7S input

1=closed

0=open

Read 

only

54

D

Input of high 

pressure or 

discharge protector 

or overcurrent 

alarm

1=closed

0=open

Read 

only

55

D

Input of low 

pressure switch 

alarm

1=closed

0=open

Read 

only

56

D

Input of 

changeable digital 

S9S input

1=closed

0=open

Read 

only

57

D

Output of 

compressor 1

1=on
0=off

Read 

only

59

D

Output of 

compressor 2

1=on
0=off

Read 

only

60

D

Output of pump

1=on
0=off

Read 

only

61

D

Output of reversing 

valve

1=on
0=off

Read 

only

62

D

Output of alarm

1=on
0=off

Read 

only

63

D

On or off

1=on
0=off

Read/

write

64

D

Cooling or heating

1=cooling

0=heating

Read/

write

65

D

Summary of Contents for EWWP014KBW1N

Page 1: ...OPERATION MANUAL EWWP014KBW1N EWWP022KBW1N EWWP028KBW1N EWWP035KBW1N EWWP045KBW1N EWWP055KBW1N EWWP065KBW1N Packaged water cooled water chillers...

Page 2: ...1 EWWP014KBW1N EWWP045KBW1N EWWP022KBW1N EWWP055KBW1N EWWP028KBW1N EWWP065KBW1N EWWP035KBW1N Packaged water cooled water chillers Operation manual READ THIS MANUAL ATTENTIVELY BEFORE STARTING UP THE U...

Page 3: ...led Model EWWP 045 055 065 Power supply Phase 3N Frequency Hz 50 Voltage V 400 Voltage tolerance 10 Recommended fuses aM 3x 40 3x 50 3x 50 Compressor Phase 3 Frequency Hz 50 Voltage V 400 Nominal runn...

Page 4: ...O PCB A2P input output The I O PCB A2P contains a reverse phase protector The reverse phase protector detects if the 3 phases of the power supply are connected correctly If a phase is not connected o...

Page 5: ...t from the water to prevent damage to the unit or blockage of the evaporator or condenser The water lter should be cleaned on a regular base Air purge valve delivered with the unit installed in the el...

Page 6: ...your local dealer 9 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identi cation label of the unit Water supply Fill...

Page 7: ...n page 8 Resetting alarms on page 8 Resetting warnings on page 8 Keys digital controller Keys remote interface Main display Sensor readout menu Parameter selection menu Parameter setting menu A T Pres...

Page 8: ...the setting of the selected parameter Only valid for read write parameters 7 Press the B key to con rm the modi ed setting OR Press the A key to cancel the modi ed setting 8 Press the A key to return...

Page 9: ...ror communication failure between the digital controller of the unit and the remote user interface Con rm the correct selection of parameter code h23 This should be default setting 0 and con rm the co...

Page 10: ...hreshold for maintenance warning c10 and c11 0 0 100 x100 hours R W U 241 I c15 Total running hours of pump x100 hours R D 126 A d No user or direct parameters accessible f No user or direct parameter...

Page 11: ...ss the A key to cancel the modi ed setting 11 Press the A key to return to the parameter group 12 Press 2 times the A key to return to the main display If during the procedure no buttons are pressed f...

Page 12: ...te on off switch installed by the customer allows the user to switch the unit on without using the D or C key on the controller When user parameter h07 is set to 0 not active the unit can only be swit...

Page 13: ...able with read only status the command will not be executed at all Variables requested by the supervisory system that are not available in a chiller with an address card are sent from the address card...

Page 14: ...s a user parameter refer to How to consult and modify the user parameters on page 10 Variables database The BMS or supervisory system and the chiller unit communicate through a xed set of variables al...

Page 15: ...s activated Refer to the explanation of the digital controller in the chapter Resetting alarms on page 8 The remote ON OFF input is enabled and the remote switch is off Put the remote switch on or dis...

Page 16: ...e electrical components are not damaged or loose Earth connection Make sure that the earth wires are still connected properly and that the earth terminals are tightened Refrigerant circuit Check for l...

Page 17: ...ect parameter setting values s p or levels l p a a l p function is not used Select parameter group Select parameter Read and modify parameter D C 2 D C 2 2 C B A A C D B C D C D C D C D C D C D C D C...

Page 18: ......

Page 19: ......

Page 20: ...4PW61660 1A 2012 04 Copyright 2010 Daikin...

Reviews: