Daikin EWWD120MBYNN Installation Manual Download Page 4

Installation manual

1

EWWD120~540MBYNN

Packaged water-cooled water chillers

4PW22684-1A

C

ONTENTS

Page

Introduction ....................................................................................... 1

Technical specifications .............................................................. 1

Electrical specifications ............................................................................. 1
Options and features ................................................................................. 1
Standard supplied accessories.................................................................. 2

Operation range ................................................................................ 2

Main components.............................................................................. 2

Selection of location .......................................................................... 2

Inspecting and handling the unit ....................................................... 2

Unpacking and placing the unit ......................................................... 3

Preparing, checking and connecting the water circuit ....................... 3

Water charge, flow and quality .......................................................... 4

Piping insulation ................................................................................ 5

Discharge from pressure relief devices ............................................. 5

Field wiring ........................................................................................ 5

Parts table.................................................................................................. 5
Power circuit and cable requirements ........................................................ 5
Connection of the watercooled water chiller power supply ........................ 5
Interconnection cables............................................................................... 5
Connection and setup of a DICN system................................................... 6
Cable for remote digital controller .............................................................. 6

Before starting................................................................................... 7

Customization in the service menu ................................................... 7

How to continue................................................................................. 8

Thank you for purchasing this Daikin air conditioner. 

I

NTRODUCTION

The Daikin EWWD-MBYNN packaged water-cooled water chillers
are designed for indoor installation and used for cooling applications
only. The units are available in 9 standard sizes with nominal cooling
capacities ranging from 120 to 540 kW. 

The EWWD units can be combined with Daikin fan coil units or air
handling units for air conditioning purposes. They can also be used
for supplying chilled water for process cooling.

The present installation manual describes the procedures for unpack-
ing, installing and connecting the EWWD units.

Technical specifications

(1)

 

Electrical specifications

(1)

Options and features

(1)

Options

Suction stop valve

Ampere and voltmeter

Main isolator switch

Dual pressure relief valve on the condenser

Low noise operation

BMS-Connection (MODBUS/J-BUS, BACNET, LON)

Features

Glycol application for leaving evaporator water down to –10°C

Daikin Integrated Chiller Network (DICN)

Liquid line solenoid valve

Sight glass with moisture indication

Voltage free contacts

general operation/pumpcontact

alarm

operation circuit 1

operation circuit 2 (only for EWWD360~540)

EWWD120MBYNN

EWWD280MBYNN

EWWD500MBYNN

EWWD180MBYNN

EWWD360MBYNN

EWWD520MBYNN

EWWD240MBYNN

EWWD440MBYNN

EWWD540MBYNN

Packaged water-cooled water chillers

Installation manual

READ THIS MANUAL ATTENTIVELY BEFORE STARTING
UP THE UNIT. DO NOT THROW IT AWAY. KEEP IT IN YOUR
FILES FOR FUTURE REFERENCE.

IMPROPER INSTALLATION OR ATTACHMENT OF EQUIP-
MENT OR ACCESSORIES COULD RESULT IN ELECTRIC
SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR OTHER DAM-
AGE TO THE EQUIPMENT. BE SURE ONLY TO USE
ACCESSORIES MADE BY DAIKIN WHICH ARE SPECIFI-
CALLY DESIGNED FOR USE WITH THE EQUIPMENT AND
HAVE THEM INSTALLED BY A PROFESSIONAL.

IF UNSURE OF INSTALLATION PROCEDURES OR USE,
ALWAYS CONTACT YOUR DAIKIN DEALER FOR ADVICE
AND INFORMATION.

(1) Refer to the operation manual or engineering data book for the complete 

list of specifications, options and features.

Model EWWD

120

180

240

Dimensions HxWxD

(mm)

1014x2672x930

Weight

• machine weight

 (kg)

1000

1273

1527

• operation weight

 (kg)

1032

1318

1588

Connections

• chilled water inlet/outlet

(1)

(inch)

3" OD 

(76 mm OD)

3" (88.9 mm OD)

• condenser water inlet/outlet

(1)

(inch)

2-1/2" 

3" (88.9 mm OD)

Model EWWD

280

360

440

Dimensions HxWxD

(mm)

1014x2672

x930

2000x2672x930

Weight

• machine weight

 (kg)

1613

2546

2800

• operation weight

 (kg)

1693

2636

2902

Connections

• chilled water inlet/outlet

(1)

(inch)

3" (88.9 mm OD)

• condenser water inlet/outlet

(1)

(inch)

3" (88.9 mm OD)

Model EWWD

500

520

540

Dimensions HxWxD

(mm)

2000x2672x898

Weight

• machine weight

 (kg)

3034

3150

3346

• operation weight

 (kg)

3156

3281

3485

Connections

• chilled water inlet/outlet

(1)

(1) Victaulic

®

 coupling

(inch)

3" (88.9 mm OD)

• condenser water inlet/outlet

(1)

(inch)

3" (88.9 mm OD)

Model EWWD

120~540

Power circuit

• Phase

3~

• Frequency

(Hz)

50

• Voltage

(V)

400

• Voltage tolerance

(%)

±10

Summary of Contents for EWWD120MBYNN

Page 1: ...INSTALLATION MANUAL EWWD120MBYNN EWWD180MBYNN EWWD240MBYNN EWWD280MBYNN EWWD360MBYNN EWWD440MBYNN EWWD500MBYNN EWWD520MBYNN EWWD540MBYNN Packaged water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retag...

Page 4: ...10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication Voltage free contacts general operation pumpcontact alarm operation circuit 1 operation circ...

Page 5: ...enerated by the unit does not disturb anyone 5 Ensure that water cannot cause any damage to the location in case it drips out of the unit INSPECTING AND HANDLING THE UNIT At delivery the unit should b...

Page 6: ...d couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWWD120 The water outlet pipe containing the outlet water temperature sen...

Page 7: ...isted in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes o...

Page 8: ...ltage free contacts to indicate the status of the unit These voltage free contacts can be wired as described on the wiring diagram The maximum allowable current is 4 A Remote inputs Besides the voltag...

Page 9: ...s EWWD360 540 Specifications of the cable 6 ray telephone cable with a maximum cable resistance of 0 1 m 2 For units in a DICN configuration the digital controllers of the units can be installed remot...

Page 10: ...ist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEF...

Page 11: ...certain measured temperatures inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe off...

Page 12: ...all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master...

Page 13: ...shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this bu...