Daikin EWWD120MBYNN Installation Manual Download Page 13

EWWD120~540MBYNN

Packaged water-cooled water chillers

4PW22684-1A

Installation manual

10

Example 2: Single ring system with separate pumps

Figure 2 shows the system configuration, field wiring and terminals
for field wiring of this example.

Purpose

Purpose of this system is to deliver a constant water flow at a
constant temperature to a particular load. One unit, slave 3 (S3), is
kept as a standby unit.

Setup

The system is controlled on leaving water temperature. It is
required to install the additional sensor R8T (EKCLWS) in the
mixed water outlet and to connect it to the PCB of the master
unit.

Pump 1, pump 2 and pump 3 keep running as long as the mas-
ter unit, slave 1 or slave 2 are ON. Pump 4 only starts running if
slave 3 is switched ON. After switching OFF the units, the pump
runs for a time indicated by the 

 setting.

Slave 3 (S3) is configured to operate when its remote start/stop
switch S6S (S3) is pushed by the operator.

Slave 1 (S1), slave 2 (S2) and the master unit (M) are switched
ON or OFF using the remote start/stop switch S6S (M) which is
connected to the master unit.

The setpoint can be switched from 

  to

  using the dual setpoint selection switch S10S

which is connected to the master unit.

Parameter settings of the units

Usersettings menu:

Changeable inputs/outputs must be defined as follows:

Service setting menu:

Remark

Slave 3 can be configured to start up automatically if:

1 of the other units is in alarm or;

all other units are running on full capacity and the setpoint is not
reached yet.

To have your slave 3 unit act this way, set its mode to 

 

. In this

case, S6S (S3) has no function.

Example 3: Double ring system with several pumps

Figure 3 shows the system configuration, field wiring and terminals
for field wiring of this example.

Purpose

Purpose of this system is to keep a buffer at a constant temperature
and to feed a load from this buffer. One unit, slave 3 (S3), is kept as a
standby unit.

Setup

The system is controlled on entering water temperature.

The pumps of the slave units only run when their compressor is
running (energy saving). the pump runs for a time indicated by
the 

 setting.

The pump of the master unit must run continuously so as to
sense the correct temperature.

Slave 3 (S3) is configured to operate when its remote start/stop
switch S6S (S3) is pushed by the operator.

Slave 1 (S1), slave 2 (S2) and the master unit (M) are switched
ON or OFF using the remote start/stop switch S6S (M) which is
connected to the master unit.

The setpoint can be switched from 

 to 

using the dual setpoint selection switch S10S which is
connected to the master unit.

Parameter settings of the units

Usersettings menu:

Changeable inputs/outputs must be defined as follows:

Service setting menu:

Remark

Slave 3 can be configured to start up automatically if:

1 of the other units is in alarm or;

all other units are running on full capacity and the setpoint is not
reached yet.

To have your slave 3 unit act this way, set its mode to 

 

. In this

case, S6S (S3) has no function.

NOTE

K*P can also be a 24 V DC or 230 V AC contactor.

The additional sensor R8T (EKCLWS) must be
connected directly to the PCB of the master unit.

Slave 3

Slave 2

Slave 1

Master

 )

  

  )

 

     

Slave 3

Slave 2

Slave 1

Master

Terminal 76-78 

S10S DI1

  

Terminal 76-79 

S6S DI2

 

 

Terminal 76-85 

DI3

Terminal 76-86 

DI4

Terminal 8T+8T–

R8T AI1

  

 

NOTE

K*P can also be a 24 V DC or 230 V AC contactor.

Slave 3

Slave 2

Slave 1

Master

 )

  

  )  

     

Slave 3

Slave 2

Slave 1

Master

Terminal 76-78 

S10S DI1

  

Terminal 76-79 

S6S DI2

 

 

Terminal 76-85 

DI3

Terminal 76-86 

DI4

Terminal 8T+8T–

R8T AI1

Summary of Contents for EWWD120MBYNN

Page 1: ...INSTALLATION MANUAL EWWD120MBYNN EWWD180MBYNN EWWD240MBYNN EWWD280MBYNN EWWD360MBYNN EWWD440MBYNN EWWD500MBYNN EWWD520MBYNN EWWD540MBYNN Packaged water cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med senere ndringer 11 Direktiv med f retag...

Page 4: ...10 C Daikin Integrated Chiller Network DICN Liquid line solenoid valve Sight glass with moisture indication Voltage free contacts general operation pumpcontact alarm operation circuit 1 operation circ...

Page 5: ...enerated by the unit does not disturb anyone 5 Ensure that water cannot cause any damage to the location in case it drips out of the unit INSPECTING AND HANDLING THE UNIT At delivery the unit should b...

Page 6: ...d couplings to the evaporator inlet s Connecting the water outlet pipe containing the outlet water tem perature sensor not for EWWD120 The water outlet pipe containing the outlet water temperature sen...

Page 7: ...isted in the table below The filter kit supplied with the unit must be installed in front of the evaporator water inlet by means of the supplied couplings as shown in the figure The filter has holes o...

Page 8: ...ltage free contacts to indicate the status of the unit These voltage free contacts can be wired as described on the wiring diagram The maximum allowable current is 4 A Remote inputs Besides the voltag...

Page 9: ...s EWWD360 540 Specifications of the cable 6 ray telephone cable with a maximum cable resistance of 0 1 m 2 For units in a DICN configuration the digital controllers of the units can be installed remot...

Page 10: ...ist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for external damage 2 Open all shut off valves indicated by a red label OPEN THIS VALVE BEF...

Page 11: ...certain measured temperatures inlet water evaporator temperature and mixed outlet water evaporator temperature This in order to correct a possible measurement fault The default value of the probe off...

Page 12: ...all units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master...

Page 13: ...shows the system configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this bu...

Page 14: ...Installation manual 11 EWWD120 540MBYNN Packaged water cooled water chillers 4PW22684 1A NOTES...

Page 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergen...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22684 1A...

Reviews: