Daikin EWLP020KBW1N Installation Manual Download Page 8

Installation manual

6

EWLP012~065KBW1N

Condenserless water-cooled water chillers

4PW61665-1 – 07.2010

W

ATER

 

CHARGE

FLOW

 

AND

 

QUALITY

To  assure proper operation of the unit a minimum water volume is
required in the system and the water flow through the evaporator
must be within the operation range as specified in the table below.

W

ATER

 

PIPING

 

INSULATION

The complete water circuit, inclusive all piping, must be insulated to
prevent condensation and reduction of the cooling capacity.

Protect the water piping against water freezing during winter period
(e.g. by using a glycol solution or heatertape).

R

EFRIGERANT

 

PIPING

 

INSULATION

To  prevent burning injuries by accidental touching the hot (max
135°C) discharge pipe, it must be insulated thoroughly. 

A minimum of insulation to protect the liquid pipe from damage is
advisable.

I

NSTALLATION

 

OF

 

THE

 

CONDENSER

 

INLET

 

TEMPERATURE

 

SENSOR

For condenser water inlet control it is possible to enlarge the provided
water sensor cable for a total length of 100 m. It gives the opportunity
to place the water sensor near to the remote watercooled condenser
in order to have a reliable condenser water inlet measurment.

Connecting sensors and power supply

Sensors can be located up to 100 meters distance away from the
controller provided that you use cables with Ø1 mm

2

  min. To improve

immunity against noises we recommend using shielded cables (connect
just one end of the shielding to the earth of the electrical panel).

F

IELD

 

WIRING

 

Parts table

F1,2,3 .................... Main fuses for the unit

H3P........................ Indication lamp alarm

H4P,H5P ................ Indication lamp operation compressor circuit 1, 

circuit 2

K1F,K2F ................. fancontactor

PE.......................... Main earth terminal

S7S........................ Switch for remote cooling/heating change-over 

valve or dual setpoint

S9S........................ Switch for remote start/stop or dual setpoint

- - - ......................... Field wiring

Power circuit and cable requirements

1

The electrical power supply to the unit must be arranged so that
it can be switched on or off independently of the electrical supply
to other items of the plant and equipment in general.

2

A power circuit must be provided for connection of the unit. This
circuit must be protected with the required safety devices, i.e. a
circuit breaker, a slow blow fuse on each phase and an earth
leak detector. Recommended fuses are mentioned on the wiring
diagram supplied with the unit. 

Connection of the water-cooled water chiller power 
supply

1

Using the appropriate cable, connect the power circuit to the N,
L1, L2 and L3 terminals of the unit. (cable section 2.5~10 mm

2

)

2

Connect the earth conductor (yellow/green) to the earthing
terminal PE.

Minimum 

water volume (l)

Minimum 

water flow

Maximum 

water flow

EWLP012

62.1

17 l/min

69 l/min

EWLP020

103

29 l/min

115 l/min

EWLP026

134

38 l/min

153 l/min

EWLP030

155

45 l/min

179 l/min

EWLP040

205

57 l/min

229 l/min

EWLP055

268

77 l/min

307 l/min

EWLP065

311

89 l/min

359 l/min

The water pressure should not exceed the maximum
working pressure of 10 bar.

NOTE

Provide adequate safeguards in the water circuit to
make sure that the water pressure will never exceed
the maximum allowable working pressure.

1

Switch box (with connector X62A on I/O PCB)

2

Sensor cable (length ±1 m)

3

Sensor

4

Remote watercooled condenser

5

Cable

6

Interconnection (IP67)

1

2

3

X62A

X62A

1

3

2

6

5

4

All field wiring and components must be installed by a
licensed electrician and must comply with relevant
European and national regulations.

The field wiring must be carried out in accordance with the
wiring diagram supplied with the unit and the instructions
given below.

Be sure to use a dedicated power circuit. Never use a
power supply shared by another appliance.

Switch off the main isolator switch before making any
connections (switch off the circuit breaker, remove or
switch off the fuses).

4PW61665-1_digital_EN.book  Page 6  Friday, August 27, 2010  2:13 PM

Summary of Contents for EWLP020KBW1N

Page 1: ...TION MANUAL EWLP012KBW1N EWLP020KBW1N EWLP026KBW1N EWLP030KBW1N EWLP040KBW1N EWLP055KBW1N EWLP065KBW1N Condenserless water cooled water chillers 4PW61665 1_digital_EN book Page 1 Friday August 27 2010...

Page 2: ...arecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet...

Page 3: ...WLP units Technical specifications 1 Electrical specifications 1 Options and features 1 Options Glycol application for chilled water temperature down to 10 C or 5 C BMS connection MODBUS optional kit...

Page 4: ...ut of the unit The equipment is not intended for use in a potentially explosive atmosphere INSPECTING AND HANDLING THE UNIT At delivery the unit should be checked and any damage should be reported imm...

Page 5: ...nd to prevent foreign materials e g mineral oils such as SUNISO and moisture from mixing into the system Vacuum pump use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not f...

Page 6: ...iquid line sightglass is showing some gas bubbles the rough refrigerant charge is sufficient by fine tuning the additional 10 refrigerant charge weight If the liquid line sightglass is showing flash g...

Page 7: ...ular base WATER QUALITY SPECIFICATIONS A corrosion B scale CONNECTING THE WATER CIRCUIT The evaporator is provided with GAS female pipe thread connections for the water inlet and outlet refer to the o...

Page 8: ...uit and cable requirements 1 The electrical power supply to the unit must be arranged so that it can be switched on or off independently of the electrical supply to other items of the plant and equipm...

Page 9: ...040 0 22 EWLP055 0 21 EWLP065 0 20 2 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current...

Page 10: ...Installation manual 8 EWLP012 065KBW1N Condenserless water cooled water chillers 4PW61665 1 07 2010 NOTES 4PW61665 1_digital_EN book Page 8 Friday August 27 2010 2 13 PM...

Page 11: ...water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergency shut down Switch off the ci...

Page 12: ...4PW61665 1 07 2010 Copyright 2010 Daikin 4PW61665 1_digital_EN book Page 1 Friday August 27 2010 2 13 PM...

Reviews: