Daikin EWAQ080DAYN Operation Manual Download Page 22

Operation manual

21

EWAQ080~260DAYN

Packaged air-cooled water chillers

4PW35556-1E

5.6

5.7

5.8

5.9a

5.9b

5.10

5.11

5.12

Symptom 5.6:  Superheat temperature is not correct

(

1A9

/

2A9:SUPERHEAT ERR

)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Superheat temperature is too high.

Check if the unit has enough 
refrigerant (no foaming visible in 
sight glass).
Check if the suction temperature 
sensor of the EEV driver is in the 
holder in the suction tube and not 
hanging loose.

Superheat temperature is too low.

Check if the EEV driver or the control 
motor of EEV is wired correctly and 
operating.

The sensed suction temperature is 
more than 2°C higher than the 
entering water temperature of the 
evaporator.

Check if the suction temperature 
sensor of the controller is in its 
holder and not hanging loose.

Symptom 5.7:  High-pressure switch and high pressure setback

(

1E3

/

2E3:HIGH PRESSURE SW

1E3

/

2E3:HP SETBACK

)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Condenser fan does not operate 
properly.

Check that the fans turn freely. Clean 
if necessary.

Dirty or partially blocked condenser.

Remove any obstacle and clean 
condenser coil using brush and 
blower.

Inlet air temperature of the 
condenser is too high.

The air temperature measured at the 
inlet of the condenser may not 
exceed 43°C.

Fan turning in the wrong direction.

Two phases of the power supply to 
the fan motor must be inverted (by a 
licensed electrician).

RESET

After pressure rise, this safety resets 
automatically, but the controller still 
needs to be reset.

Symptom 5.8:  Low pressure 

(

1E4

/

2E4:LOW PRESSURE

)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Water flow to water heat exchanger 
too low.

Increase the water flow.

Shortage of refrigerant.

Check for leaks and refill refrigerant, 
if necessary.

Unit is working out of its operation 
range.

Check the operation conditions of 
the unit.

Inlet temperature to the water heat 
exchanger is too low.

Increase the inlet water temperature.

Dirty evaporator.

Clean the evaporator, or call your 
local dealer.

Low pressure safety setting too high.

Refer to the installation manual 
"Customization in the service menu", 
paragraph "Setting of the minimum 
outlet water temperature" for correct 
values.

Flowswitch is not working or no 
water flow.

Check the flowswitch and the water 
pump.

RESET

After pressure rise, this safety resets 
automatically, but the controller still 
needs to be reset.

Symptom 5.9a:  The compressor does not work (only for SJ161-4)

(Compressor thermal protection is activated)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The compressor motor coil 
temperature is too high because the 
compressor motor takes 
(demands/needs) too much current 
and is not sufficiently cooled by 
refrigerant.

Make sure there are no refrigerant 
leaks.
After repairing leaks, charge the unit 
with additional refrigerant until the 
sight glass in the liquid line shows no 
foaming.

Make sure the unit operates within 
its operating range (too high ambient 
or too high water temperature).

Make sure the compressor motor is 
not locked.

RESET

After temperature decrease the 
thermal protector is reset 
automatically and the compressor 
will start again. This is not detected 
by the controller.

If the protector is activated 
frequently, call your local dealer.

Symptom 5.9b:  Compressor safety (only for SJ161-4)

(

1E6

/

2E6:COMPR 1/2 SAFETY)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Failure of one of the phases.

Check fuses on the supply panel or 
measure the supply voltage.

Voltage too low.

Measure the supply voltage.

The unit is working out of its range.

Make sure the unit operates within 
its operating range.

Overload of motor.

Reset. If the failure persists, call your 
local dealer.

There is a short circuit.

Check the wiring.

RESET

Pull the black handle on the 
compressor fuse inside the switch 
box and reset the controller.

Symptom 5.10:  Compressor safety (only for SJ180-4~SJ240-4 and SJ300-4)

(

1E6

/

2E6:COMPR 1

/

2 SAFETY

)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

The compressor motor coil 
temperature is too high because the 
compressor motor takes 
(demands/needs) too much current 
and is not sufficiently cooled by 
refrigerant.

Make sure there are no refrigerant 
leaks.
After repairing leaks, charge the unit 
with additional refrigerant until the 
sight glass in the liquid line shows no 
foaming.

Make sure the unit operates within 
its operating range (too high ambient 
or too high water temperature).

Make sure the compressor motor is 
not locked.

RESET

After temperature decrease, a 5 
minute delay is activated. After this 
delay the relay in the electronic 
protection module (EPM) is pulled in. 
The controller needs to be reset 
manually.

Failure of one of the phases.

Check fuses on the supply panel or 
measure the supply voltage.

Voltage too low.

Measure the supply voltage.

The unit is working out of its range.

Make sure the unit operates within 
its operating range.

Overload of motor.

Reset. If the failure persists, call your 
local dealer.

The compressor is running in 
reverse phase (only for SJ240-
SJ300)

Check the wiring.

There is a short circuit.

Check the wiring.

RESET

Pull the black handle on the 
compressor fuse inside the switch 
box and reset the controller.

Symptom 5.11:  Discharge thermal protector is activated 

(

1F3

/

2F3:HIGH DISCH TEMP1

/

2

)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Unit is working outside the operation 
range.

Check the operation condition of the 
unit.

The unit is undercharged.

Check if there are no refrigerant 
leaks.
After repairing leaks, charge the unit 
with additional refrigerant until the 
sight glass in the liquid line shows no 
foaming.

RESET

After temperature decrease, the 
safety resets automatically but the 
controller still needs to be reset.

Symptom 5.12:  Reverse phase protector is activated

(

1U1

/

2U1:REV PHASE PROT

)

P

OSSIBLE

 

CAUSES

C

ORRECTIVE

 

ACTION

Two phases of the power supply are 
connected in the wrong phase 
position.

Invert two phases of the power 
supply (by licensed electrician).

One phase is not connected 
properly.

Check the connection of all phases.

Voltage too low.

Measure the supply voltage.

RESET

After inverting two phases or fixing 
the power supply cables properly, 
the protector is reset automatically, 
but the controller still needs to be 
reset.

Summary of Contents for EWAQ080DAYN

Page 1: ...OPERATION MANUAL EWAQ080DAYN EWAQ100DAYN EWAQ130DAYN EWAQ150DAYN EWAQ180DAYN EWAQ210DAYN EWAQ240DAYN EWAQ260DAYN Packaged air cooled water chillers...

Page 2: ...make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations listed in Checks before initial start u...

Page 3: ...15 15 20 20 13 13 13 13 15 15 15 15 Phase 3 Frequency Hz 50 Voltage V 400 Nominal running current Circuit 1 Circuit 2 A A 39 39 51 51 35 35 35 35 39 39 39 39 Control and fan motor Phase 1 Frequency Hz...

Page 4: ...erature sensor R1T 29 Pump optional 2 Condenser 15 Drier charge valve 30 Buffertank optional 3 Compressor 16 Power supply intake 31 Expansion vessel optional 4 Electronic expansion valve sight glass w...

Page 5: ...ansion valve The expansion valve brings the liquid refrigerant to a pressure at which it can easily be evaporated in the evaporator p p p M12C M11C p p p M22C M21C M15F M13F M14F M25F M23F M24F B1PH B...

Page 6: ...and reliable protection against overheating overloading phase loss and phase reversal The controller will detect the shut down of the compressor The controller needs to be reset manually Reverse phas...

Page 7: ...S Fan overcurrent relay for circuit 1 K15F Fancontactor for circuit 1 only for EWAQ080 100 and EWAQ180 260 K15S Fan overcurrent relay for circuit 1 only for EWAQ080 100 and EWAQ180 260 K16F Fancontact...

Page 8: ...her material 11 Power supply voltage Check the power supply voltage on the local supply panel The voltage should correspond to the voltage on the identification label of the unit 12 Water connection C...

Page 9: ...l operational information on page 9 Adjusting the temperature setpoint on page 10 Resetting the unit on page 10 Setting the language If desired the operating language can be changed to any of the foll...

Page 10: ...ond number stands for the dew point saturation temperature in degrees Celsius LOWNOISE at the bottom of the first screen the status of the lownoise setting is shown Y active or N not active 6 Press th...

Page 11: ...network safeties When a unit or circuit safety occurs the compressor is shut down The safeties menu will indicate which safety is activated The UNIT STATUS screen of the readout menu will indicate OF...

Page 12: ...1 and the capacity of the unit To consult information about the unit status of circuit 2 only for EWAQ130 260 To consult actual operational informa tion about the current Ampere and voltage of the un...

Page 13: ...in BUZZER IF SAFETY YES _ ADVANCED BACKLIGHT TIME 05min GRAPHIC READOUT YES ENTER SERVICE PASSWORD 0000 TO LOGIN To check the actual value of the general software timer To check the actual value of th...

Page 14: ...T HISTORY 002 C21RH 00000hCS 00000 _ UNIT HISTORY 002 C22RH 00000hCS 00000 _ UNIT HISTORY 002 AI1 NONE AI2 NONE _ UNIT HISTORY 002 AI3 NONE AI4 NONE To consult time and date information To consult add...

Page 15: ...nex I on page 25 Defining and activating the control mode The unit is equipped with a thermostat which controls the cooling capacity of the unit Select the appropriate mode MANUAL CONTROL manual contr...

Page 16: ...ntrol The DUAL PUMP screen of the usersettings menu allows the user to define the steering of two pumps for this to be possible a changeable digital output has to be configured for a second pump in th...

Page 17: ...however will only come into operation if another unit is in alarm another unit is in DISCONNECT ON OFF mode the setpoint is not reached when all other units have been running on full capacity for some...

Page 18: ...TIME M RT 120 sec starts counting when the compressor has started During the count down the compressor will not be switched off by the thermostat function To check the actual value of the software tim...

Page 19: ...witch setpoint 1 or setpoint 2 REMOTE ON OFF indicates the position of the remote on off switch CAP LIMIT 25 50 75 SET indicates the position of the enable disable capacity limitation switches LOW NOI...

Page 20: ...to enter and select the next number When pressing the key on the last number the confirmation of the new password is completed TROUBLESHOOTING This section provides useful information for diagnosing a...

Page 21: ...vated and alarm messages are displayed The ON LED is broken Contact your local dealer Message safety menu Symptom POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Com...

Page 22: ...or is not locked RESET After temperature decrease the thermal protector is reset automatically and the compressor will start again This is not detected by the controller If the protector is activated...

Page 23: ...ges are displayed Voltage is too low Test the voltage in the supply panel and if necessary in the electrical compartment of the unit voltage drop due to supply cables is too high POSSIBLE CAUSES CORRE...

Page 24: ...damage and make sure that the hole diameter size all over the filter surface is still 1 0 mm maximum Water sensors Check that all the water sensors are correctly fixed into the inlet and outlet water...

Page 25: ...EWAQ080 260DAYN Packaged air cooled water chillers 4PW35556 1E Operation manual 24 NOTES...

Page 26: ...e DICN setup Example A DICN setup with 2 units means load up requests of maximum 2 compressors at a time INLET CONTROL Default value Lower limit Upper limit Units 1 circuit Units 2 circuits Step diffe...

Page 27: ...TING SETPOINT MODE AMBIENT MAXPOS 03 0 NEG 00 0 RF 020 0 SLOPE 006 0 12 0 C 13 5 C 15 0 C 18 0 C 17 5 C 10 0 C 20 0 C 6 0 C 3 0 C 10 0 C A B AMBIENT _ FLOATING SETPOINT MODE CH AI SLOPE NTC MAXPOS 03...

Page 28: ...0 INLET WATER 013 6 OUTLET WATER 007 0 _v UNIT HISTORY 001 1E6 COMPR 1 SAFETY 22h33m00s 23 03 06 COOL INLSP1 012 0 _ UNIT INFO FAN ST VA Y 2PUMP Y HEATERTAPE Y FAN DO ST 2 DO INV 2 ENTER PASSWORD PAS...

Page 29: ...NE OPEN DO5 NONE OPEN _ UNIT STATUS C11 OFF SAFETY ACT C12 OFF SAFETY ACT UNIT CAPACITY 000 _ UNIT STATUS C21 OFF SAFETY ACT C22 OFF SAFETY ACT _ C1 ACT PRESSURES HP1 019 0b 050 8 LP1 004 4b 05 2 FAN1...

Page 30: ...4PW35556 1E Copyright Daikin...

Reviews: