Daikin EWAP400MBYNN Installation Manual Download Page 7

EWAP400~540MBYNN

Packaged air-cooled water chillers

4PW22678-1B

Installation manual

4

A field supplied blow down port for flushing fluid and
accumulated material from inside the filter can be connected on
the filter end cap.

Connecting the counter pipes
Weld the supplied counter pipes to the ends of the water circuit
and connect to the unit with the provided 

 couplings.

2

Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down.

3

Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing.

4

Shut-off valves should be provided at the unit so that normal
servicing can be accomplished without draining the system.

5

Vibration eliminators in all water piping connected to the chiller
are recommended to avoid straining the piping and transmitting
vibration and noise.

6

For units in a DICN configuration with common leaving water
control, be sure to foresee an insertion hole for the additional
water temperature sensor. Sensor and sensor holder are
optional parts.

The insertion hole shall be 1/4"GAS female thread and should
be located in the mixed waterflow of the chillers.
Make sure that the sensortip is in the waterflow and that you
have a length of straight pipe (L) of at least 5x the pipe diameter
(A) before the sensor.

Choose the position of insertion in a way that the cable length of
the sensor (12 m) is long enough to be attached to the master
PCB.

C

ONNECTING

 

THE

 

WATER

 

CIRCUIT

The evaporator is foreseen of flexible joints for the water inlet and
outlet (refer to the outlook diagram). Evaporator water connections
are to be made in accordance with the outlook diagram, respecting
the water in- and outlet.

If air or dust gets in the water circuit, problems may occur. Therefore,
always take into account the following when connecting the water
circuit:

1.

Use clean pipes only.

2.

Hold the pipe end downwards when removing burrs.

3.

Cover the pipe end when inserting it through a wall so that no dust
and dirt enter.

W

ATER

 

CHARGE

FLOW

 

AND

 

QUALITY

To  assure proper operation of the unit, the water flow through the
evaporator must be within the operation range as specified in the
table below and a minimum water volume is required in the system.

The minimum water volume v [l] in the system should fullfill the
criteria below:

The water quality must be in accordance with the specifications listed
in the table below.

P

IPING

 

INSULATION

The complete water circuit, inclusive all piping, must be insulated to
prevent condensation and reduction of the cooling capacity.

Protect the water piping against water freezing during winter period
(e.g. by using a glycol solution or heatertape).

Minimum water flow

Maximum water flow

EWAP400

565 l/min

2265 l/min

EWAP460

670 l/min

2680 l/min

EWAP540

775 l/min

3100 l/min

Victaulic

®

ØA

 5 x ØA

>30m

m

>3

0m

m

69m

m

69

m

m

>30m

m

69m

m

v>(Q/2)xt/(Cx

T)

Q

highest cooling capacity of the unit in lowest capacity step within 
the range of application (kW)

t

antirecycling timer of unit (AREC)/2(s)=300 s

C

specific heat capacity of the fluidum (kJ/kg°C)=4.186 kJ/kg°C for 
water

T

temperature difference between starting and stopping of the 
compressor.

T=a+2b+c

(for designation of a, b and c, refer to the operation manual)

NOTE

For units in a DICN configuration, the minimum
required water volume in the system must equal the
biggest required minimum volume of every individual
chiller in the system.

circulating 

water

supply 

water

tendency if 

out of criteria

Items to be controlled

pH

 at 25°C

6.8~8.0

6.8~8.0

co

scale

Electrical conductivity

[mS/m]

at 25°C

<40

<30

co

scale

Chloride ion

[mg Cl

/l]

<50

<50

corrosion

Sulfate ion

[mg SO

4

2

  –

/l]

<50

<50

corrosion

M-alkalinity (pH 4.8)

[mg CaCO

3

/l]

<50

<50

scale

Total hardness

[mg CaCO

3

/l]

<70

<70

scale

Calcium hardness

[mg CaCO

3

/l]

<50

<50

scale

Silica ion

[mg SiO

2

/l]

<30

<30

scale

Items to be referred to

Iron

[mg Fe/l]

<1.0

<0.3

cor 

scale

Copper

[mg Cu/l]

<1.0

<0.1

corrosion

Sulfide ion

[mg S

2–

/l]

not 

detectable

not 

detectable

corrosion

Ammonium ion

[mg NH

4

+

 /l]

<1.0

<0.1

corrosion

Remaining chloride

[mg Cl/l]

<0.3

<0.3

corrosion

Free carbide

[mg CO

2

/l]

<4.0

<4.0

corrosion

Stability index

cor 

scale

The water pressure should not exceed the maximum
working pressure of 10 bar.

NOTE

Provide adequate safeguards in the water circuit to
make sure that the water pressure will never exceed
the maximum allowable working pressure.

Summary of Contents for EWAP400MBYNN

Page 1: ...INSTALLATION MANUAL EWAP400MBYNN EWAP460MBYNN EWAP540MBYNN Packaged air cooled water chillers...

Page 2: ...3 24 V K2P M2P L2 L3 SLAVE 1 F18 K2P F8 F9 74 75 76 77 78 79 N L1 F10 F19 230 V 73 24 V K1P M1P L2 L3 MASTER F20 S1S S6S M K1P F11 F12 74 75 76 77 78 79 S10S M M3P SLAVE 2 M2P SLAVE 1 M1P MASTER R8T L...

Page 3: ...nderung 03 Directives telles que modifi es 04 Richtlijnen zoals geamendeerd 05 Directivas seg n lo enmendado 06 Direttive come da modifica 07 v 08 Directivas conforme altera o em 09 10 Direktiver med...

Page 4: ...grills BMS Connection MODBUS J BUS BACNET LON Inverter fans Heat recovery High ESP fans Features Stepless capacity control 15 100 Evaporator heater tape Glycol application for leaving evaporator wate...

Page 5: ...the unit and the floor is flat to prevent vibration and noise generation 2 The space around the unit is adequate for servicing and the minimum space for air inlet and air outlet refer to the operatio...

Page 6: ...or I beam frame to support the unit on the roof or it can be installed on a concrete base Ground level mounted The unit must be installed on a solid base It is recommended to fix the unit on a concret...

Page 7: ...To assure proper operation of the unit the water flow through the evaporator must be within the operation range as specified in the table below and a minimum water volume is required in the system Th...

Page 8: ...note the following Switch for remote on off Units with status or will be controlled by the remote on off switch connected to the chiller defined as Units with status are controlled by the switch conne...

Page 9: ...not even for a very short period of time before the following pre commissioning checklist is filled out completely tick when checked standard steps to go through before starting the unit 1 Check for...

Page 10: ...s to comply Defining of the changeable digital analog inputs and outputs Besides locked inputs and outputs there are a number of changeable inputs and outputs of which the function can be chosen from...

Page 11: ...from a supervisory system If set to no the supervisory system can only read out values but cannot modify them used to address the PCB indicates the communication protocol If the optional gateway is us...

Page 12: ...ll units the pump runs for a time indicated by the setting Slave 3 S3 is configured to operate when its remote start stop switch S6S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master u...

Page 13: ...em configuration field wiring and terminals for field wiring of this example Purpose Purpose of this system is to keep a buffer at a constant temperature and to feed a load from this buffer One unit s...

Page 14: ...Installation manual 11 EWAP400 540MBYNN Packaged air cooled water chillers 4PW22678 1B NOTES...

Page 15: ...circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergenc...

Page 16: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW22678 1B...

Reviews: