Daikin EWAH TZ D Series Installation, Operation And Maintenance Manual Download Page 43

D

–EIMAC01905-23_00EN - 43/53 

MAINTENANCE 

This chiller must be maintained by qualified technicians. Before beginning any work on the system, the personnel 
shall assure that all security precautions have been taken.  

Personel  working  on  the  electrical  or  the  refrigeration  components  must  be  authorized,  trained  and  fully  qualified. 
Maintenance and repair requiring the assistance of other skilled personnel should be carried out under the supervision of 
the person competent in the use of flammable refrigerants. Any person conducting servicing or maintenance on a system 
or associated parts of the equipment should be competent according to EN 13313.  

People working on refrigerating systems with flammable refrigerants should have know-how of safety aspects of 
flammable refrigerant handling, supported by evidence of appropriate training. 

Always protect the operating personnel with personal protective equipment appropriate for the tasks to be performed. 
Common individual devices are: helmet, goggles, gloves, caps, safety shoes. Additional individual and group protective 
equipment should be adopted after an adequate analysis of the specific risks in the area of relevance, according to the 
activities to be performed. 
 

Table 17

– General maintenance table

 

Electrical 
components 

Never work on any electrical components until the general supply to the unit has been cut using 
the disconnect switch(es) in the control box. The frequency variators are equipped with capacitor 
batteries with a discharge time of 20 minutes; after disconnecting power, wait 20 minutes before 
opening the control box. 

Refrigerating 
system 

Following precautions should be taken before working on the refrigerant circuit: 
— Obtain permit for hot work (if required); 
— Ensure that no flammable materials are stored in the work area and that no ignition sources 
are present anywhere in the work area; 
— Ensure that suitable fire extinguishing equipment is available; 
— Ensure that the work area is 

properly ventilated

 before working on the refrigerant circuit or 

before welding, brazing or soldering work; 
— Ensure that the leak detection equipment being used is non-sparking, adequately sealed or 
intrinsically safe; 
— Ensure that all maintenance staff have been instructed. 
The following procedure should be followed before working on the refrigerant circuit:  

1. 

Remove refrigerant (specify the residual pressure); 

2. 

Purge circuit with 

inert gas

 (e.g. nitrogen); 

3. 

evacuate to a pressure of 0,3 (abs.) bar (or 0,03 MPa); 

4. 

Purge again with 

inert gas 

(e.g. nitrogen); 

5. 

Open the circuit 

The area should be checked with an appropriate refrigerant detector prior to and during any hot 
work to make the technician aware of a potentially flammable atmosphere.  
If  compressors  or  compressor  oils  are  to  be  removed,  it  should  be  ensured  that  it  has  been 
evacuated to an acceptable level to ensure that there is no flammable refrigerant remaining within 
the lubricant. 

Only refrigerant recovery equipment designed for use with  flammable refrigerants should 
be employed. 

If the national rules or regulations permit the refrigerant to be drained, this should be done safely, 
using  a  hose,  for  example,  through  which  the  refrigerant  is  discharged  into  the  outside 
atmosphere  in  a  safe  area.  It  should  be  ensured  that  an  inflammable  explosive  refrigerant 
concentration cannot occur in the vicinity of an ignition source or penetrate into a building under 
any circumstance. 
In  the  case  of  refrigerating  systems  with  an  indirect  system,  the  heat -transfer  fluid  should  be 
checked for the possible presence of refrigerant. 
After  any  repair  work,  the  safety  devices,  for  example  refrigerant  detectors  and  mechanical 
ventilation systems, should be checked and the results recorded.  
It should be ensured that any missing or illegible label on components of the refrigerant circuit is 
replaced. 
Sources of ignition should not be used when searching for a refrigerant leak. 

7.1 

Routine maintenance 

This chiller must be maintained by qualified technicians. Before begi nning any work on the system the personnel shall  
assure that all security precautions have been taken.   
Neglecting unit maintenance, could degrade all parts of the units (coils, compressors, frames, pipes, etc..) with negative 
effect on performances and functionality. 

There  are  two  different  levels  of  maintenance,  which  can  be  chosen  according  to  the  type  of  application  (critical/non 
critical) or to the installation environment (highly aggressive or not). 
Examples of critical applications are process cooling, data centres, etc. 

Highly Aggressive Environments can be defined as the follows: 

  Industrial environment (with possible concentration of fumes result of combustion and chemical process)  

Summary of Contents for EWAH TZ D Series

Page 1: ...3 Supersedes Telep t s haszn lati s karbantart si tmutat Air cooled chiller with inverter driven screw compressor EWAH TZ D EWAD TZ D EWAS TZ D EWFH TZ D EWFD TZ D EWFS TZ D Installation Operation and...

Page 2: ...stem 33 Introduction and system description P ID 33 Coolant quality requirements 36 First operations at unit commissioning start 36 Free cooling purge valve related 37 Operations in case of failure 37...

Page 3: ...ydronic Free cooling P ID 35 Fig 26 Description of labels applied on the electrical panel small 40 Fig 27 Description of labels applied on the electrical panel medium 41 Fig 28 Description of labels a...

Page 4: ...D EIMAC01905 23_00EN 4 53 Fig 1 Refrigerant circuit diagram P ID MONO circuit units...

Page 5: ...CTRONIC EXPANSION VALVE 12 ELECTRONIC EXPANSION VALVE 13 BPHE EVAPORATOR 14 PRESSURE RELIEF VALVE Pset 15 5 bar 15 ACCESS FITTING 16 PRESSURE GAUGE OPTIONAL 17 ANGLE VALVE 18 ANTIVIBRATION JOINT only...

Page 6: ...D EIMAC01905 23_00EN 6 53 Fig 2 Refrigerant circuit diagram P ID DUAL circuit units...

Page 7: ...IZER ELECTRONIC EXPANSION VALVE 12 ELECTRONIC EXPANSION VALVE 13 SHELL TUBES EVAPORATOR 14 PRESSURE RELIEF VALVE Pset 15 5 bar 15 ACCESS FITTING 16 PRESSURE GAUGE OPTIONAL 17 ANGLE VALVE 18 ANTIVIBRAT...

Page 8: ...TWO WAY VALVE MOTORIZED u WATER FILTER v FREECOOLING COIL La WATER IN LINE Lh WATER IN MANIFOLD Lc WATER IN COIL Ld WATER OUT COIL FLEXIBLE Le WATR OUT MANIFOLD Lf FREECOOLING COIL BYPASS Lg EVAPORATO...

Page 9: ...IQ 25 5 10 80 C LOW PRESSURE 15 5 20 80 C WATER CIRCUITS WATER IN OUT 10 15 55 C Fig 4 Description of the labels applied to the electrical panel Table 5 Label Identification 1 Manufacturer s logo 5 Ca...

Page 10: ...install it outdoors if it is intended for use indoors 16 Do not use cables with inadequate sections nor extension cord connections even for very short periods or emergencies 17 For units with power co...

Page 11: ...quid refrigerant evaporates to cool the water EWFD TZD EWFH TZD and EWFS TZD ranges are equipped with hydronic free cooling systems When free cooling mode is active below a specific OAT water glycol m...

Page 12: ...le or toxic materials shall be stored as required by national regulations Open naked flames shall not be permitted in machinery rooms except for welding brazing or similar activity and then only provi...

Page 13: ...0 C whichever is more critical shall be set to 25 of the LFL The detector shall continue to activate at higher concentrations Table 8 R1234ze E LFL value Refrigerant LFL Pre set alarm R1234ze E 0 303...

Page 14: ...inspection by the transport company representative is carried out Immediately report the damage to the manufacturer representative a set of photographs is helpful in recognizing responsibility Unit r...

Page 15: ...values represent a guideline please refer to the Chiller Selection Software CSS for real operating limits for the specific model For free cooling units the free cooling mode can be activated only whe...

Page 16: ...D EIMAC01905 23_00EN 16 53 Fig 5 EWAH TZD Blue unit envelope Fig 6 EWAH TZD Silver unit envelope...

Page 17: ...Option 187 high evaporator leaving water temperature Ref 3 Operation requires option 142 High ambient temperature kit Ref 4 Operation at outside ambient air temperature 5 C requires option 229 fan spe...

Page 18: ...D EIMAC01905 23_00EN 18 53 Fig 9 EWAD TZD Silver unit envelope Fig 10 EWAD TZD Gold and Platinum unit envelope...

Page 19: ...or leaving water temperature Ref 3 Operation requires option 142 High ambient temperature kit Ref 4 Operation at outside ambient air temperature 5 C requires option 229 fan speed modulation or option...

Page 20: ...D EIMAC01905 23_00EN 20 53 Fig 12 EWAS TZD Silver unit envelope Fig 13 EWAS TZD Gold and Platinum unit envelope...

Page 21: ...uires Option 187 high evaporator leaving water temperature Ref 3 Operation requires option 142 High ambient temperature kit The charts shown in these pages constitute a guideline on operating limits i...

Page 22: ...High ambient temperature kit The charts shown in these pages constitute a guideline on operating limits in the range Refer to the CSS selection software for the actual operating limits in the working...

Page 23: ...ove sea level Contact the factory if the unit is to be installed at altitudes 1000 m above sea level Table 11 Minimum percentage of glycol in case of low ambient temperature AAT 2 3 8 15 20 A 1 10 20...

Page 24: ...iller DAE units can be installed without charge restrictions into machinery rooms or in open air location class III According to EN 378 1 a mechanical vent on the secondary circuit s has to be install...

Page 25: ...e unit Lifting ropes chains must have a minimum lenght as it is specified in the drawing The installer has the responsibility for proper sizing of rigging equipment and its proper use It is recommende...

Page 26: ...D EIMAC01905 23_00EN 26 53 Unit with 6 lifting points The drawing shows only the 10 fans version The lifting mode is the same regardless of the number of fans...

Page 27: ...awing shows only the 16 fans version The lifting mode is the same regardless of the number of fans Unit with 12 lifting points The drawing shows only the 24 fans version The lifting mode is the same r...

Page 28: ...unit is installed in places that are easily accessible to people and animals protection grids for the unit shall be installed To ensure the best performance on the installation site the following pre...

Page 29: ...ng conditions and deliver the maximum available capacity under any given circumstances even if the lateral distance is lower than recommended unless the operating conditions should affect personnel sa...

Page 30: ...normally In order to avoid the hot air recirculation due to dominant winds the installation where all chillers are aligned to the dominant wind is preferred see figure below Multiple chiller installed...

Page 31: ...owest number of elbows and the lowest number of vertical changes of direction In this way installation costs are reduced and system performance is improved Water system must have Anti vibration mounti...

Page 32: ...f case of unit replacement the entire water system must be emptied and cleaned before the new unit is installed Regular tests and proper chemical treatment of water are recommended before starting up...

Page 33: ...ed to allow flushing of the piping system The bypass can be used during maintenance to isolate the heat exchanger without disrupting flow to other units Any damage due to the presence of foreign bodie...

Page 34: ...e free cooling effect System changeover is controlled by embedded unit controller depending on operating conditions and unit setpoint Between mechanical and freecooling operation the water side pressu...

Page 35: ...d VALVE f SAFETY VALVE 10 BAR 1 2 MF h AIR VENT 3 8 NPT TBC i DRAIN 1 4 NPT r WATER FILTER t TWO WAY VALVE MOTORIZED u WATER FILTER v FREECOOLING COIL La WATER IN LINE Lh WATER IN MANIFOLD Lc WATER I...

Page 36: ...osion inhibitor is necessary for ensured coil protection e g those based on monopropylene glycol or sodium molybdate Maximum opening for strainer mesh shall be 1mm The most appropriate water treatment...

Page 37: ...coils with nitrogen at 1 2 barg 4 9 Evaporator and heat recovery exchangers anti freeze protection All evaporators are supplied with a thermostatically controlled anti freeze electrical resistance whi...

Page 38: ...ution system Should this product need to be connected to a low voltage public distribution system specific additional measures will have to be taken to avoid interference with other sensitive equipmen...

Page 39: ...the system is switched off and the main switch of the unit is open Failure to observe this rule could result in serious personal injury 5 4 Cable requirements The cables connected to the circuit brea...

Page 40: ...logo 9 Copper conductors 2 Gas type 10 Closed valves warning 3 Hazardous Voltage warning 11 Warning label 4 Sticker high voltage flash 12 Electrical resistence warning 5 Non flammable gas sticker if p...

Page 41: ...ixing 8 Unit nameplate data 4 Gas type 16 Flammable label acording to EN ISO 7010 W021 5 Non flammable gas sticker if present Fig 28 Description of labels applied on the electrical panel large LARGE E...

Page 42: ...or unqualified personnel to access the unit it is forbidden to access the electrical components without having opened the unit main switch and switched off the power supply it is forbidden to access t...

Page 43: ...e following procedure should be followed before working on the refrigerant circuit 1 Remove refrigerant specify the residual pressure 2 Purge circuit with inert gas e g nitrogen 3 evacuate to a pressu...

Page 44: ...place if necessary X Verify that all electrical terminals are tight Tighten if necessary X Clean inside the electrical control board X Visual inspection of components for any signs of overheating X Ve...

Page 45: ...etc X Refrigeration circuit Check for any refrigerant leakage X Verify refrigerant flow using the liquid sight glass Sight glass full X Verify filter dryer pressure drop X Verify oil filter pressure d...

Page 46: ...sage until it comes out clean Microchannels fins are stronger than traditional tube fin coil fins but still need to be handled with care 8 It is possible to clean a coil with a high pressure washer ma...

Page 47: ...atures down to 20 C However they should not be switched on at temperatures lower than 0 C unless the following procedure is executed Open the switchbox only trained technicians should perform this ope...

Page 48: ...its operating limits or not performing proper maintenance according to this manual can void the warranty Observe the following points in particular in order to conform to warranty limits 1 The unit ca...

Page 49: ...frigerated water Yes No N A Piping completion Install the water filter even when not supplied at the inlet of the exchangers Install a flow switch calibrate and test off on off switching according to...

Page 50: ...D For chillers belonging to this category some local regulations require a periodic inspection by an authorized agency Please check with your local requirements After a period of 10 years the manufact...

Page 51: ...rical panel 1 Fill in with indelible ink the refrigerant charge label supplied with the product as following instructions Any refrigerant charge for each circuit 1 2 3 added during commissioning the t...

Page 52: ...aws implementing the Directive 2012 19 EU RAEE Lead batteries must be collected and sent to specific waste collection centers Avoid the escape of refrigerant gases into the environment by using suitab...

Page 53: ...f its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p...

Reviews: