Daikin EWAH TZ D Series Installation, Operation And Maintenance Manual Download Page 12

D

–EIMAC01905-23_00EN - 12/53 

1.4 

Information about installation 

The chiller has to be installed in open air or machinery room (location classification III). 
To ensure location classification III a mechanical vent on the secondary circuit(s) has to be installed. 
Local building codes and safety standards shall be followed; in absence of local codes and standards refer to EN 378- 
3:2016 as a guide. 
In paragraph “Additional guidelines for safe use of R1234ze(E)” there are provided additional informations that should be  
added to the requirements of safety standards and building codes. 

Additional guidelines for safe use of R1234ze(E) for equipment located in the open air 

Refrigerating systems sited in the open air shall be positioned to avoid leaked refrigerant flowing into a building or otherwise 
endangering people and property. 
The refrigerant shall not be able to flow into any ventilation fresh air opening, doorway, trap door or similar opening in the 
event of a leak. Where a shelter is provided for refrigerating equipment sited in the open air it shall have natural or force d 
ventilation. 
For refrigeration systems installed outside in a location where a release of refrigerant can stagnate e.g. below ground, then 
the installation shall comply with the requirements for gas detection and ventilation of machinery rooms.  

Additional guidelines for safe use of R1234ze(E) for equipment located in a machinery room 

When a machinery room is chosen for the location of the refrigerating equipment it shall be located in accordance with  
local and national regulations. The following requirements (according to EN 378-3:2016) can be used for the assessment. 

 

A risk analysis based on the safety concept for the refrigerating system (as determined by the manufacturer and 
including the charge and safety classification of the refrigerant used) shall be conducted to determine whether it 
is necessary to place the refrigerating system in a separate refrigeration machinery room.  

 

Machinery rooms should not be used as occupied spaces. The building owner or user shall ensure that access 
is permitted only by qualified and trained personnel doing the necessary maintenance to the ma chinery room or 
general plant. 

 

Machinery rooms shall not be used for storage with the exception of tools, spare parts and compressor oil for 
the installed equipment. Any refrigerants, or flammable or toxic materials shall be stored as required by national 
regulations. 

 

Open (naked) flames shall not be permitted in machinery rooms, except for welding, brazing or similar activity 
and then only provided the refrigerant concentration is monitored and adequate ventilation is ensured.  Such 
open flames shall not be left unattended. 

 

A remote switching (emergency type) for stopping the refrigerating system shall be provided outside the room 
(near the door). A similar acting switch shall be located at a suitable location inside the room.  

 

All piping and ducting passing throught floors, ceiling and walls of machinery room shall be sealed. 

 

Hot surfaces shall not exceed a temperature of 80 % of the auto -ignition temperature (in °C) or 100 K less than 
the auto-ignition temperature of the refrigerant, whichever is higher.  

Table 7 

– R1234ze(E) ignition and max temperatures

 

Refrigerant  Auto ignition temperature Maximum surface temperature 

R1234ze(E) 

36 8  °C  

2 6 8  ° C 

 

 

Machinery rooms shall have doors opening outward and sufficient in number to ensure freedom for persons to 
escape in an emergency; the doors shall be tight fitting, self-closing and so designed that they can be opened 
from inside (antipanic system). 

 

Special machinery rooms where the refrigerant charge is above the practical limit for the volume of the room 
shall have a door that either opens directly to the outside air or through a dedicated vestibule equipped with 
self-closing, tight-fitting doors. 

 

The ventilation of machinery rooms shall be sufficient both for normal operating conditions and emergencies. 

 

Ventilation for normal operating conditions shall be in accordance with national regulations.  

 

The emergency mechanical ventilation system shall be activated by a detector(s), located in the machinery 
room. 

o

  This ventilation system shall be: 

 

independent of any other ventilation system on the site. 

 

provided with two independent emergency controls one located outside the machinery room, 
and the other inside. 

o

  The emergency exhaust ventilation fan shall: 

 

Be either in the air flow with the motor outside the airflow, or rated for hazardous areas 
(according to the assessment). 

 

Be located to avoid pressurization of the exhaust ductwork in the machinery room.  

 

not cause sparks to occur if it contacts the duct material. 

o

  Airflow of the emergency mechanical ventilation shall be at least 

𝑉  = 0,014 × 𝑚

2

3

 

 

where 

is the air flow rate in m

3

/s; 

is the mass of refrigerant charge, in kg, in the refrigerating system with the largest charge, any  
part of which is located in the machinery room; 

0.014 is a conversion factor. 

Summary of Contents for EWAH TZ D Series

Page 1: ...3 Supersedes Telep t s haszn lati s karbantart si tmutat Air cooled chiller with inverter driven screw compressor EWAH TZ D EWAD TZ D EWAS TZ D EWFH TZ D EWFD TZ D EWFS TZ D Installation Operation and...

Page 2: ...stem 33 Introduction and system description P ID 33 Coolant quality requirements 36 First operations at unit commissioning start 36 Free cooling purge valve related 37 Operations in case of failure 37...

Page 3: ...ydronic Free cooling P ID 35 Fig 26 Description of labels applied on the electrical panel small 40 Fig 27 Description of labels applied on the electrical panel medium 41 Fig 28 Description of labels a...

Page 4: ...D EIMAC01905 23_00EN 4 53 Fig 1 Refrigerant circuit diagram P ID MONO circuit units...

Page 5: ...CTRONIC EXPANSION VALVE 12 ELECTRONIC EXPANSION VALVE 13 BPHE EVAPORATOR 14 PRESSURE RELIEF VALVE Pset 15 5 bar 15 ACCESS FITTING 16 PRESSURE GAUGE OPTIONAL 17 ANGLE VALVE 18 ANTIVIBRATION JOINT only...

Page 6: ...D EIMAC01905 23_00EN 6 53 Fig 2 Refrigerant circuit diagram P ID DUAL circuit units...

Page 7: ...IZER ELECTRONIC EXPANSION VALVE 12 ELECTRONIC EXPANSION VALVE 13 SHELL TUBES EVAPORATOR 14 PRESSURE RELIEF VALVE Pset 15 5 bar 15 ACCESS FITTING 16 PRESSURE GAUGE OPTIONAL 17 ANGLE VALVE 18 ANTIVIBRAT...

Page 8: ...TWO WAY VALVE MOTORIZED u WATER FILTER v FREECOOLING COIL La WATER IN LINE Lh WATER IN MANIFOLD Lc WATER IN COIL Ld WATER OUT COIL FLEXIBLE Le WATR OUT MANIFOLD Lf FREECOOLING COIL BYPASS Lg EVAPORATO...

Page 9: ...IQ 25 5 10 80 C LOW PRESSURE 15 5 20 80 C WATER CIRCUITS WATER IN OUT 10 15 55 C Fig 4 Description of the labels applied to the electrical panel Table 5 Label Identification 1 Manufacturer s logo 5 Ca...

Page 10: ...install it outdoors if it is intended for use indoors 16 Do not use cables with inadequate sections nor extension cord connections even for very short periods or emergencies 17 For units with power co...

Page 11: ...quid refrigerant evaporates to cool the water EWFD TZD EWFH TZD and EWFS TZD ranges are equipped with hydronic free cooling systems When free cooling mode is active below a specific OAT water glycol m...

Page 12: ...le or toxic materials shall be stored as required by national regulations Open naked flames shall not be permitted in machinery rooms except for welding brazing or similar activity and then only provi...

Page 13: ...0 C whichever is more critical shall be set to 25 of the LFL The detector shall continue to activate at higher concentrations Table 8 R1234ze E LFL value Refrigerant LFL Pre set alarm R1234ze E 0 303...

Page 14: ...inspection by the transport company representative is carried out Immediately report the damage to the manufacturer representative a set of photographs is helpful in recognizing responsibility Unit r...

Page 15: ...values represent a guideline please refer to the Chiller Selection Software CSS for real operating limits for the specific model For free cooling units the free cooling mode can be activated only whe...

Page 16: ...D EIMAC01905 23_00EN 16 53 Fig 5 EWAH TZD Blue unit envelope Fig 6 EWAH TZD Silver unit envelope...

Page 17: ...Option 187 high evaporator leaving water temperature Ref 3 Operation requires option 142 High ambient temperature kit Ref 4 Operation at outside ambient air temperature 5 C requires option 229 fan spe...

Page 18: ...D EIMAC01905 23_00EN 18 53 Fig 9 EWAD TZD Silver unit envelope Fig 10 EWAD TZD Gold and Platinum unit envelope...

Page 19: ...or leaving water temperature Ref 3 Operation requires option 142 High ambient temperature kit Ref 4 Operation at outside ambient air temperature 5 C requires option 229 fan speed modulation or option...

Page 20: ...D EIMAC01905 23_00EN 20 53 Fig 12 EWAS TZD Silver unit envelope Fig 13 EWAS TZD Gold and Platinum unit envelope...

Page 21: ...uires Option 187 high evaporator leaving water temperature Ref 3 Operation requires option 142 High ambient temperature kit The charts shown in these pages constitute a guideline on operating limits i...

Page 22: ...High ambient temperature kit The charts shown in these pages constitute a guideline on operating limits in the range Refer to the CSS selection software for the actual operating limits in the working...

Page 23: ...ove sea level Contact the factory if the unit is to be installed at altitudes 1000 m above sea level Table 11 Minimum percentage of glycol in case of low ambient temperature AAT 2 3 8 15 20 A 1 10 20...

Page 24: ...iller DAE units can be installed without charge restrictions into machinery rooms or in open air location class III According to EN 378 1 a mechanical vent on the secondary circuit s has to be install...

Page 25: ...e unit Lifting ropes chains must have a minimum lenght as it is specified in the drawing The installer has the responsibility for proper sizing of rigging equipment and its proper use It is recommende...

Page 26: ...D EIMAC01905 23_00EN 26 53 Unit with 6 lifting points The drawing shows only the 10 fans version The lifting mode is the same regardless of the number of fans...

Page 27: ...awing shows only the 16 fans version The lifting mode is the same regardless of the number of fans Unit with 12 lifting points The drawing shows only the 24 fans version The lifting mode is the same r...

Page 28: ...unit is installed in places that are easily accessible to people and animals protection grids for the unit shall be installed To ensure the best performance on the installation site the following pre...

Page 29: ...ng conditions and deliver the maximum available capacity under any given circumstances even if the lateral distance is lower than recommended unless the operating conditions should affect personnel sa...

Page 30: ...normally In order to avoid the hot air recirculation due to dominant winds the installation where all chillers are aligned to the dominant wind is preferred see figure below Multiple chiller installed...

Page 31: ...owest number of elbows and the lowest number of vertical changes of direction In this way installation costs are reduced and system performance is improved Water system must have Anti vibration mounti...

Page 32: ...f case of unit replacement the entire water system must be emptied and cleaned before the new unit is installed Regular tests and proper chemical treatment of water are recommended before starting up...

Page 33: ...ed to allow flushing of the piping system The bypass can be used during maintenance to isolate the heat exchanger without disrupting flow to other units Any damage due to the presence of foreign bodie...

Page 34: ...e free cooling effect System changeover is controlled by embedded unit controller depending on operating conditions and unit setpoint Between mechanical and freecooling operation the water side pressu...

Page 35: ...d VALVE f SAFETY VALVE 10 BAR 1 2 MF h AIR VENT 3 8 NPT TBC i DRAIN 1 4 NPT r WATER FILTER t TWO WAY VALVE MOTORIZED u WATER FILTER v FREECOOLING COIL La WATER IN LINE Lh WATER IN MANIFOLD Lc WATER I...

Page 36: ...osion inhibitor is necessary for ensured coil protection e g those based on monopropylene glycol or sodium molybdate Maximum opening for strainer mesh shall be 1mm The most appropriate water treatment...

Page 37: ...coils with nitrogen at 1 2 barg 4 9 Evaporator and heat recovery exchangers anti freeze protection All evaporators are supplied with a thermostatically controlled anti freeze electrical resistance whi...

Page 38: ...ution system Should this product need to be connected to a low voltage public distribution system specific additional measures will have to be taken to avoid interference with other sensitive equipmen...

Page 39: ...the system is switched off and the main switch of the unit is open Failure to observe this rule could result in serious personal injury 5 4 Cable requirements The cables connected to the circuit brea...

Page 40: ...logo 9 Copper conductors 2 Gas type 10 Closed valves warning 3 Hazardous Voltage warning 11 Warning label 4 Sticker high voltage flash 12 Electrical resistence warning 5 Non flammable gas sticker if p...

Page 41: ...ixing 8 Unit nameplate data 4 Gas type 16 Flammable label acording to EN ISO 7010 W021 5 Non flammable gas sticker if present Fig 28 Description of labels applied on the electrical panel large LARGE E...

Page 42: ...or unqualified personnel to access the unit it is forbidden to access the electrical components without having opened the unit main switch and switched off the power supply it is forbidden to access t...

Page 43: ...e following procedure should be followed before working on the refrigerant circuit 1 Remove refrigerant specify the residual pressure 2 Purge circuit with inert gas e g nitrogen 3 evacuate to a pressu...

Page 44: ...place if necessary X Verify that all electrical terminals are tight Tighten if necessary X Clean inside the electrical control board X Visual inspection of components for any signs of overheating X Ve...

Page 45: ...etc X Refrigeration circuit Check for any refrigerant leakage X Verify refrigerant flow using the liquid sight glass Sight glass full X Verify filter dryer pressure drop X Verify oil filter pressure d...

Page 46: ...sage until it comes out clean Microchannels fins are stronger than traditional tube fin coil fins but still need to be handled with care 8 It is possible to clean a coil with a high pressure washer ma...

Page 47: ...atures down to 20 C However they should not be switched on at temperatures lower than 0 C unless the following procedure is executed Open the switchbox only trained technicians should perform this ope...

Page 48: ...its operating limits or not performing proper maintenance according to this manual can void the warranty Observe the following points in particular in order to conform to warranty limits 1 The unit ca...

Page 49: ...frigerated water Yes No N A Piping completion Install the water filter even when not supplied at the inlet of the exchangers Install a flow switch calibrate and test off on off switching according to...

Page 50: ...D For chillers belonging to this category some local regulations require a periodic inspection by an authorized agency Please check with your local requirements After a period of 10 years the manufact...

Page 51: ...rical panel 1 Fill in with indelible ink the refrigerant charge label supplied with the product as following instructions Any refrigerant charge for each circuit 1 2 3 added during commissioning the t...

Page 52: ...aws implementing the Directive 2012 19 EU RAEE Lead batteries must be collected and sent to specific waste collection centers Avoid the escape of refrigerant gases into the environment by using suitab...

Page 53: ...f its content and the products and services presented therein Specification are subject to change without prior notice Refer to the data communicated at the time of the order Daikin Applied Europe S p...

Reviews: