Daikin EWAA011-016DAV3P Operation Manual Download Page 14

5 Operation

Operation manual

14

EWAA011~016DA + EWYA009~016DA

Packaged air-cooled water chillers

and packaged air to water heat pumps

4P620244-1B – 2021.02

general  fine  but  at  low  ambient  temperatures  too  cold,  raise  the
slope  so  that  leaving  water  temperature  is  heated  increasingly
more at decreasingly lower ambient temperatures.

▪ Change  the 

offset

  to  equally  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures. For example, if leaving water temperature is always
a bit too cold at different ambient temperatures, shift the offset up
to  equally  increase  the  leaving  water  temperature  for  all  ambient
temperatures.

Examples

Weather-dependent curve when slope is selected:

X1

X2

c

d

e

Y1

Y2

Y3

Y4

a

b

Weather-dependent curve when offset is selected:

Y1

Y2

Y3

Y4

X1

X2

a

b

c

d

e

Item

Description

a

WD curve before changes.

b

WD curve after changes (as example):

▪ When  slope  is  changed,  the  new  preferred

temperature  at  X1  is  unequally  higher  than  the
preferred temperature at X2.

▪ When  offset  is  changed,  the  new  preferred

temperature  at  X1  is  equally  higher  as  the  preferred
temperature at X2.

c

Slope

d

Offset

e

Selected weather dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

X1, X2

Examples of outdoor ambient temperature

Y1, Y2,

Y3, Y4

Examples of desired leaving water temperature. The
icon corresponds to the heat emitter for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

Possible actions on this screen

Select slope or offset.

Increase or decrease the slope/offset.

When slope is selected: set slope and go to offset.

When offset is selected: set offset.

Confirm changes and return to the submenu.

5.8.4

Using weather-dependent curves

Configure weather-dependent curves as following:

To define the setpoint mode

To use the weather-dependent curve, you need to define the correct
setpoint mode:

Go to setpoint mode …

Set the setpoint mode to …

Main zone – Heating

[2.4] 

Main zone

 > 

Setpoint

mode

WD heating, fixed cooling

OR 

Weather dependent

Main zone – Cooling

[2.4] 

Main zone

 > 

Setpoint

mode

Weather dependent

Additional zone – Heating

[3.4] 

Additional zone

 >

Setpoint mode

WD heating, fixed cooling

OR 

Weather dependent

Additional zone – Cooling

[3.4] 

Additional zone

 >

Setpoint mode

Weather dependent

To change the type of weather-dependent curve

To change the type for all zones (main + additional), go to [2.E] 

Main

zone

 > 

WD curve type

.

Viewing which type is selected is also possible via [3.C] 

Additional

zone

 > 

WD curve type

To change the weather-dependent curve

Zone

Go to …

Main zone – Heating

[2.5] 

Main zone

 > 

Heating WD

curve

Main zone – Cooling

[2.6] 

Main zone

 > 

Cooling WD

curve

Additional zone – Heating

[3.5] 

Additional zone

 >

Heating WD curve

Additional zone – Cooling

[3.6] 

Additional zone

 >

Cooling WD curve

INFORMATION

Maximum and minimum setpoints

You cannot configure the curve with temperatures that are
higher  or  lower  than  the  set  maximum  and  minimum
setpoints  for  that  zone.  When  the  maximum  or  minimum
setpoint is reached, the curve flattens out.

To fine-tune the weather-dependent curve: slope-offset curve

The  following  table  describes  how  to  fine-tune  the  weather-
dependent curve of a zone:

You feel …

Fine-tune with slope and

offset:

At regular outdoor

temperatures …

At cold outdoor

temperatures …

Slope

Offset

OK

Cold

OK

Hot

Cold

OK

Summary of Contents for EWAA011-016DAV3P

Page 1: ...air to water heat pumps English Operation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAA011 016DAV3P EWAA011 016DAW1P EWAA011 016DAV3P H EWAA011 016DAW1P H EWYA009...

Page 2: ...settings that he used to configure your system Check if he has filled in the installer settings tables If not request him to do so Keep the documentation for future reference Target audience End users...

Page 3: ...ans that electrical and electronic products may NOT be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil...

Page 4: ...and subsequently into the room when you purge air from the heat emitters or collectors 3 About the system Depending on the system layout the system can Heat up a space Cool down a space INFORMATION H...

Page 5: ...ature b Desired room temperature To change the desired leaving water temperature You can use the leaving water temperature setpoint screen to read out and adjust the desired leaving water temperature...

Page 6: ...used for SD cards USB connector With a USB memory stick the installer can Update the software This requires a correct config file on the USB memory stick Import the settings generated by E Configurato...

Page 7: ...Schedule Level 1 5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 4 Space heating cooling Operation mode Operation mode schedule 1 9 Room comfort setpoint Heating comf...

Page 8: ...r unit f Main zone f1 Installed room thermostat type Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Unit operation...

Page 9: ...ormation about the outdoor unit 9 Installer settings Restriction Only for the installer Gives access to advanced settings A Commissioning Restriction Only for the installer Perform tests and maintenan...

Page 10: ...le Unit pump ON OFF In menu You can read out 8 6 Operation modes Current operation mode Example Defrost oil return mode 8 7 About Version information about the system 8 8 Connection status Information...

Page 11: ...g water temperature 1 Go to 2 Main zone or 3 Additional zone Main zone 2 Additional zone 3 2 Adjust the desired leaving water temperature 20 C 2 a b Main zone 12 C 3 a b Additional zone a Actual leavi...

Page 12: ...lear an action set its time as the time of the previous action 4 Confirm the changes Result The schedule for Monday is defined The value of the last action is valid until the next programmed action In...

Page 13: ...mperature the unit relies on its weather dependent curve This curve defines how much the leaving water temperature must be at different outdoor temperatures Because the slope of the curve depends on l...

Page 14: ...ope offset When slope is selected set slope and go to offset When offset is selected set offset Confirm changes and return to the submenu 5 8 4 Using weather dependent curves Configure weather depende...

Page 15: ...have to Keep the area around the unit clean Keep the user interface clean with a soft damp cloth Do NOT use any detergents Regularly check if the water pressure is above 1 bar Refrigerant This produc...

Page 16: ...to the Malfunctioning main menu screen and confirm whether the backup heater can take over the heat load or not When Emergency is set to auto SH reduced DHW off or auto SH reduced DHW on 2 and a heat...

Page 17: ...by installer 10 1 Configuration wizard Setting Fill in System Backup heater type 9 3 1 Emergency 9 5 Number of zones 4 4 Glycol Filled system overview field setting E 0D Backup heater Voltage 9 3 2 C...

Page 18: ......

Page 19: ......

Page 20: ...4P620244 1B 2021 02 Copyright 2020 Daikin 4P620244 1 B 0000000W Verantwortung f r Energie und Umwelt...

Reviews: