5 Operation

Operation manual

15

EWAA004~008D2 + EWYA004~008D2
Packaged air-cooled water chillers
and packaged air to water heat pumps
4P688015-1 – 2022.04

5.8.2

2-points curve

Define the weather-dependent curve with these two setpoints:

▪ Setpoint (X1, Y2)

▪ Setpoint (X2, Y1)

Example

Y1

Y2

X1

X2

a

Item

Description

a

Selected weather dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

X1, X2

Examples of outdoor ambient temperature

Y1, Y2

Examples of desired leaving water temperature. The
icon corresponds to the heat emitter for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

Possible actions on this screen

Go through the temperatures.

Change the temperature.

Go to the next temperature.

Confirm changes and proceed.

5.8.3

Slope-offset curve

Slope and offset

Define the weather-dependent curve by its slope and offset:

▪ Change  the 

slope

  to  differently  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures.  For  example,  if  leaving  water  temperature  is  in
general  fine  but  at  low  ambient  temperatures  too  cold,  raise  the
slope  so  that  leaving  water  temperature  is  heated  increasingly
more at decreasingly lower ambient temperatures.

▪ Change  the 

offset

  to  equally  increase  or  decrease  the

temperature  of  the  leaving  water  for  different  ambient
temperatures. For example, if leaving water temperature is always
a bit too cold at different ambient temperatures, shift the offset up
to  equally  increase  the  leaving  water  temperature  for  all  ambient
temperatures.

Examples

Weather-dependent curve when slope is selected:

X1

X2

c

d

e

Y1

Y2

Y3

Y4

a

b

Weather-dependent curve when offset is selected:

Y1

Y2

Y3

Y4

X1

X2

a

b

c

d

e

Item

Description

a

WD curve before changes.

b

WD curve after changes (as example):

▪ When  slope  is  changed,  the  new  preferred

temperature  at  X1  is  unequally  higher  than  the
preferred temperature at X2.

▪ When  offset  is  changed,  the  new  preferred

temperature  at  X1  is  equally  higher  as  the  preferred
temperature at X2.

c

Slope

d

Offset

e

Selected weather dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

X1, X2

Examples of outdoor ambient temperature

Y1, Y2,

Y3, Y4

Examples of desired leaving water temperature. The
icon corresponds to the heat emitter for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

Possible actions on this screen

Select slope or offset.

Increase or decrease the slope/offset.

When slope is selected: set slope and go to offset.

When offset is selected: set offset.

Confirm changes and return to the submenu.

5.8.4

Using weather-dependent curves

Configure weather-dependent curves as following:

To define the setpoint mode

To use the weather-dependent curve, you need to define the correct
setpoint mode:

Go to setpoint mode …

Set the setpoint mode to …

Main zone – Heating

Summary of Contents for EWAA006D2V3P

Page 1: ...oled water chillers and packaged air to water heat pumps English Operation manual Packaged air cooled water chillers and packaged air to water heat pumps EWAA004D2V3P EWAA006D2V3P EWAA008D2V3P EWYA004...

Page 2: ...to inform you about the settings that he used to configure your system Check if he has filled in the installer settings tables If NOT request him to do so Keep the documentation for future reference T...

Page 3: ...ns that electrical and electronic products may NOT be mixed with unsorted household waste Do NOT try to dismantle the system yourself the dismantling of the system treatment of the refrigerant of oil...

Page 4: ...uit and subsequently into the room when you purge air from the heat emitters or collectors 3 About the system Depending on the system layout the system can Heat up a space Cool down a space INFORMATIO...

Page 5: ...eating cooling On On Room C 2 2 Set operation to On or Off To change the desired room temperature During room temperature control you can use the room temperature setpoint screen to read out and adjus...

Page 6: ...User reference guide 5 Operation INFORMATION Heating is only applicable in case of reversible models 5 1 User interface Overview The user interface has the following components a b c d a Slot for WLA...

Page 7: ...how a help text related to the current page if available e Right dial The LCD shows an arc on the right side of the display when you can use the right dial Turn then press the right dial Change a valu...

Page 8: ...ice High Medium Low Schedule 8 1 Energy data Electricity input Produced heat 7 4 Quiet Mode Schedule Level Restrictions 1 5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maxim...

Page 9: ...r unit f Main zone f1 Installed room thermostat type Unit operation is decided based on the ambient temperature of the dedicated Human Comfort Interface BRC1HHDA used as room thermostat Unit operation...

Page 10: ...ata and information about the outdoor unit 9 Installer settings Restriction Only for the installer Gives access to advanced settings A Commissioning Restriction Only for the installer Perform tests an...

Page 11: ...On or Off 5 5 Reading out information To read out information 1 Go to 8 Information Possible read out information In menu You can read out 8 1 Energy data Produced energy consumed electricity and con...

Page 12: ...Go to 1 Room Room 1 2 Adjust the desired room temperature 21 C 1 a b Room a Actual room temperature b Desired room temperature If scheduling is on after changing the desired room temperature The temp...

Page 13: ...lear the content of a day schedule 1 Select the day of which you want to clear the content For example Friday Mon Sat Wed Fri Thu Tue Sun User defined 1 C 2 Select Delete Delete Edit Copy 3 Select OK...

Page 14: ...ent operation The unit operates weather dependent if the desired leaving water temperature is determined automatically by the outdoor temperature It therefore is connected to a temperature sensor on t...

Page 15: ...t ambient temperatures For example if leaving water temperature is always a bit too cold at different ambient temperatures shift the offset up to equally increase the leaving water temperature for all...

Page 16: ...of a zone You feel Fine tune with setpoints At regular outdoor temperatures At cold outdoor temperatures Y2 a Y1 a X1 a X2 a OK Cold OK Hot You feel Fine tune with setpoints At regular outdoor tempera...

Page 17: ...of the error and the error code is displayed on the screen 2 Press in the error screen Result A long description of the error is displayed on the screen 8 2 To check the malfunction history Conditions...

Page 18: ...emitters or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure tha...

Page 19: ......