Malfunction Indications and Safeties Overview
ESIE11-02
3–10
3
1
3
4
5
Resetting warnings
During normal operation, the display of the controller may start flashing, alternately showing the inlet
water temperature and the following warning code:
■
hc1
: indicates that the compressor 1 requires maintenance: the total running hours of the
compressor 1 (direct parameter
c10
) has exceeded the setting of the timer threshold for
maintenance warning (user parameter
c14
).
■
hc2
: indicates that the compressor 2 requires maintenance: the total running hours of the
compressor 2 (direct parameter
c11
) has exceeded the setting of the timer threshold for
maintenance warning (user parameter
c14
).
To reset the maintenance warning
hc1
or
hc2
, proceed as follows:
Remark
Do not forget to carry out the required maintenance activities after resetting the timers.
Besides resetting timer
c10
and
c11
, it is also possible to reset timer
c15
(running hours of pump) in
the same way.
Step
Action
1
Consult
c10
running hours of compressor 1 or
c11
running hours of compressor 2.
2
When
c10
or
c11
parameter value is displayed, press the
C
and
D
key
simultaneously for 5 seconds. The value of the timer becomes
0
and the warning is reset.
Summary of Contents for EUWY 24KBZW1 Series
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...