The table below describes the patterns and symbols used for the correction factors illustration above.
Glycol freezing
point
The table below contains glycol freezing points for different glycol concentrations.
Pattern
Description
Ethylene glycol
Propylene glycol
Kc
Correction on cooling capacity
Ki
Correction on power input
Kf
Correction on flow rate
Kp
Correction on pressure drop
Type
Concentration (wt%)
0
10
20
30
40
Ethylene glycol
Freezing point °C
0
-4
-9
-16
-23
Minimum LWE °C
5
2
0
-5
-11
Propylene glycol
Freezing point °C
0
-3
-7
-13
-22
Minimum LWE °C
5
3
-2
-4
-10