![Daikin EUWL KZW1 Series Service Manual Download Page 102](http://html1.mh-extra.com/html/daikin/euwl-kzw1-series/euwl-kzw1-series_service-manual_3565814102.webp)
Troubleshooting
ESIE-0303
3–20
3
1
3
4
5
4.2
Items to Be Checked
Introduction
The tables below contain the most frequent failures and their corresponding corrective action:
■
In case the unit does not start and there is no malfunction indication.
■
In case the unit does not start and there is a malfunction indication.
No malfunction
indication
The unit does not start and there is no malfunction indication:
Malfunction
indication
The unit does not start and there is a malfunction indication:
Possible causes
Items to be checked
Power supply problem:
■
Main supply
■
Control system supply
■
Loose or broken connections
■
Blown fuses (due to short circuit)
■
Defective transformer
The unit is not switched ON.
■
Check the remote start/stop set-up and correct it, if
necessary.
■
In case of remote control, check the field wiring.
One of the timers is still active.
Check the timers overview in this manual and wait
until all timers have elapsed. See ‘‘Compressor Tim-
ers” on page 2-7.
The unit is incorrectly programmed.
Check the settings.
Do not set the compressor step in manual mode
control to 0%.
Malfunction
Possible causes
Items to be checked
Freeze-up
■
Water flow too low
■
Refrigerant shortage
■
Operation out of range
■
Defective thermostat control
■
Pump operation
■
Water flow (blocked valves)
■
Flow switch operation
■
Operation condition
■
Blocked parts in the refrigerant system
■
Refrigerant leaks
Overcurrent in
the compressor
■
Failure on one of the phases
■
Low supply voltage
■
Motor overload
■
Power supply
■
Fuses
■
Mains isolator switch
■
Mains relay contacts
■
Operation condition
■
Compressor windings
■
Current on all 3 phases
■
Reset the overcurrent relay
Summary of Contents for EUWL KZW1 Series
Page 1: ......
Page 2: ......
Page 8: ...Introduction ESIE 0303 vi 3 1 4 5 ...
Page 10: ...ESIE 0303 1 2 Part 1 System Outline 3 1 1 5 ...
Page 50: ...Piping Layout ESIE 0303 1 42 Part 1 System Outline 3 1 1 4 5 ...
Page 60: ...Wiring Layout ESIE 0303 1 52 Part 1 System Outline 3 1 1 4 5 ...
Page 61: ...ESIE 0302 Wiring Layout Part 1 System Outline 1 53 3 6 Wiring Diagram Wiring diagram ...
Page 62: ...Wiring Layout ESIE 0302 1 54 Part 1 System Outline ...
Page 64: ...ESIE 0303 2 2 Part 2 Functional Description 3 1 2 5 ...
Page 84: ...ESIE 0303 3 2 Part 3 Troubleshooting 3 1 3 5 ...
Page 87: ...ESIE 0303 Inputs and Outputs Overview Part 3 Troubleshooting 3 5 3 3 4 5 1 ...
Page 88: ...Inputs and Outputs Overview ESIE 0303 3 6 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 94: ...Malfunction Indications and Safeties Overview ESIE 0303 3 12 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 100: ...Checking the Inputs and Outputs ESIE 0303 3 18 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 112: ...Troubleshooting ESIE 0303 3 30 Part 3 Troubleshooting 3 1 3 4 5 ...
Page 114: ...ESIE 0303 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ...
Page 130: ...ESIE 0303 5 2 Part 5 Maintenance 3 1 5 ...
Page 139: ...ESIE 0303 Index 3 3 4 5 1 Wiring Diagram k 1 53 ...
Page 140: ...ESIE 0303 4 Index 3 1 4 5 ...