ESIE11-02
General Outline
1–35
3
1
4
5
1.13
Electrical Specifications: EUWA*16-20KBZW1
Electrical
specifications
The table below contains the electrical specifications.
Model
EUWAN16KBZW1 EUWAP16KBZW1 EUWAB16KBZW1 EUWAN20KBZW1 EUWAP20KBZW1 EUWAB20KBZW1
Power supply
Phase
3N~
Frequency
50 Hz
Voltage
400 V
Voltage tolerance
± 10 %
Unit
Starting current
97.9 A
99.9 A
113 A
115 A
Nominal running
current
27.2 A
29.2 A
31.8 A
33.8 A
Max. running
current
33.8 A
35.8 A
39.8 A
41.8 A
Recommended
fuses
3 x 40 gL/gG
3 x 50 gL/gG
3 x 50 gL/gG
3 x 50 gL/gG
Fans
Phase
1~
Voltage
230 V
Max. running
current
5.8 A
Compressor
Phase
3~
Voltage
400 V
Starting current
95.0 A
110.0 A
Nom. running
current
10.7 A
13.0 A
Max. running
current
14.0 A
17.0 A
Starting method
Direct on line
Control circuit
Phase
1~
Voltage
230/ 24 V AC (supplied by factory installed transformers)
Recommended
fuses
Factory installed
Crankcase heater
(E1/2 HC)
50 W
Pump
Phase
__
3~
__
3~
Voltage
__
400.0 V
__
400.0 V
Max. running
current
__
2.0 A
__
2.0 A
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...