Checking the Inputs and Outputs
ESIE11-02
3–18
3
1
3
4
5
3.6
Checking the Power Supply and Fuses: EUWA*5-24KBZW1 and
EUWY*5-24KBZW1
Overview
The table below contains an overview of the circuits, the voltage and their fuse codes.
Circuit
Wiring code
Type / voltage
Fuse code
Main supply
L1 + L2 + L3 + N
3 phases / 400 V AC
F1+F2+F3
Control circuit I/O PCB
L1 + N
L3 + N
1 phase / 230 V AC
1 phase / 230 V AC
F4
F1U
Control circuit controller
TR1-sec.
24 V AC
F3U, F5U
Control circuit (pump) for
EUWAN5-24KBZW1
X1M 8-7
24 V AC
F6
Fan circuit for
EUWA*5-12KBZW1
L1 + N
1 phase / 230 V AC
F7
Fan circuit for
EUWA*18-24KBZW1
L1 + N
1 phase / 230 V AC
F8
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...