ESIE11-02
The Digital Controller
Part 2 – Functional Description
2–39
3
2
4
5
1
2.8
Option EKAC10C Address Card
Overview
Remark
■
Modbus communication RS485/RTU only
■
Modbus communication RS485 and remote user interface is not possible at the same time
■
No BACnet possibility
■
The RS485 communication settings for Modbus protocol are:
■
baudrate: 9600
■
stop bit: 2
■
parity: none
Controller settings
Following parameters have to be programmed to activate Modbus communication:
■
H23: select 1 to enable
M
odbus communication
■
H10: select serial address of the chiller
1
2
3
2
24
31
56
75
5
5
85
+
+
2x 0.35 mm
2
/ AWG 22
120 Ω
(1/4 W 120 Ohm)
1
EKAC10C
EKAC10C
EKAC10C
GND T+ T–
h10
= 1
h10
= n
120
Ω
BMS
GND
T+
T–
1..
EKAC10C
...n
EKAC10C
GND
T+
T–
3
EKAC10C
+
BMS
EKAC10C
+
EKRUMCA
Summary of Contents for EUWAB10KBZW1
Page 2: ......
Page 8: ...ESIE11 02 vi Table of Contents 3 1 4 5...
Page 10: ...Introduction ESIE11 02 viii 3 1 4 5...
Page 12: ...ESIE11 02 1 2 Part 1 System Outline 3 1 1 5...
Page 86: ...Wiring Layout ESIE11 02 1 76 Part 1 System Outline...
Page 88: ...ESIE11 02 2 2 Part 2 Functional Description 3 1 2 5...
Page 128: ...The Digital Controller ESIE11 02 2 42 Part 2 Functional Description 3 1 2 4 5...
Page 130: ...ESIE11 02 3 2 Part 3 Troubleshooting 3 1 3 5...
Page 168: ...ESIE11 02 4 2 Part 4 Commissioning and Test Run 3 1 4 5...
Page 198: ...Test Run and Operation Data ESIE11 02 4 32 Part 4 Commissioning and Test Run 3 1 4 5...
Page 200: ...ESIE11 02 5 2 Part 5 Maintenance 3 1 5...
Page 210: ...ESIE11 02 4 Index 3 1 4 5...