5 Piping installation

Installation manual

8

ETVH/23E

Daikin Altherma 3 H HT F

4P644728-1D – 2022.08

5.2

Connecting water piping

5.2.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  field
piping  and  make  sure  the  piping  is  aligned  properly.
Deformation of the piping can cause malfunctioning of the
unit.

To  facilitate  service  and  maintenance,  4  shut-off  valves  and  1
differential  pressure  bypass  valve  are  provided.  Mount  the  shut-off
valves on the space heating water IN/OUT connections, and on the
water  IN/OUT  connections  from/to  the  outdoor  unit.  To  ensure  the
minimum flow rate (and prevent overpressure), install the differential
pressure bypass valve on the space heating water outlet.

1

Connect  the  O-rings  and  shut-off  valves  to  the  outdoor  unit
water connection pipes of the indoor unit.

2

Connect the outdoor unit field piping to the shut-off valves.

3

Connect  the  O-rings  and  shut-off  valves  to  the  space  heating/
cooling water pipes of the indoor unit.

4

Connect  the  space  heating/cooling  field  piping  to  the  shut-off
valves.

5

Connect  the  domestic  hot  water  in  and  out  pipes  to  the  indoor
unit.

b1

b2

a1

a2

c2

c1

a1

Space heating/cooling – Water IN (screw connection, 1")

a2

Space heating/cooling – Water OUT (screw connection,
1")

b1

DHW – Cold water IN (screw connection, 3/4")

b2

DHW – Hot water OUT (screw connection, 3/4")

c1

Water IN from outdoor unit (screw connection, 1")

c2

Water OUT to outdoor unit (screw connection, 1")

6

Install the following components (field supply) on the cold water
inlet of the DHW tank:

g

c

b1

b2

d

a

*e

*f

a

a

Shut-off valve (recommended)

b1

DHW – Cold water IN (screw connection, 3/4")

b2

DHW – Hot water OUT (screw connection, 3/4")

c

Non-return valve (recommended)

d

Pressure reducing valve (recommended)

*e

Pressure relief valve (max. 10 bar (=1.0 MPa))
(mandatory)

*f

Tundish (mandatory)

g

Expansion vessel (recommended)

NOTICE

▪ It is recommended to install shut-off valves to domestic

cold  water  in  and  domestic  hot  water  out  connections.
These shut-off valves are field supplied.

However,  make  sure  there  is  no  valve  between  the
pressure  relief  valve  (field  supply)  and  the  DHW
tank.

NOTICE

A  pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  (=1  MPa)  must  be  installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

NOTICE

▪ A  drain  device  and  pressure  relief  device  must  be

installed  on  the  cold  water  inlet  connection  of  the
domestic hot water cylinder.

▪ To avoid back siphonage, it is recommended to install a

non-return valve on the water inlet of the domestic hot
water tank in accordance with the applicable legislation.
Make sure it is NOT between the pressure relief valve
and the DHW tank.

▪ It is recommended to install a pressure reducing valve

on  the  cold  water  inlet  in  accordance  with  the
applicable legislation.

▪ It is recommended to install an expansion vessel on the

cold  water  inlet  in  accordance  with  the  applicable
legislation.

▪ It is recommended to install the pressure relief valve on

a higher position than the top of the domestic hot water
tank.  Heating  of  the  domestic  hot  water  tank  causes
water  to  expand  and  without  pressure  relief  valve  the
water pressure inside the tank can rise above the tank
design  pressure.  Also  the  field  installation  (piping,
tapping points, etc.) connected to the tank is subjected
to this high pressure. To prevent this, a pressure relief
valve  needs  to  be  installed.  The  overpressure
prevention depends on the correct operation of the field
installed  pressure  relief  valve.  If  this  is  NOT  working
correctly,  overpressure  will  deform  the  tank  and  water
leakage may occur. To confirm good operation, regular
maintenance is required.

NOTICE

Differential

 

pressure  bypass  valve

  (delivered  as

accessory).  We  recommend  to  install  the  differential
pressure bypass valve in the space heating water circuit.

▪ Mind  the  minimum  water  volume  when  choosing  the

installation  location  of  the  differential  pressure  bypass
valve  (at  the  indoor  unit,  or  at  the  collector).  See

"5.1.1 To check the water volume and flow rate"

 [

4

 7].

▪ Mind  the  minimum  flow  rate  when  adjusting  the

differential  pressure  bypass  valve  setting.  See

"5.1.1  To  check  the  water  volume  and  flow  rate"

  [

4

  7]

and 

"8.2.1 To check the minimum flow rate"

 [

4

 31].

NOTICE

Install air purge valves at all local high points.

Summary of Contents for ETVX16E6V7

Page 1: ...therma 3 H HT F English Installation manual Daikin Altherma 3 H HT F ETVH16S18E 6V ETVH16S23E 6V ETVH16S18E 9W ETVH16S23E 9W ETVX16S18E 6V ETVX16S23E 6V ETVX16S18E 9W ETVX16S23E 9W A B C Z 1 2 3 9 htt...

Page 2: ...e 21 7 2 3 Configuration wizard System 21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 23 7 2 6 Configuration wizard Additional zone 24 7 2 7 Configuration wizard T...

Page 3: ...the instructions from this manual See 5 Piping installation 47 In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is...

Page 4: ...omestic hot water circuit j Sealing tape for low voltage wiring intake 3 1 2 To handle the indoor unit Use the handles at the back and at the bottom to carry the unit b a a b a Handles at the back of...

Page 5: ...he cables from the back of the user interface panel to prevent damage 2 1 1 3 4 X14Y X1A 3 Remove the switch box cover 4 T25 4 If necessary remove the front plate This is for example necessary in the...

Page 6: ...pallet and place it on the floor Also see 3 1 2 To handle the indoor unit 44 2 Connect the drain hose to the drain See 4 3 2 To connect the drain hose to the drain 46 3 Slide the indoor unit into pos...

Page 7: ...piping and accessories 5 1 1 To check the water volume and flow rate Minimum water volume Check that the total water volume in the installation is minimum 20 litres the internal water volume of the o...

Page 8: ...lve between the pressure relief valve field supply and the DHW tank NOTICE A pressure relief valve field supply with an opening pressure of maximum 10 bar 1 MPa must be installed on the domestic cold...

Page 9: ...system is possible Uninhibited glycol will turn acidic under the influence of oxygen This process is accelerated by the presence of copper and high temperatures The acidic uninhibited glycol attacks m...

Page 10: ...r tank 1 Open every hot water tap in turn to purge air from the system pipe work 2 Open the cold water supply valve 3 Close all water taps after all air is purged 4 Check for water leaks 5 2 6 To insu...

Page 11: ...ent Wires 2 0 75 mm 9 B 1 1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional...

Page 12: ...see 4 2 1 To open the indoor unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the main power supply In case of normal kWh rate power supply Interconnection cable mai...

Page 13: ...ackup heater capacity Power supply Maximum running current Zmax 6V 2 kW 1N 230 V a 9 A 4 kW 1N 230 V a 17 A b c 0 22 6 kW 1N 230 V a 26 A b c 0 22 2 kW 3 230 V d 5 A 4 kW 3 230 V d 10 A 6 kW 3 230 V d...

Page 14: ...all a shut off valve before the underfloor heating to prevent condensation on the floor during cooling operation Wires 2 0 75 mm Maximum running current 100 mA 230 V AC supplied by PCB 2 D Shut off va...

Page 15: ...door unit 45 1 Top panel 1 2 3 2 User interface panel 3 Upper switch box cover 2 Connect the domestic hot water pump cable to the appropriate terminals as shown in the illustration below A 1 M M2P B A...

Page 16: ...illustration below 7 9 YC Y2 X2M 1 2 3 A4P 1 2 Wires connected to the space cooling heating ON OFF output 3 Wire between X2M and A4P A4P Installation of EKRP1HBAA is required A Y2 7 B A B 7 9 X2M A4P...

Page 17: ...puts cable to the appropriate terminals as shown in the illustration below A 1 2 4 5 S6S S7S S8S S9S 3 B A B A8P X801M a 1 2 3 4 5 a Installation of EKRP1AHTA is required 3 Fix the cable with cable ti...

Page 18: ...acts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running 0 1 Forced off 1 0 Recommended on 1 1 Forced on The use of a Smart Grid pulse meter i...

Page 19: ...2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d Contact sides of relays e Jumper factory...

Page 20: ...izard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the configuration wizard To restart the configuration wizard go to In...

Page 21: ...rview settings and you go back to the home screen the user interface will show a popup screen and request to restart the system When confirmed the system will restart and recent changes will be applie...

Page 22: ...periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION The auto emergency setting can be set in the menu stru...

Page 23: ...change one check if the other is still as expected INFORMATION During normal operation the capacity of the second step of the backup heater at nominal voltage is equal to 6 03 6 04 INFORMATION If 4 0...

Page 24: ...endent operation the user can shift the water temperature up or down by a maximum of 10 C Schedule Indicates if the desired leaving water temperature is according to a schedule Influence of the LWT se...

Page 25: ...ing reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up during storage co...

Page 26: ...temperature is heated increasingly more at decreasingly lower ambient temperatures Change the offset to equally increase or decrease the temperature of the leaving water for different ambient temperat...

Page 27: ...the maximum or minimum setpoint is reached the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curv...

Page 28: ...644728 1D 2022 08 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 7 4 3 Information Dealer information The installer can fill in his contact nu...

Page 29: ...rical heaters Limit setting kW Enable room buffering Allow heater Allow pump 9 Installer settings Configuration wizard Domestic hot water Backup heater Emergency Balancing Water pipe freeze prevention...

Page 30: ...ring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit Between indoor unit and outdoor unit Between the local supply pa...

Page 31: ...start the measurement will be successful Before 30 min from start the measurement might be unsuccessful If the measurement is successful the logic to activate the backup heater will use a timeframe t...

Page 32: ...fter the first 12 hours of power on manually disable room frost protection by setting 2 06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking o...

Page 33: ...d Pump e Backup heater f Shut off valve male female 1 g Expansion vessel h Magnetic filter dirt separator i Safety valve j Air purge k Drain valve l Loose nut 1 m Shut off valve recommended n Non ret...

Page 34: ...eat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P ON OFF thermostat PC power circuit A3P Heat pump convector A4P Digit...

Page 35: ...Grid Inrush Inrush current Max load Maximum load Normally closed Normally closed Normally open Normally open Safety thermostat contact 16 V DC detection voltage supplied by PCB Safety thermostat conta...

Page 36: ...l kWh rate power supply installation Unit power supply 400 V or 230 V earth Only for normal power supply installation OUTDOOR UNIT STANDARD PART POWER SUPPLY WLAN module communication 5 core A20P J2 X...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P644728 1D 2022 08 Copyright 2021 Daikin 4P644728 1 D 00000004 Verantwortung f r Energie und Umwelt...

Reviews: