6
|
Application guidelines
Installer reference guide
64
EPRA14~18D + ETSH/X(B)16P30+50E
Daikin Altherma 3 H HT ECH₂O
4P679467-1C – 2023.07
P
h
C
e
a
b
c
A
B
P
h
Produced heat
C
e
Consumed energy
A
Outdoor unit
B
Backup heater
a
Limited outdoor unit operation
b
Full outdoor unit operation
c
Backup heater step 1 turned ON
6.6.4 BBR16 power limitation
INFORMATION
Restriction:
BBR16 settings are only visible when the language of the user interface is
set to Swedish.
NOTICE
2 weeks to change.
After you activated BBR16, you only have 2 weeks to change its
settings (
BBR16 activation
and
BBR16 power limit
). After 2 weeks, the unit
freezes these settings.
Note:
This is different from the permanent power limitation, which is always
changeable.
Use the BBR16 power limitation when you must comply with BBR16 regulations
(Swedish energy regulations).
You can combine the BBR16 power limitation with the other kW power
consumption controls. If you do so, the unit uses the most restrictive control.
P
i
t
BBR16
a
b
P
i
Power input
t
Time
BBR16
BBR16 limit level
a
Power limitation active
b
Actual power input
Setup and configuration
▪
No additional equipment needed.
▪
Set the power consumption control settings in [9.9] via the user interface (see
-
Activate BBR16
-
Set the desired power limitation level