10
|
Configuration
Installer reference guide
159
EPRA14~W1 + ETSH/X(B)16P30+50EF
Daikin Altherma 3 H HT ECH₂O
4P679467-1 – 2022.02
Example
Y1
Y2
X1
X2
a
Item
Description
a
Selected weather dependent zone:
▪
: Main zone or additional zone heating
▪
: Main zone or additional zone cooling
▪
: Domestic hot water
X1, X2
Examples of outdoor ambient temperature
Y1, Y2
Examples of desired tank temperature or leaving water temperature.
The icon corresponds to the heat emitter for that zone:
▪
: Underfloor heating
▪
: Fan coil unit
▪
: Radiator
▪
: Storage tank
Possible actions on this screen
Go through the temperatures.
Change the temperature.
Go to the next temperature.
Confirm changes and proceed.
10.4.3 Slope-offset curve
Slope and offset
Define the weather-dependent curve by its slope and offset:
▪
Change the
slope
to differently increase or decrease the temperature of the
leaving water for different ambient temperatures. For example, if leaving water
temperature is in general fine but at low ambient temperatures too cold, raise
the slope so that leaving water temperature is heated increasingly more at
decreasingly lower ambient temperatures.
▪
Change the
offset
to equally increase or decrease the temperature of the leaving
water for different ambient temperatures. For example, if leaving water
temperature is always a bit too cold at different ambient temperatures, shift the
offset up to equally increase the leaving water temperature for all ambient
temperatures.
Examples
Weather-dependent curve when slope is selected: