5 Piping installation

Installation manual

9

ETBH/9W
Daikin Altherma 3 H MT W
4P634879-1 – 2021.03

b

a

a

Water IN (screw connection, 1")

b

Space heating water OUT (screw connection, 1")

NOTICE

Overpressure bypass valve

 (delivered as accessory). We

recommend to install the overpressure bypass valve in the
space heating water circuit.

▪ Mind  the  minimum  water  volume  when  choosing  the

installation  location  of  the  overpressure  bypass  valve
(at  the  indoor  unit,  or  at  the  collector).  See 

"5.1.1  To

check the water volume and flow rate"

 [

4

 8].

▪ Mind  the  minimum  flow  rate  when  adjusting  the

overpressure  bypass  valve  setting.  See 

"5.1.1  To

check  the  water  volume  and  flow  rate"

  [

4

  8]  and

"8.2.1 To check the minimum flow rate"

 [

4

 32].

NOTICE

Install air purge valves at all local high points.

NOTICE

In case an optional domestic hot water tank is installed: A
pressure  relief  valve  (field  supply)  with  an  opening
pressure  of  maximum  10  bar  (=  1  MPa)  must  be  installed
on the domestic cold water inlet connection in accordance
with the applicable legislation.

5.2.2

To fill the water circuit

To  fill  the  water  circuit,  use  a  field  supply  filling  kit.  Make  sure  you
comply with the applicable legislation.

NOTICE

Make sure both air purge valves (one on the magnetic filter
and one on the backup heater) are open.

All  automatic  air  purge  valves  MUST  remain  open  after
commissioning.

5.2.3

To protect the water circuit against
freezing

About freeze protection

Frost can damage the system. To prevent the hydraulic components
from  freezing,  the  software  is  equipped  with  special  frost  protection
functions such as water pipe freeze prevention and drain prevention
(see the installer reference guide) that include the activation of pump
in case of low temperatures.

However,  in  case  of  a  power  failure,  these  functions  cannot
guarantee protection.

Do one of the following to protect the water circuit against freezing:

▪ Add  glycol  to  the  water.  Glycol  lowers  the  freezing  point  of  the

water.

▪ Install freeze protection valves. Freeze protection valves drain the

water  from  the  system  before  it  can  freeze.  Insulate  the  freeze
protection valves in a similar way as the water piping, but do NOT
insulate the inlet and outlet (release) of these valves.

NOTICE

If  you  add  glycol  to  the  water,  do  NOT  install  freeze
protection  valves. 

Possible  consequence: 

Glycol  leaking

out of the freeze protection valves.

Freeze protection by glycol

About freeze protection by glycol

Adding glycol to the water lowers the freezing point of water.

WARNING

Ethylene glycol is toxic.

WARNING

Due  to  the  presence  of  glycol,  corrosion  of  the  system  is
possible.  Uninhibited  glycol  will  turn  acidic  under  the
influence  of  oxygen.  This  process  is  accelerated  by  the
presence  of  copper  and  high  temperatures.  The  acidic
uninhibited  glycol  attacks  metal  surfaces  and  forms
galvanic  corrosion  cells  that  cause  severe  damage  to  the
system. Therefore it is important that:

▪ the water treatment is correctly executed by a qualified

water specialist,

▪ a  glycol  with  corrosion  inhibitors  is  selected  to

counteract acids formed by the oxidation of glycols,

▪ no  automotive  glycol  is  used  because  their  corrosion

inhibitors  have  a  limited  lifetime  and  contain  silicates
which can foul or plug the system,

▪ galvanized pipes are NOT used in glycol systems since

the  presence  may  lead  to  the  precipitation  of  certain
components in the glycol's corrosion inhibitor.

NOTICE

Glycol  absorbs  water  from  its  environment.  Therefore  do
NOT add glycol that has been exposed to air. Leaving the
cap  off  the  glycol  container  causes  the  concentration  of
water  to  increase.  The  glycol  concentration  is  then  lower
than  assumed.  As  a  result,  the  hydraulic  components
might freeze up after all. Take preventive actions to ensure
a minimal exposure of the glycol to air.

Types of glycol

The types of glycol that can be used depend on whether the system
contains a domestic hot water tank:

Summary of Contents for ETBH12EF6V

Page 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H MT W English Installation manual Daikin Altherma 3 H MT W ETBH12EF6V ETBH12EF9W ETBX12EF6V ETBX12EF9W...

Page 2: ...ny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19...

Page 3: ...22 7 2 4 Configuration wizard Backup heater 24 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard Tank 26 7 3 Weather dependent curve 26 7...

Page 4: ...rical device Possible consequence Electrical shock or fire In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is poss...

Page 5: ...f valve h Overpressure bypass valve i Wall bracket 4 Unit installation 4 1 Preparing the installation site 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoo...

Page 6: ...en the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open the user interface panel 1 2 3 2 5 Optional Remove the user interfa...

Page 7: ...ect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation...

Page 8: ...does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if a...

Page 9: ...tect the water circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system...

Page 10: ...t be set to 1 If the glycol setting is NOT set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to...

Page 11: ...as accessory 420 Room thermostat wired or wireless See below table Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Thermostat type For the additional zone 3 A Thermostat...

Page 12: ...t Installer reference guide Use the cable delivered with the WLAN module D Wireless gateway Bizone kit See Installation manual of the bizone kit Addendum book for optional equipment Use the cable deli...

Page 13: ...r supply connect X11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indo...

Page 14: ...public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the...

Page 15: ...ow NOTICE Wiring is different for a NC normally closed valve and a NO normally open valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to...

Page 16: ...1 To open the indoor unit 46 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4...

Page 17: ...um load 20 mA 5 V DC 9 C Bivalent 1 Open the following see 4 2 1 To open the indoor unit 46 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable t...

Page 18: ...ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safety thermosta...

Page 19: ...ontact 1 2 S11S Low voltage Smart Grid contact 2 1 Connect the wiring as follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cab...

Page 20: ...Smart Grid pulse meter C B X5M X5M 3 4 13 14 3 Connect the high voltage wiring as follows B C A A L N L N X10M 1 X10M 2 X10M 3 X10M 4 2 1 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid...

Page 21: ...les You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not...

Page 22: ...ate INFORMATION By default daylight savings time is enabled and clock format is set to 24 hours If you want to change these settings you can do this in the menu structure User settings Time date once...

Page 23: ...H reduced DHW off if the house is unattended for longer periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION...

Page 24: ...3ph Code Description 9 3 2 5 0D 0 230V 1ph 1 230V 3ph 2 400V 3ph Configuration The backup heater can be configured in different ways It can be chosen to have a 1 step only backup heater or a backup h...

Page 25: ...e outdoor ambient temperature for heating does NOT depend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient...

Page 26: ...le reheat mode during reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up...

Page 27: ...erent ambient temperatures For example if leaving water temperature is always a bit too cold at different ambient temperatures shift the offset up to equally increase the leaving water temperature for...

Page 28: ...ched the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve of a zone or tank You feel Fine tune...

Page 29: ...P634879 1 2021 03 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 7 4 3 Information Dealer information The installer can fill in his contact nu...

Page 30: ...temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor...

Page 31: ...nit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel an...

Page 32: ...r and tank temperatures During test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode T...

Page 33: ...06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make s...

Page 34: ...ing diagram Indoor unit 3D120613B R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e S...

Page 35: ...less On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired...

Page 36: ...ot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat...

Page 37: ...Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H o...

Page 38: ......

Page 39: ......

Page 40: ...4P634879 1 2021 03 Copyright 2021 Daikin 4P634879 1 0000000Z Verantwortung f r Energie und Umwelt...

Reviews: