7 Configuration

Installation manual

25

ETBH/9W
Daikin Altherma 3 H MT W
4P634879-1 – 2021.03

It is important to set 

Emitter type

 correctly and in accordance with

your system layout. The target delta T for the main zone depends on
it.

#

Code

Description

[2.7]

[2‑0C]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

The setting of the emitter type has an influence on the space heating
setpoint range and the target delta T in heating as follows:

Description

Space heating

setpoint range

Target delta T in

heating

0: 

Underfloor

heating

Maximum 55°C

Variable

1: 

Fancoil unit

Maximum 55°C

Variable

2: 

Radiator

Maximum 65°C

Fixed 10°C

NOTICE

Average 

emitter 

temperature

 

Leaving 

water

temperature – (Delta T)/2

This  means  that  for  a  same  leaving  water  temperature
setpoint,  the  average  emitter  temperature  of  radiators  is
lower  than  that  of  underfloor  heating  because  of  a  bigger
delta T.

Example radiators: 40–10/2=

35°C

Example underfloor heating: 40–5/2=

37.5°C

To compensate, you can:

▪ Increase 

the 

weather-dependent 

curve 

desired

temperatures [2.5].

▪ Enable  leaving  water  temperature  modulation  and

increase the maximum modulation [2.C].

Control

Define how the operation of the unit is controlled.

Control

In this control...

Leaving water

Unit operation is decided based on the leaving
water temperature regardless the actual room
temperature and/or heating or cooling demand
of the room.

External room
thermostat

Unit operation is decided by the external
thermostat or equivalent (e.g. heat pump
convector).

Room thermostat

Unit operation is decided based on the ambient
temperature of the dedicated Human Comfort
Interface (BRC1HHDA used as room
thermostat).

#

Code

Description

[2.9]

[C‑07]

▪ 0: 

Leaving water

▪ 1: 

External room thermostat

▪ 2: 

Room thermostat

Setpoint mode

Define the setpoint mode:

Fixed

: the desired leaving water temperature does not depend on

the outdoor ambient temperature.

▪ In 

WD heating, fixed cooling

 mode, the desired leaving water

temperature:

▪ depends on the outdoor ambient temperature for heating

▪ does  NOT  depend  on  the  outdoor  ambient  temperature  for

cooling

▪ In 

Weather 

dependent

  mode,  the  desired  leaving  water

temperature depends on the outdoor ambient temperature.

#

Code

Description

[2.4]

N/A

Setpoint mode

:

Fixed

WD heating, fixed cooling

Weather dependent

When  weather  dependent  operation  is  active,  low  outdoor
temperatures  will  result  in  warmer  water  and  vice  versa.  During
weather  dependent  operation,  the  user  can  shift  the  water
temperature up or down by a maximum of 10°C.

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Influence of the LWT setpoint mode [2.4] is as follows:

▪ In 

Fixed

  LWT  setpoint  mode,  the  scheduled  actions  consist  of

desired leaving water temperatures, either preset or custom.

▪ In 

Weather  dependent

  LWT  setpoint  mode,  the  scheduled

actions consist of desired shift actions, either preset or custom.

#

Code

Description

[2.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

7.2.6

Configuration wizard: Additional zone

The  most  important  settings  for  the  additional  leaving  water  zone
can be set here.

Emitter type

For  more  info  about  this  functionality,  see 

"7.2.5  Configuration

wizard: Main zone"

 [

4

 24].

#

Code

Description

[3.7]

[2‑0D]

▪ 0: 

Underfloor heating

▪ 1: 

Fancoil unit

▪ 2: 

Radiator

Control

The  control  type  is  displayed  here,  but  cannot  be  adjusted.  It  is
determined by the control type of the main zone. For more info about
the functionality, see 

"7.2.5 Configuration wizard: Main zone"

 [

4

 24].

#

Code

Description

[3.9]

N/A

▪ 0: 

Leaving  water

  if  the  control  type

of the main zone is 

Leaving water

.

▪ 1: 

External  room  thermostat

 if the

control  type  of  the  main  zone  is

External  room  thermostat

 or 

Room

thermostat

.

Setpoint mode

For  more  info  about  this  functionality,  see 

"7.2.5  Configuration

wizard: Main zone"

 [

4

 24].

#

Code

Description

[3.4]

N/A

▪ 0: 

Fixed

▪ 1: 

WD heating, fixed cooling

▪ 2: 

Weather dependent

If  you  choose 

WD  heating,  fixed  cooling

  or 

Weather

dependent

, the next screen will be the detailed screen with weather-

dependent curves. Also see 

"7.3 Weather-dependent curve"

 [

4

 26].

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Also see 

"7.2.5 Configuration wizard: Main zone"

 [

4

 24].

Summary of Contents for ETBH12EF6V

Page 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H MT W English Installation manual Daikin Altherma 3 H MT W ETBH12EF6V ETBH12EF9W ETBX12EF6V ETBX12EF9W...

Page 2: ...ny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 19...

Page 3: ...22 7 2 4 Configuration wizard Backup heater 24 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard Tank 26 7 3 Weather dependent curve 26 7...

Page 4: ...rical device Possible consequence Electrical shock or fire In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is poss...

Page 5: ...f valve h Overpressure bypass valve i Wall bracket 4 Unit installation 4 1 Preparing the installation site 4 1 1 Installation site requirements of the indoor unit The indoor unit is designed for indoo...

Page 6: ...en the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open the user interface panel 1 2 3 2 5 Optional Remove the user interfa...

Page 7: ...ect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation...

Page 8: ...does NOT display error 7H NOTICE When circulation in each or certain space heating loops is controlled by remotely controlled valves it is important that the minimum flow rate is guaranteed even if a...

Page 9: ...tect the water circuit against freezing Add glycol to the water Glycol lowers the freezing point of the water Install freeze protection valves Freeze protection valves drain the water from the system...

Page 10: ...t be set to 1 If the glycol setting is NOT set correctly the liquid inside the piping can freeze Freeze protection by freeze protection valves About freeze protection valves When no glycol is added to...

Page 11: ...as accessory 420 Room thermostat wired or wireless See below table Wires 0 75 mm Maximum running current 100 mA For the main zone 2 9 Control 2 A Thermostat type For the additional zone 3 A Thermostat...

Page 12: ...t Installer reference guide Use the cable delivered with the WLAN module D Wireless gateway Bizone kit See Installation manual of the bizone kit Addendum book for optional equipment Use the cable deli...

Page 13: ...r supply connect X11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate connection to the indo...

Page 14: ...public low voltage supply systems for equipment with rated current 75 A provided that the system impedance Zsys is less than or equal to Zmax at the interface point between the user s supply and the...

Page 15: ...ow NOTICE Wiring is different for a NC normally closed valve and a NO normally open valve B C A A B C A A M2S NO NC C 5 6 X2M C 21 28 X2M C 5 6 X2M C 21 29 X2M B X2M 3 Fix the cable with cable ties to...

Page 16: ...1 To open the indoor unit 46 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the alarm output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y1 X2M 1 2 3 A4...

Page 17: ...um load 20 mA 5 V DC 9 C Bivalent 1 Open the following see 4 2 1 To open the indoor unit 46 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the changeover to external heat source cable t...

Page 18: ...ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safety thermosta...

Page 19: ...ontact 1 2 S11S Low voltage Smart Grid contact 2 1 Connect the wiring as follows B C A A X5M 4 X5M 3 S4S X5M 10 X5M 9 S10S X5M 6 X5M 5 S11S 2 1 C B X5M X5M 3 4 5 6 9 10 13 14 2 Fix the cables with cab...

Page 20: ...Smart Grid pulse meter C B X5M X5M 3 4 13 14 3 Connect the high voltage wiring as follows B C A A L N L N X10M 1 X10M 2 X10M 3 X10M 4 2 1 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid...

Page 21: ...les You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not...

Page 22: ...ate INFORMATION By default daylight savings time is enabled and clock format is set to 24 hours If you want to change these settings you can do this in the menu structure User settings Time date once...

Page 23: ...H reduced DHW off if the house is unattended for longer periods Code Description 9 5 1 4 06 0 Manual 1 Automatic 2 auto SH reduced DHW on 3 auto SH reduced DHW off 4 auto SH normal DHW off INFORMATION...

Page 24: ...3ph Code Description 9 3 2 5 0D 0 230V 1ph 1 230V 3ph 2 400V 3ph Configuration The backup heater can be configured in different ways It can be chosen to have a 1 step only backup heater or a backup h...

Page 25: ...e outdoor ambient temperature for heating does NOT depend on the outdoor ambient temperature for cooling In Weather dependent mode the desired leaving water temperature depends on the outdoor ambient...

Page 26: ...le reheat mode during reheat mode the guaranteed minimum tank temperature is set by the Reheat setpoint minus the reheat hysteresis If the tank temperature drops below this value the tank is heated up...

Page 27: ...erent ambient temperatures For example if leaving water temperature is always a bit too cold at different ambient temperatures shift the offset up to equally increase the leaving water temperature for...

Page 28: ...ched the curve flattens out To fine tune the weather dependent curve slope offset curve The following table describes how to fine tune the weather dependent curve of a zone or tank You feel Fine tune...

Page 29: ...P634879 1 2021 03 Code Description 3 A C 06 External room thermostat type for the additional zone 1 1 contact 2 2 contacts 7 4 3 Information Dealer information The installer can fill in his contact nu...

Page 30: ...temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor...

Page 31: ...nit is properly mounted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel an...

Page 32: ...r and tank temperatures During test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode T...

Page 33: ...06 to 0 and KEEP it disabled until the screed dryout has finished Ignoring this notice will result in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make s...

Page 34: ...ing diagram Indoor unit 3D120613B R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e S...

Page 35: ...less On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wired...

Page 36: ...ot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For low voltage Smart Grid For safety thermostat...

Page 37: ...Only for Human Comfort Interface Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H o...

Page 38: ......

Page 39: ......

Page 40: ...4P634879 1 2021 03 Copyright 2021 Daikin 4P634879 1 0000000Z Verantwortung f r Energie und Umwelt...

Reviews: