![Daikin ERQ Service Manual Download Page 250](http://html1.mh-extra.com/html/daikin/erq/erq_service-manual_2460609250.webp)
Precautions for New Refrigerant (R-410A)
ESIE09-05
240
Precautions for New Refrigerant (R-410A)
1.2 Refrigerant Cylinders
Cylinder specifications
•
The cylinder is painted refrigerant color (pink).
•
The cylinder valve is equipped with a siphon tube.
Handling of cylinders
(1) Laws and regulations
R-410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High-Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high-pressure gases. Be sure to follow the regulations.
(2) Handing of vessels
Since R-410A is high-pressure gas, it is contained in high-pressure vessels.
Although those vessels are durable and strong, careless handling can cause damage that
can lead to unexpected accidents. Do not drop vessels, let them fall, apply impact or roll
them on the ground.
(3) Storage
Although R-410A is not flammable, it must be stored in a well-ventilated, cool, and dark
place in the same way as any other high-pressure gases.
It should also be noted that high-pressure vessels are equipped with safety devices that
releases gas when the ambient temperature reaches more than a certain level (fusible plug
melts) and when the pressure exceeds a certain level (spring-type safety valve operates).
Refrigerant can be charged in liquid state with cylinder in
upright position.
Caution: Do not lay cylinder on its side during charging, since
it cause refrigerant in gas state to enter the system.
Siphon tube
Cylinder
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Summary of Contents for ERQ
Page 2: ...http splitoff ru tehn doc html...
Page 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Page 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Page 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Page 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...