ESIE09-05
Field Setting
Test Operation
101
Setting by pushbutton switches
The following settings are made by pushbutton switches on PC board.
(Factory setting)
There are the following three setting modes.
c
Setting mode 1 (H1P off)
Initial status (when normal) : Also indicates during “abnormal”.
d
Setting mode 2 (H1P on)
Used to modify the operating status and to set program addresses, etc. Usually used in
servicing the system.
e
Monitor mode (H1P blinks)
Used to check the program made in Setting mode 2.
Caution
Capacity Setting after changing the main PC Board(A1P) to spare parts PC Board
When you change the main PC Board(A1P) to spare parts PC Board, please carry out the
following setting.
Please Attach the Capacity Setting Adaptor corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adaptor
1
2
3
Capacity Class
112
140
160
Outdoor unit
100
125
140
CAPACITY SETTING ADAPTOR (for 100/J112)
CAPACITY SETTING ADAPTOR (for 125/J140)
CAPACITY SETTING ADAPTOR (for 140/J160)
Position of Attaching the Capacity Setting Adaptor
ERQ100 / 125 / 140A7V1B
Note
X51A
H1P
H2P
H3P
H4P
H5P
H6P
H7P
LED indication
BS1
MODE
BS2
SET
BS3
RETURN
BS4
TEST
BS5
RESET
(V2760)
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html
Summary of Contents for ERQ
Page 2: ...http splitoff ru tehn doc html...
Page 16: ...Combination Table ESIE09 05 6 General Information http splitoff ru tehn doc html...
Page 22: ...Specifications ESIE09 05 12 Specifications http splitoff ru tehn doc html...
Page 30: ...Functional Parts Layout ESIE09 05 20 Refrigerant Circuit http splitoff ru tehn doc html...
Page 52: ...Outline of Control ESIE09 05 42 Function http splitoff ru tehn doc html...