10
|
Commissioning
Installer reference guide
143
ERLA EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596821-1A – 2020.05
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
97].
2
Set the air purge mode: go to [A.7.3.1]
>
Installer settings
>
Commissioning
>
Air purge
>
Type
.
3
Select
Automatic
and press .
4
Go to [A.7.3.4]
>
Installer settings
>
Commissioning
>
Air
purge
>
Start air purge
and press to start the air purge function.
Result:
Air purging will start and the following screen will be shown.
10.4.3 To perform a test run
INFORMATION
The test run only applies to the additional temperature zone.
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
97].
2
Go to [A.7.1]: >
Installer settings
>
Commissioning
>
Test run
.
3
Select a test and press .
Example:
Heating
.
4
Select
OK
and press .
Result:
The test run starts. It stops automatically when done (±30 min). To stop it
manually, press , select
OK
and press .
INFORMATION
If 2 user interfaces are present, you can start a test run from both user interfaces.
▪
The user interface used to start the test run displays a status screen.
▪
The other user interface displays a "busy" screen. You cannot use the user
interface as long as the "busy" screen is shown.
10.4.4 To perform an actuator test run
Perform an actuator test run to confirm the operation of the different actuators.
For example, when you select
Pump
, a test run of the pump will start.
Purpose of the actuator test run is to confirm the operation of the different
actuators (e.g., when you select pump operation, a test run of the pump will start).
Prerequisite:
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page are turned OFF.
1
Set the user permission level to Installer. See
"To set the user permission level
97].
2
Go to [A.7.4]: >
Installer settings
>
Commissioning
>
Actuator
test run
.
3
Select an actuator and press .
Example:
Pump
.
4
Select
OK
and press .
Result:
The actuator test run starts. It automatically stops when finished. To stop it
manually, press , select
OK
and press .
Summary of Contents for ERLA03DAV3
Page 1: ...Installer reference guide Daikin Altherma 3 R F ERLA03DAV3 EHFZ03S18DJ3V...
Page 182: ...1 7 Field settings table 6 8 2 ID9E51 Applicable units EHFZ03S18DJ3V Notes 4P596829 1 2019 10...
Page 189: ......
Page 190: ......
Page 191: ......
Page 192: ...4P596821 1A 2020 05 Copyright 2019 Daikin Verantwortung f r Energie und Umwelt...