9.1.2 Guidelines when connecting the electrical wiring
Keep the following in mind:
▪
If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the
covered part and fasten the terminal with the appropriate tool.
b
a
a
Stranded conductor wire
b
Round crimp-style terminal
▪
Use the following methods for installing wires:
Wire type
Installation method
Single-core wire
c b
c
a
a
A
AA´
A´
a
Curled single-core wire
b
Screw
c
Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
Allowed
NOT allowed
Tightening torques
Outdoor unit:
Item
Tightening torque (N•m)
M4 (X1M)
1.2~1.8
M4 (earth)
1.2~1.4
M5 (X1M)
2.0~3.0
M5 (earth)
2.4~2.9
Indoor unit:
Item
Tightening torque (N•m)
X1M
2.45 ±10%
X2M
0.88 ±10%
X5M
0.88 ±10%