11
|
Configuration
Installer reference guide
199
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1 – 2022.01
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t
Time
Example: setpoint (T
U
)≤maximum heat pump temperature–[6‑01] (T
HP MAX
–[6‑01])
t
[6-00]
HP
5
10
20
30
40
43
45
T
U
=T
HP OFF
T
HP MAX
T
DHW
T
HP ON
50
HP
Heat pump. If heating up time by the heat pump takes too long, auxiliary heating by
the backup heater can take place
T
HP MAX
Maximum heat pump temperature at sensor in storage tank
T
HP OFF
Heat pump OFF temperature (T
HP MAX
−[6-01])
T
HP ON
Heat pump ON temperature (T
HP OFF
−[6-00])
T
DHW
Domestic hot water temperature
T
U
User setpoint temperature (as set on the user interface)
t
Time
INFORMATION
The maximum heat pump temperature depends on the ambient temperature. For
more information, see the operation range.
WD curve
When weather dependent operation is active the desired tank temperature is
determined automatically depending on the averaged outdoor temperature: low
outdoor temperatures will result in higher desired tank temperatures as the cold
water tap is colder and vice versa.
"11.4 Weather-dependent curve"
161].
WD curve type
There are 2 methods to define the weather-dependent curves:
▪
2-points
(see
▪
Slope-Offset
(see
162])
In [2.E]
WD curve type
, you can choose which method you want to use.
In [5.E]
WD curve type
, the chosen method is shown read-only (same value as in
[2.E]).
#
Code
Description
[2.E] / [5.E]
N/A
▪
0:
2-points
▪
1:
Slope-Offset
11.5.7 User settings
Overview
The following items are listed in the submenu: