6
|
Application guidelines
Installer reference guide
53
ERGA04~08EAV3(A) + EHBH/X04+08EA/EJ6V+9W
Daikin Altherma 3 R W
4P629085-1 – 2020.08
If… has priority
Then set the priority heater via the
user interface to…
Space heating
Backup heater
Result:
The booster heater (if
applicable) will be turned OFF first.
2
Turns OFF all electrical heaters.
3
Limits the outdoor unit.
4
Turns OFF the outdoor unit.
Example
If the configuration is as follows:
▪
Power limitation level does NOT allow operation of both booster heater and
backup heater (step 1 and step 2).
▪
Priority heater =
Booster heater
(if applicable).
Then power consumption is limited as follows:
P
h
C
e
a
b
c
d
e
A
B
C
P
h
Produced heat
C
e
Consumed energy
A
Outdoor unit
B
Booster heater
C
Backup heater
a
Limited outdoor unit operation
b
Full outdoor unit operation
c
Booster heater turned ON
d
Backup heater step 1 turned ON
e
Backup heater step 2 turned ON
6.7 Setting up an external temperature sensor
You can connect one external temperature sensor. It measures the indoor or
outdoor ambient temperature. We recommend to use an external temperature
sensor in the following cases:
Indoor ambient temperature
▪
In room thermostat control, the dedicated Human Comfort Interface (BRC1HHDA
used as room thermostat) measures the indoor ambient temperature. Therefore,
the Human Comfort Interface must be installed on a location:
-
Where the average temperature in the room can be detected
-
That is NOT exposed to direct sunlight
-
That is NOT near a heat source
-
That is NOT affected by outside air or air draught because of, for example, door
opening/closing
▪
If this is NOT possible, we recommend to connect a remote indoor sensor (option
KRCS01-1).