Unit installation
Installer reference guide
73
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1A – 2022.07
PATTERN 2 and 3
For PATTERN 2 and 3, additionally to the spacing guidelines described in
"7.1.3 Installation site requirements of
69], you also need to comply with the minimum floor area requirements as described in the
following flow chart. The flow chart uses the following tables:
"Table 1: Maximum refrigerant charge allowed in a
"Table 2: Minimum floor area: indoor unit"
75] and
opening area for natural ventilation"
75].
INFORMATION
Multiple indoor units.
If two or more indoor units are installed in a room, you must
consider the maximum refrigerant charge that can be released in the room when a
SINGLE leak occurs.
Example:
If two indoor units are installed in the room, each with
its own outdoor unit, then you have to consider the refrigerant charge of the largest
indoor-outdoor combination.
Input from installer:
▪ Total refrigerant charge (m
c
) (kg)
▪ Area of room A (A
room A
) (m
2
)
Start
Use table 1 in chapter "Technical data" to
calculate the maximum refrigerant charge
(m
max
) (kg) allowed for room A.
Contact your dealer.
Use table 3 in chapter "Technical data" and
dm to calculate the minimum bottom opening
area for natural ventilation between room A
and
room B
(A
nv-min
)
(cm
2
).
The unit can be installed in room A, and
without further room size or ventilation
requirements.
Determine the refrigerant amount that exceeds
m
max
(dm) (kg). (dm=m
c
–m
max
)
m
max
≥m
c
?
Yes
No
No
Use table 2 in chapter "Technical data" to
calculate the total minimum floor area
(A
min total
) (m
2
)
required for the total refrigerant
charge (m
c
).
A
min total
≤A
room A
+A
room B
?
Yes
Input from installer:
▪ Area of adjacent room B (A
room B
) (m
2
)
Unit can be installed in
room A
if you provide 2 openings (one at the bottom, one at the top) between room A and B to ensure natural ventilation. The openings
must comply with the following conditions:
▪
Bottom opening (A
nv
):
▪ Must be a permanent opening that cannot be closed.
▪ Must be completely located between 0 and 300 mm from the floor.
▪ Must be ≥A
nv-min
(minimum bottom opening area).
▪ ≥50% of the required opening area A
nv-min
must be ≤200 mm from the floor.
▪ The bottom of the opening must be ≤100 mm from the floor.
▪ If the opening starts from the floor, the height of the opening must be ≥20 mm.
▪
Top opening:
▪ Must be a permanent opening that cannot be closed.
▪ Must be ≥50% of A
nv-min
(minimum bottom opening area).
▪ Must be ≥1.5 m from the floor.
A
B
A
nv
(≥A
nv-min
)
Min. 50%
of A
nv-min