9
|
Electrical installation
Installer reference guide
113
EPRA08~W1 + ETVH/9W
Daikin Altherma 3 H MT F
4P634886-1 – 2021.03
B
A
B
5 6
1 2 3
X2M
X1A
X11YA
X11YB
X11Y
X5M
9 10
X1M
a
b
c
a
Interconnection cable (=main power supply)
b
Normal kWh rate power supply
c
Preferential power supply contact
3
Fix the cables with cable ties to the cable tie mountings.
INFORMATION
In case of preferential kWh rate power supply, connect X11Y to X11YB. The necessity
of separate normal kWh rate power supply to indoor unit (b) X2M/5+6 depends on
the type of preferential kWh rate power supply.
Separate connection to the indoor unit is required:
▪
if preferential kWh rate power supply is interrupted when active, OR
▪
if no power consumption of the indoor unit is allowed at the preferential kWh
rate power supply when active.
9.3.2 To connect the backup heater power supply
Backup heater type
Power supply
Wires
*6V
1N~ 230 V (6V3)
2+GND
3~ 230 V (6T1)
3+GND
*9W
3N~ 400 V
4+GND
[9.3]
Backup heater
WARNING
The backup heater MUST have a dedicated power supply and MUST be protected by
the safety devices required by the applicable legislation.
CAUTION
To guarantee the unit is completely earthed, ALWAYS connect the backup heater
power supply and the earth cable.
The backup heater capacity can vary, depending on the indoor unit model. Make
sure that the power supply is in accordance with the backup heater capacity, as
listed in the table below.