6 Electrical installation
Installation manual
20
ELSH/X(B)12P30+50E
Daikin Altherma 3 R MT ECH
₂
O
4P708484-1 – 2023.03
a
Drainback connection
b
Spillover connection
c
Hose with non-return valve (1/2")
With installed drainback solar kit (option)
1
Combine the fill and drain kit (option) with the drainback solar
kit (option) to fill the storage tank.
2
Connect the hose with non-return valve to the fill and drain kit.
Follow the steps described in the previous chapter.
5.4.6
To insulate the water piping
The piping in the complete water circuit MUST be insulated to
prevent condensation during cooling operation and reduction of the
heating and cooling capacity.
If the temperature is higher than 30°C and the humidity is higher
than RH 80%, the thickness of the insulation materials should be at
least 20 mm to prevent condensation on the surface of the
insulation.
6
Electrical installation
DANGER: RISK OF ELECTROCUTION
WARNING
▪ All wiring MUST be performed by an authorised
electrician and MUST comply with the applicable
national wiring regulation.
▪ Make electrical connections to the fixed wiring.
▪ All components procured on-site and all electrical
construction MUST comply with the applicable
legislation.
WARNING
ALWAYS use multicore cable for power supply cables.
WARNING
If the supply cord is damaged, it MUST be replaced by the
manufacturer, its service agent or similarly qualified
persons in order to avoid a hazard.
CAUTION
Do NOT push or place redundant cable length into the unit.
NOTICE
The distance between the high voltage and low voltage
cables should be at least 50 mm.
6.1
About electrical compliance
Only for the backup heater of the indoor unit
"6.3.3 To connect the backup heater power supply"
6.2
Guidelines when connecting the
electrical wiring
Tightening torques
Indoor unit:
Item
Tightening torque (N•m)
M4 (X1M)
1.2
M4 (X12M, X15M)
0.88 ±10%
Indoor unit – BUH option:
Item
Tightening torque (N•m)
M4 (X6M) *3V, *6V
2.45 ±10%
M4 (X6M) *9W
1.2
6.3
Connections to the indoor unit
Item
Description
Power supply (main)
See
"6.3.2 To connect the main power
23].
Power supply (backup
heater)
See
"6.3.3 To connect the backup heater
24].
Backup heater
See
"6.3.4 To connect the backup heater to
25].
Shut-off valve
See
"6.3.5 To connect the shut-off
Electricity meters
See
"6.3.6 To connect the electricity
26].
Domestic hot water
pump
See
"6.3.7 To connect the domestic hot
27].