2
Lifestyle functions
Minimum temperature
Settings
Maximum temperature
Heating
Confirm settings
Operating lock
Temperature correction
Switching off
Back
Automatic operation
Service
Day operation
Cooling
Night operation
Display illumination
Target/actual temperature
Loading factory settings
Operating voltage:
230 V ±10 %, 50 Hz
Fuse 230 V: T1AH
Switch. element 230 V: Relay
Switching power:
1 A resistive load
Rated current w/o valve drives:
230 V:
≤2 mA
Max. current draw allowed with
connect. valve drives 230V:
1 A
Temperature setting range:
5 - 30 °C
Connection terminals:
0.22 mm² to 1.5 mm²
Reduction difference:
adjustable
Temperature measurement:
0 - 40 °C
Ambient temperature:
0 - 50 °C
Storage temperature range:
-20 to +70 °C
Admissible ambient humidity:
80%, not condensing
Temp. for ball pressure test:
Terminals: 100 °C
Plastic enclosure: 75 °C
CE conformity according to:
EN 60730
Protection class 230 V: II
Protection degree:
IP 20
Pollution degree: 2
Rated impulse voltage:
1500 V
Type action:
Type 1 / Type 1.C
Weight:
105 g
Dimensions (W x H x D):
86 x 86 x 31 mm
Valve protection function:
Once every 14 days for 10 minutes
after the last triggering.
Antifreeze function:
From +5 °C in heating mode. Inactive
in cooling mode.
Technical data
This symbol means that electrical and electronic products may
NOT be mixed with unsorted household waste. Units must be
treated at a specialized treatment facility for reuse, recycling
and recovery.
By ensuring this product is disposed of correctly, you will help to
prevent potential negative consequences for the environment and
human health.
For more information, contact your installer or local authority.