7.2
Parameter settings via the service code
The parameters of the boiler controller have been configured in the factory in accordance with the following table.
These parameters can only be changed with the service code. Take the following actions to activate the program memory:
1.
Press the
and the button simultaneously, until a
0
appears on the service display and a
0
on the temperature display.
2.
Use the button to enter
15
(service code) on the temperature display.
3.
Use the
button to set the parameter you wish to configure, on the service display.
4.
Use the and button to set the parameter to the required value (visible) on the temperature display.
5.
After all the required changes have been entered, press the button until
P
appears on the service display.
The boiler controller has now been reprogrammed.
Note
Pressing the button will take you out of the menu without saving the parameter changes.
Example: Change maximum CH power
1.
Press the
and the button simultaneously.
2.
Use the button to go to
15
.
3.
Press the
button 3 x. 60 and 3 will appear on the display.
4.
Use the button to change the 60 to 70.
5.
Press the button until
P
appears.
6.
The change has now been implemented. The maximum CH power has been increased from 60 to 70 %.
EKOMBG*ABV1
Parameter Description
22
28
33
Settings reach
0
Service code
[15]
-
-
-
Access to installers settings, the service code must be
entered (=15)
1
Installation type
0
0
0
0= Combi
1= Space h hot water by means of storage tank
2= Tap (hot water only)
3= Solo
2
CH pump setting
0
0
0
0= pump post-running time active
1= pump continuously active
2
–
5 = Not active
3
Set maximum CH power
60
60
60
Setting reach set value parameter c up to 100%
(100 % = 99 + 1x )
3.
Maximum capacity modulating CH pump
80
80
80
Setting reach set value parameter c. up to 100%
4
Set maximum hot water power
99
99
99
Setting reach set value parameter d up to 100%
5
Min. leaving water temperature of the fuel
line
25
25
25
Setting reach 10°C to set value parameter 5
5.
Max setting value leaving water
temperature via operating panel
90
90
90
Setting reach 30°C to 90°C
6
Min. outdoor temperature of the fuel line
-7
-7
-7
Setting reach -30 to 10°C
7
Max. outdoor temperature of the fuel line
25
25
25
Setting reach 15°C to 30°C
8
CH pump post-running time after CH
operation
1
1
1
Setting reach 0 to 15 minutes
9
CH pump post-running time after boiler
operation
1
1
1
Setting reach 0 to 15 minutes (n/a to Combi unit)
A
Setting three-way valve or electrical valve
0
0
0
0= powered during CH operation
1= powered during hot water operation and rest
2= powered during every heat request (CH, hot water and
continuous heating function)
3= group regulation
4 and higher = Not applicable
Summary of Contents for EKOMBG22ABV1
Page 29: ...Daikin Europe NV 31...
Page 82: ...Daikin Europe NV 31...
Page 136: ...Daikin Europe NV 32...
Page 189: ...Daikin Europe NV 31...
Page 242: ...Daikin Europe NV 32...
Page 295: ...Daikin Europe NVs GmbH 31...
Page 347: ...Daikin Europe NV 31...
Page 372: ...Daikin Europe NV 4 Daikin EKOMBG22ABV1 EKOMBG28ABV1 EKOMBG33ABV1 CH DHW O...
Page 377: ...Daikin Europe NV 9 3 A CH L B C M D S1 N X4 E S2 O F P S3 G Q H R I 230 V S J T K U...
Page 381: ...Daikin Europe NV 13 4 2 1 2 cm O 4 2 1 50 cm2 4 2 2 A 1 2 70 C a b DHW c d e...
Page 382: ...Daikin Europe NV 14 4 3 EKVK4AA B 4 3 1 4 3 2...
Page 387: ...Daikin Europe NV 19 5 3 1 3 mm 1 2 A 3 1 4 2 5 6 10 2 7 8 5 3 1 X4 6 7 11 12 8 9 6 7...
Page 389: ...Daikin Europe NV 21 RF CH 5 RF CH 2 C rF L RF RF 1 5 4 4 10 1 7 5 5 5 1 1 2 2 3 4 50 mbar 5...
Page 391: ...Daikin Europe NV 23 5 2 CE B23 B33 C13 C33 C43 CLV C53 C63 CE...
Page 398: ...Daikin Europe NV 30 5 5 5 O 1 5 3 250 mm 2000 mm 1000 mm 1 500 mm...
Page 399: ...Daikin Europe NV 31...
Page 405: ...Daikin Europe NV 37 6 3 1 2 3 4 5 6 6 3 1 10 2...
Page 406: ...Daikin Europe NV 38 7 7 1 LED CH bar q 0 Su Et q LED Eco LED LED 8 2 LED 2 LED LED LED 30...
Page 414: ...Daikin Europe NV 46 8 3 8 3 1 7 7 7 8 8 3 2 20 mbar 7 7 7 8 8 3 3 CH 10 1 OpenTherm CH RF 80...
Page 417: ...Daikin Europe NV 49 9 9 1 1 1 2 3 4 5 6 7 1 2 3 8 4 5 6 9 10 11 Allen 12 9 1 2 1 2 3 4 5...
Page 418: ...Daikin Europe NV 50 9 1 3 1 2 O 10 12 Nm 3 4 5 6 1 2 3 A 7 8 9 10 CH 11 12 13 14 7 7 7 8 15 16...
Page 423: ...Daikin Europe NV 55 11 Daikin Europe NV CH...
Page 424: ...008 1548499_04 05 2022 88550712...