6 Configuration
Installation manual
28
EKMBPP1
Modbus adapter
4P720139-1B – 2023.09
Holding register
Address
Name
Range
Description
H0056
–
–
–
Reserved for future use
H0057
–
–
–
Reserved for future use
6.5
Readback data
All readback data is available in the input registers.
6.5.1
Remote controller readback
Input register Address
Name
Range
I0050
30051
Remote controller temperature
(for 1 indoor unit only)
°C multiplied by 100 (available for 1
indoor unit only)
I0051
30052
Remote controller operation
mode (group)
(a)
▪ 0: Idle/Fan
▪ 1: Heating
▪ 2: Cooling
▪ 3: Heating and cooling
(a)
For IAQ units, or when operation mode is set to Ventilation, the register
value is fixed at 0.
INFORMATION
The remote controller temperature sensor value (
I0050)
is
only available if there is only 1 indoor unit on the P1P2
network. In addition, the remote controller (if present) has to be
configured as Sub. When there are multiple indoor units, or
when the remote controller (if present) is configured as Main,
the register is fixed at 0.
6.5.2
Group readback
Group data registers provide a summary of the data from all active
indoor units on the network.
Input register
Address
Name
Range
Description
I0020
30021
Unit Count
0~16
Number of units found on the
network
I0021
30022
Is Error
0~1
▪ 0: No error
▪ 1: At least 1 unit in error
I0022
30023
Error Code
0~65535
▪ 255: No error
▪ Other values: error code from
first unit in error
I0023
30024
Return Air Average
°C × 100
Average of all unit return air
temperatures