Technical data
Daikin EKHWP/EKHWC/EKHWD
Daikin High-efficiency hot water storage tank
008.1618744 – 03/2017
Installation and operating instructions
29
9.1.3 EKHWP
Non-pressurised (DrainBack) - DB
Unit
EKHWP300B
EKHWP500B
Energy Labelling Regulation: (EU) 812/2013 / Ecodesign Regulation: (EU) 814/2013
Energy efficiency class
—
B
Standing loss
W
64
72
Hot water storage tank volume
litres
294
477
basic data
Empty weight
kg
58
82
Total filled weight
kg
359
593
Dimensions (L x W x H) without switching unit from E-PAC
cm
59.5 x 61.5 x 164.6
79 x 79 x 165.8
Tilt dimension
cm
163
167
Maximum permissible storage water temperature
°C
85
Heat consumption at stand-by and at 60 °C
kWh/24h
1.3
1.4
Drinking water heat exchanger (stainless steel 1.4404)
potable water capacity
litres
27.9
Maximum operating pressure
bar
6
Domestic water heat exchanger surface
m
2
5.8
6.0
Storage tank charging heat exchanger (stainless steel 1.4404)
Water capacity heat exchanger
litres
13.2
18.5
Heat exchanger surface area
m
2
2.7
3.8
Solar heating backup (stainless steel 1.4404)
Water capacity heat exchanger
litres
—
2.3
Heat exchanger surface area
m
2
—
0.5
Heat technics power data
Volume of hot water without reheating at draw-off rate
(8 l/
3)
/ 12 l/min
4)
) (T
KW
= 10 °C / T
WW
= 40 °C / T
SP
= 50 °C)
litres
184
3)
/ 153
4)
364
3)7)
/ 318
4)7)
328
3)8)
/ 276
4)8)
Volume of hot water without reheating at draw-off rate
(8 l/
4)
/ 12 l/min
4)
) (T
KW
= 10 °C / T
WW
= 40 °C / T
SP
= 60 °C)
litres
282
3)
/ 252
4)
540
3)
/ 494
4)
Volume of hot water without reheating at draw-off rate
(8 l/
4)
/ 12 l/min
4)
) (T
KW
= 10 °C / T
WW
= 40 °C / T
SP
= 65 °C)
litres
352
3)
/ 321
4)
612
3)
/ 564
4)
Reheating time (Wh) with a draw-off quantity (bathtub: 140 l
5)
/
shower: 90 l
6)
)
(T
KW
=10 °C / T
WW
=40 °C / T
SP
=50 °C)
min
45
5)9)
/ 30
6)9)
25
5)10)
/ 17
6)10)
Pipe connections
Cold and hot water
inches
1" AG
Heating flow / return flow
inches
1" IG / 1" AG
Solar connections
inches
1" IG
Tab. 9-4 Basic data EKHWP - DrainBack
7)
Charging by heat pump and electric booster heater.
8)
Charging only by heat pump without electric booster heater.
9)
With heat pump 8 kW.
10) With heat pump 16 kW.