Technical data
9
Technical data
9.1
Basic data
9.1.1 EKHWD
Not all the hot water storage tanks listed here are
offered certain countries.
Unit
EKHWDH500B
EKHWDB500B
Energy Labelling Regulation: (EU) 812/2013 / Ecodesign Regulation: (EU) 814/2013
Energy efficiency class
—
B
Standing loss
W
72
Hot water storage tank volume
litres
477
basic data
Empty weight
kg
73
76
Total filled weight
kg
585
591
Dimensions (L x W x H)
cm
79 x 79 x 165.8
Tilt dimension
cm
167
Maximum permissible storage water temperature
°C
85
Heat consumption at stand-by and at 60 °C
kWh/24 h
1.4
Drinking water heat exchanger (stainless steel 1.4404)
Water capacity heat exchanger
litres
24.5
Maximum operating pressure
bar
6
Domestic water heat exchanger surface
m
2
5
1. Storage tank charging heat exchanger (stainless steel 1.4404)
Water capacity heat exchanger
litres
11.0
Heat exchanger surface area
m
2
2.2
2. Storage tank charging heat exchanger (stainless steel 1.4404)
Water capacity heat exchanger
litres
—
10.9
Heat exchanger surface area
m
2
—
2.2
Heat technics power data
Output characteristic N
L
in accordance with DIN 4708
1)
4.1
4.4 / 4.8
2)
Continuous output Q
D
according to DIN 4708
kW
35
50 / 50
2)
Maximum draw-off rate for the duration of 10 min on recharging
at 35 kW (T
KW
= 10 °C / T
WW
= 40 °C / T
SP
=60 °C)
l/min
30
31 / 34
2)
Hot water quantity without reheating with up to 15 l/min draw-off
rate (T
KW
= 10 °C/T
WW
= 40 °C/T
SP
= 60 °C)
litres
420
Hot water volume with post-heating at 15 l/min draw-off rate
(post-charge output 20 kW)
(T
KW
=10 °C / T
WW
=40 °C / T
SP
=60 °C)
litres
970
Short-term water quantity in 10 min
litres
310
Pipe connections
Cold and hot water
inches
1" AG
Heating feed and return flow
inches
1" IG / 1" AG
Tab. 9-1 Basic data EKHWD
1) With post-charging at 35 kW, 80 °C flow temperature, 65 °C storage tank temperature, 45 °C hot water temperature
;
10 °C cold water temperature.
2)
With parallel connection of both storage tank charging heat exchangers.
3)
Data applies to draw-off rate of 20 l/min.