7 Configuration
Installation manual
14
EKHWET90~120BAV3
R32 Split series – Domestic hot water tank
4P680074-1 – 2021.11
1234
Advanced user
User pin code
The
User
pin code is
0000
.
0000
User
To access the installer settings
1
Set the user permission level to
Installer
.
2
Go to [9]:
Installer settings
.
To modify an overview setting
Example:
Modify [2‑02] from 23 to 3.
Most settings can be configured via the menu structure. If for any
reason it is required to change a setting using the overview settings,
then the overview settings can be accessed as follows:
1
Set the user permission level to
Installer
. See
change the user permission level"
13].
—
2
Go to [9.I]:
Installer settings
>
Overview
field settings
.
3
Turn the left dial to select the first part of the setting
and confirm by pressing the dial.
00
01
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
0
1
2
3
4
Turn the left dial to select the second part of the
setting
00
01
23
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
2
5
Turn the right dial to modify the value from 23 to 3.
00
01
3
02
03
04
05
06
07
08
09
0A
0B
0C
0D
0E
2
6
Press the left dial to confirm the new setting.
7
Press the center button to go back to the home
screen.
INFORMATION
When you change the overview settings and you go back
to the home screen, the user interface will show a popup
screen and request to restart the system.
When confirmed, the system will restart and recent
changes will be applied.
7.2
Configuration wizard
After first power ON of the system, the user interface starts a
configuration wizard. Use this wizard to set the most important initial
settings for the unit to run properly. If required, you can afterwards
configure more settings. You can change all these settings via the
menu structure.
Protective functions
The unit is equipped with the following protective function:
▪ Tank disinfection [2-01]
The unit automatically runs the protective function when necessary.
During installation or service, this behaviour is undesired. Therefore,
the protective function can be disabled.
7.2.1
Configuration wizard: Language
#
Code
Description
[7.1]
N/A
Language
7.2.2
Configuration wizard: Time and date
#
Code
Description
[7.2]
N/A
Set the local time and date
INFORMATION
By default, daylight savings time is enabled and clock
format is set to 24 hours. These settings can be changed
during initial configuration or via the menu structure [7.2]:
User settings
>
Time/date
.
7.2.3
Configuration wizard: System
Indoor unit type
The indoor unit type is displayed, but cannot be adjusted.
Domestic hot water
The tank type is displayed, but cannot be adjusted.
Emergency
When the heat pump fails to operate, the booster heater can serve
as an emergency heater. It then takes over the heat load either
automatically or by manual interaction.
▪ When
Emergency
is set to
Automatic
and a heat pump failure
occurs, the booster heater in the tank automatically takes over the
domestic hot water production.
▪ When
Emergency
is set to
Manual
and a heat pump failure
occurs, the domestic hot water heating stops.
To manually recover it via the user interface, go to the
Malfunctioning
main menu screen and confirm whether the
booster heater can take over the heat load or not.
To keep energy consumption low, we recommend to set
Emergency
to
Manual
if the house is unattended for longer periods.
#
Code
Description
[9.5.1]
[4-06]
▪ 0:
Manual
▪ 1:
Automatic
INFORMATION
The auto emergency setting can be set in the menu
structure of the user interface only.
Booster heater capacity
The capacity of the booster heater must be set for the energy
metering and/or power consumption control feature to work properly.
When measuring the resistance value of the booster heater, you can