EKHVWQ0 E260AA1V3

Domestic hot water heat pump

4PW65343-1A – 10.2010

Operation manual

14

Automatic set point operation

This operation mode contains a learning function to predict
the daily hot water consumption. It will calculate and predict
the optimum tank temperature setpoint based on the user
tapping history.
Enabling this operation mode will keep the tank temperature
as low as possible but to a temperature which guarantees a
high comfort level.

The advantage of a low tank temperature setpoint are :

-

Reduced heatlosses

-

Better unit performance, the lower the tank temperature the 
better the heat up coefficient of performance (COP). 

-

Lower electric power consumption

Domestic water heating modes

DHW_temp_scheme

A

Normal or automatic domestic hot water tank operation 
(if activated)

B

Reheat operation (if activated)

C

Disinfection operation (if activated)

D

Powerful operation

Field settings

E

Disinfection operation temperature

F

Normal or automatic domestic hot water tank temperature

G

Powerful temperature set point

H

Reheat maximum water temperature 

J

Reheat minimum water temperature

t

Time

T

Domestic hot water tank temperature

[0] Different operation modes

[0-00] Powerfull operation mode temperature set point

[0-01] Disinfection operation mode temperature set point

[0-02] Temperature setpoint: reheat minimum temperature

[0-03] Temperature setpoint: reheat maximum temperature

[0-04] Reheat function enabled/disabled: defines whether the
reheat operation is turned ON(1) or OFF(0)

[1] Automatic domestic hot water tank temperature set point

calculation

[1-00] Renewal time for set point calculation

The automatic temperature set point calculation is done on a
daily basis. The algorithm calculates for each day of the week an
optimum domestic hot water tank temperature set point. To
calculate this temperature setpoint, the learning function
monitors per 24 hours the domestic water heating demand and
based on this demand calculates the optimum set point for that
specific day of the week.

This field setting contains the starting time for the 24 hours
monitoring period.

This field setting must be set preferably after the main heating
up of the domestic water of the day has finished.
For example: If in schedule timer operation mode the schedule
timer was set from 22 h until 6 h, the renewal time should be set
at 6 h.

[1-01] Minimum automatic temperature set point

If required the minimum temperature set point for the automatic
set point calculation can be adjusted. If, for example,
considerable heatlosses are expected on the field piping
between the hot water tap and the domestic hot water heat
pump, this temperature set point can be usefull.

[1-02] Maximum automatic temperature set point

The maximum temperature that the automatic set point can
reach.

However, if this value is set on a temperature higher than 60°C,
that maximum temperature will only be reached when field
setting [3-02] is set to 1 (ON). If the setting of [3-02] is 0, the
maximum temperature will be 60°C (only heating up by heat
pump) ignoring higher set temperatures.

A

B

C

D

E

F

H

J

T

t

G

Summary of Contents for EKHHS200AA1V3

Page 1: ...OPERATION MANUAL EKHVWQ002AAV3 EKHHS200AA1V3 EKHHS260AA1V3 Domestic hot water heat pump ...

Page 2: ...ance activities 16 7 3 Standstill 16 8 Troubleshooting 17 9 Disposal requirements 17 The English text is the original instruction Other languages are translations of the original instructions This appliance is not intended for use by persons including children with reduced physical sensory or mental capabilities or lack of experience and knowledge unless they have been given supervision or instruc...

Page 3: ...s a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be used to alert against unsafe practices NOTICE Indicates situations that may result in equipment or property damage accidents only INFORMATION This symbol identifies useful tips or additional information Electric current Danger of burning and scalding DANGER ELECTRICAL SHOCK Switch off all ...

Page 4: ...nual 4 1 Domestic water heating operation quick start up Schedule timer operation Continuous operation Powerful operation INFORMATION Refer to the installation manual of the unit for installation procedures Icon p is displayed a a To display or remove the p icon press the pr button Schedule timer operation Push the ba button Push the Y button Push the Y button The 0 LED will light up and the unit ...

Page 5: ...fers full control over your installation Basic controller functions The basic controller functions are Turning the unit ON OFF Schedule timer continuous mode Selection of features quiet mode refer to page 8 auto adaptive set point control refer to page 9 Temperature set point adjustment refer to page 6 Powerful mode The digital controller supports a power cut off of maximum 2 hours When autorestar...

Page 6: ...ailable 14 DEFROST MODE ICON d This icon indicates that the defrost mode is active 15 COMPRESSOR ICON ç This icon indicates that the compressor of the heat pump unit is active When freeze protection mode is active this icon is blinking 16 BOOSTER HEATER ICON m This icon indicates that the booster heater is active The booster heater provides auxiliary heating for the domestic hot water tank if a hi...

Page 7: ...e by 10 minutes 3 Use the wi or wj button to adjust the day of the week Each time the wi or wj button is pressed the next or previous day is displayed 4 Press the button to confirm the current set time and day of the week To leave this procedure without saving press the pr button If no button is pressed for 5 minutes the clock and day of the week will return to their previous setting Setting the sc...

Page 8: ... command It is clear that the last programmed command may date from the day before Refer to Consulting programmed actions on page 12 INFORMATION Default the schedule timer is set as follows Time Set point temperature Sunday until thursday 7 4 22 6 h 45 C Friday and saturday 5 6 22 6 h 55 C If this does not fullfill the customers demands it has to be set as explained in Programming and consulting th...

Page 9: ...he desired quiet mode is set through a field setting Refer to the field settings explained in the installation manual for a detailed description how to set one or more field settings Disinfection operation This mode will disinfect the domestic hot water tank by periodically heating the domestic water to a specific temperature During the operation of this mode the w icon will be blinking slowly with 0 ...

Page 10: ...more actions are programmed for the same day and at the same time only the action with the lowest action number will be executed You can always alter add or remove the programmed actions later Example 1 Example 2 If on mondays the customer is usually at home and uses a lot of hot water the set point for monday will increase untill the required amount of hot water is reached as shown in the figure b...

Page 11: ...s e g 4 and 5 are not displayed 7 Press the button for 5 seconds to enter the programming mode 8 Use the button to select the action number you would like to program or to modify 9 Use the pi and pj buttons to set the correct action time 10 Use the ba button to select x to switch heating and the controller off 9 set the temperature by means of the wi and wj buttons 11 Repeat steps 8 to 10 to progr...

Page 12: ...rogramming mode 6 Use the button to select the action number you would like to program or to modify 7 Use the pi and pj buttons to set the correct action time 8 Use the ba button to select or deselect x as action 9 Repeat steps 6 to 8 to program the other actions of the selected mode When all actions have been programmed make sure that the display shows the highest action number you would like to ...

Page 13: ...i e after pressing the button for 5 seconds press the pr button once You can now select another day by using the pi and pj buttons and restart consulting and programming Copying programmed actions to next day In heating mode program it is possible to copy all programmed actions of a specific day to the next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day p...

Page 14: ...on If the P button is pressed the heat pump module heats up the domestic hot water tank as fast as possible to a predefined setpoint This means that the inverter compressor frequency will be higher then in normal operation mode and that sound level and power consumption can be higher This mode might be usefull when exceptional high hot water consumption depletes all the available domestic hot water...

Page 15: ...ed defines whether the reheat operation is turned ON 1 or OFF 0 1 Automatic domestic hot water tank temperature set point calculation 1 00 Renewal time for set point calculation The automatic temperature set point calculation is done on a daily basis The algorithm calculates for each day of the week an optimum domestic hot water tank temperature set point To calculate this temperature setpoint the ...

Page 16: ...lated setting 1 ON 02 Installation related setting 23 00 03 Installation related setting 0 OFF 04 Installation related setting 32 3 Miscellaneous 00 Installation related setting 1 ON 01 Installation related setting 3 02 Installation related setting 0 OFF 03 Installation related setting 0 OFF 4 Miscellaneous 03 Installation related setting 0 04 Installation related setting 1 6 Miscellaneous 00 Inst...

Page 17: ...dissipate this gas safely it is recommended that a hot tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open flame or any electrical appliance operating nearby If hydrogen is discharged through the tap it will probably make a sound as of air escaping Each inspection has to be carried...

Page 18: ...zed treatment facility for re use recycling and recovery By ensuring this product is disposed off correctly you will help to prevent potential negative consequences for the environment and human health Please contact the installer or local authority for more information NOTES POSSIBLE CAUSES CORRECTIVE ACTIONS No readings on the remote controller blank display Check if the mains power is still con...

Page 19: ......

Page 20: ...4PW65343 1A 10 2010 Copyright 2010 Daikin ...

Reviews: