Installation manual
39
EKHBRD011~0Y17
Indoor unit for air to water heat pump system
4P402191-1B – 2017.09
A
NNEX
General overview and guide to start up the unit
Space heating
Push the
button
Temperature set point
start blinking
"
"
You selected remote
controller room
temperature
thermostat operation?
[8-00]=1, default
(
)
Room
temperature
You selected leaving
water control operation
[8-00]=0 (
)
Yes
Yes
No
No
You selected multiple
set point control
operation pattern B
including remote room
thermostat controller
control?
[7-02]=1 and ([7-03]=1
or/and [7-04]=1)
(
)
Yes
Room
temperature
External room thermostat
temperature
Yes You selected external
room thermostat
operation [6-01]=1
(
)
No
External room thermostat
temperature
Yes You selected multiple
set point control
operation pattern B
including external room
thermostat
[7-02]=1 and ([7-03]=1
or/and [7-04]=1)
[6-01]=1 (
)
What type of appliance do you
have?
No
Blank display
Push the
button
"
"
You selected
permission level 3 on
remote controller
[0-00]=3 (
)
You selected
automatic leaving
water control
(
)
[A-03]
or/and
[A-04]
Water
temperature
[A-03]
or/and
[A-04]
Yes You selected multiple
set point control
operation pattern A
[7-02]=0 and ([7-03]=1
or/and [7-04]=1)
(
)
Shift value
Push
ON/OFF
What type of appliance do you have?
▼
▼
▼
Floor heating
Radiator
Fan coil
▼
Yes
High temperature?
No
▼
▼
▼
▼
∆
T: 5°C [A-02]
∆
T: 10°C [A-02]
default value
∆
T: 5°C [A-02]
∆
T: 5°C [A-02]
▼
▼
▼
▼
Automatic leaving
water temperature?
No
Automatic leaving
water temperature?
No
Automatic leaving
water temperature?
No
Automatic leaving
water temperature?
No
Yes
Yes
Yes
Yes
▼
▼
▼
▼
▼
▼
▼
▼
Automatic leaving
water settings
[3-00]=–10
[3-01]=15
[3-02]=40
[3-03]=25
35°C
Automatic leaving
water settings
[3-00]=–10
[3-01]=15
[3-02]=70
[3-03]=45
65°C
Automatic leaving
water settings
[3-00]=–10
[3-01]=15
[3-02]=55
[3-03]=40
50°C
Automatic leaving
water settings
[3-00]=–10
[3-01]=15
[3-02]=50
[3-03]=35
45°C
4PEN402191-1B_2017_09.book Page 39 Friday, October 6, 2017 7:03 PM