Operation manual

3

EKHBRD011~Y1

Indoor unit for air to water heat pump system and options

4PW60971-1

Remote controller buttons and icons

1.

ON/OFF BUTTON 

y

The ON/OFF button starts or stops the space heating.

Pressing the ON/OFF button consecutively too many times may
cause malfunction of the system (maximum 20 times per hour).

2.

OPERATION LED 

0

The operation LED is lit during space heating operation. The
LED blinks if a malfunction occurs. When the LED is OFF, space
heating is inactive while the other operation modes can still be
active.

3.

OPERATION MODE ICONS 

h

,

 w

,

 s

These icons indicate the current operation mode(s): space
heating (

h

), domestic water heating (

w

) or quiet mode (

s

).

Within limits, different modes can be combined, e.g. space
heating and domestic water heating. The corresponding mode
icons will be displayed simultaneously.

If the domestic hot water tank is not installed, the 

w

  icon will

never be displayed.

4.

EXTERNAL CONTROL ICON 

e

This icon indicates that the outdoor unit is working in a forced
operation. As long as this icon is displayed, the remote controller
cannot be operated.

5.

DAY OF THE WEEK INDICATOR 

1234567

This indicator shows the current day of the week.

When reading or programming the schedule timer, the indicator
shows the set day.

6.

CLOCK DISPLAY 

8

The clock display shows the current time.

When reading or programming the schedule timer, the clock
display shows the action time.

7.

SCHEDULE TIMER ICON 

p

This icon indicates that the schedule timer is enabled.

8.

ACTION ICONS 

q

These icons indicate the programming actions for each day of
the schedule timer.

9.

OFF ICON 

x

This icon indicates that the OFF action is selected when
programming the schedule timer.

10.

INSPECTION REQUIRED 

k

 and 

l

These icons indicate that inspection is required on the
installation. Consult your dealer.

11.

TEMPERATURE DISPLAY 

9

The display shows the current temperature of the installation
either leaving water temperature or actual room temperature.

When changing the room temperature set point, the set point will
be 

fl

ashing for 5 seconds and then return to the actual room

temperature.

12.

SETTING 

$

Not used. For installation purposes only.

13.

NOT AVAILABLE 

n

This icon is displayed whenever a non-installed option is
addressed or a function is not available. A function not available
can mean insuf

fi

cient permission level or can mean that a slave

remote controller is used (see installation manual).

14.

DEFROST/START UP MODE ICON 

d

This icon indicates that the defrost/start up mode is active.

15.

COMPRESSOR ICON 

ç

This icon indicates that the compressor in the outdoor unit of the
installation is active.

16.

HEATER STEP 

(

If the heater kit option is installed, 

(

 icon indicate that the heater

is operating.

17.

PUMP ICON 

é

This icon indicates that the circulation pump is active.

18.

OUTDOOR TEMPERATURE DISPLAY 

u

When this icon is 

fl

ashing, the outdoor ambient temperature is

displayed. Refer to "Temperature read-out mode" on page 9 for
more information.

19.

WEATHER DEPENDENT SET POINT ICON 

a

This icon indicates that the controller will adapt the leaving water
temperature set point automatically, based on the outdoor
ambient temperature.

20.

TEMPERATURE ICON 

b

This icon is displayed when the actual room temperature or
room temperature set point are shown.

The icon is also displayed when the temperature set point is set
in schedule timer programming mode. Refer to "Temperature
read-out mode" on page 9 f
or more information.

21.

TEST OPERATION ICON 

t

This icon indicates that the unit runs in test mode.

22.

FIELD SET CODE 

;

This code represents the code from the 

fi

eld set list. Refer to the

"Field settings table" on page 16.

23.

ERROR CODE 

:

This code refers to the error code list and is for service purposes
only. Refer to the error code list in the installation manual.

NOTE

Remark that pushing the 

y

  button has no

in

fl

uence on the domestic water heating.

Domestic water heating is only switched on or off
by  means of the 

w

  button and/or disabling the

storage schedule timer.

1

3

5

6 23

8

13

33

24

11

18

20

14

4

7
9

12

10
21

32

25

26

22

19

31
30
29

27

28

2

17

15

16

Master

Slave

Permission

level 2

level 3

Operation ON/OFF

Domestic water heating operation 
ON/OFF

Setting the leaving water temperature

Setting the room temperature

Quiet mode ON/OFF

Weather dependent set point operation 
ON/OFF

Setting the clock

Programming the schedule timer

Schedule timer operation ON/OFF

Field settings

Error code display

Test operation

 = operable

Summary of Contents for EKHBRD014ABV1

Page 1: ...OPERATION MANUAL EKHBRD011ABV1 EKHBRD014ABV1 EKHBRD016ABV1 EKHBRD011ABY1 EKHBRD014ABY1 EKHBRD016ABY1 Indoor unit for air to water heat pump system and options...

Page 2: ...es or lack of experience and knowledge unless they have been given supervision or instruction concerning use of the appliance by a person responsible for their safety Children should be supervised to...

Page 3: ...e rp button See Automatic storage on page 7 The p icon will display Hot water will be produced at next scheduled action When water heat up starts the w icon will be blinking 1 second interval Manual s...

Page 4: ...used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available A function not available can mean insufficien...

Page 5: ...seconds the display will show to the actual room temperature 32 QUIET MODE BUTTON s This button enables or disables quiet mode If the controller is set to permission level 2 or 3 refer to Field setti...

Page 6: ...oor temperatures will result in warmer water and vice versa The unit has a floating set point Activating this operation will result in a lower power consumption than use with a manually fixed leaving...

Page 7: ...k function is turned ON 1 or OFF 0 2 01 Start time time at which setback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop Domestic wat...

Page 8: ...storage temperature set point is reached It is a one time hot water making feature Selecting manual storage operation for domestic water heating 1 Push and hold the w button for 5 seconds to activate...

Page 9: ...er Field settings on page 15 for a detailed description how to set one or more field settings 4 00 Status defines whether the disinfection function is turned ON 1 or OFF 0 4 01 Operation interval day...

Page 10: ...multaneous demand of space heating and domestic water heating The unit can not perform domestic water heating and space heating at the same time If both modes are requested at the same time the unit w...

Page 11: ...eating stays enabled When pushing the r p button The schedule timer for space heating and domestic water heating along with the quiet mode will be stopped and will not start again The schedule timer i...

Page 12: ...tion 3 When both setback function and schedule timer are enabled A Setback function B ON OFF instruction t Time T Temperature set point Room temperature Leaving water temperature t 18 18 C 60 60 C 60...

Page 13: ...e repeated on a weekly basis In the domestic water heating and quiet mode program depending on remote controller model 4 or 5 actions can be programmed per mode The same actions are repeated on a dail...

Page 14: ...s the button for 5 seconds to store the programmed actions If the button is pressed when action number 3 is displayed actions 1 2 and 3 are stored but 4 and 5 are deleted You automatically return to s...

Page 15: ...step 2 by pressing the pr button 5 Press the and pr buttons simultaneously for 5 seconds After 5 seconds the display will show the next day e g 2 if 1 was selected first This indicates that the day h...

Page 16: ...Press the z button for a minimum of 5 seconds to enter FIELD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2...

Page 17: ...10 20 1 C 02 Set point at low ambient temperature Lo_Ti 70 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 45 25 80 1 C 4 Disinfection function 00 Status disinfection operation 1 ON 0 1 01 D...

Page 18: ...age temperature 70 45 75 1 C 04 Automatic maximum hot water tank storage temperature 70 55 75 1 C C Leaving water temperature limits 00 Installation related setting 80 37 80 1 C 01 Installation relate...