Operation manual

7

EKCBX/H008BBV3

Unit for air to water heat pump system

4PW67442-1A – 12.2010

Quiet mode operation (

s

)

Quiet mode operation means that the outdoor unit works at reduced
capacity so that the sound produced by the outdoor unit drops. This
implies that the indoor heating (and cooling) capacity will also drop.
Beware of this when a certain level of heating (or cooling) is required
indoors.

4.6.

Controller operations

Manual operation

In manual operation, the user manually controls the settings of the
installation. The last setting remains active until the user changes it or
until the schedule timer forces another setting (refer to 

"Schedule

timer operation" on page 8

).

As the controller can be used for a wide variety of installations, it is
possible to select a function which is not available on your
installation. In that case the message 

n

 will appear.

Switching on and setting space heating (

h

) and space cooling

(

c

)

1

Use the 

=

 button to select space heating (

h

) or space cooling

(

c

).

Icon 

h

 or 

c

 appears on the display as well as the corresponding

water temperature set point.

2

Use the 

bi

 and 

bj

 buttons to set the desired water

temperature.

Temperature range for heating: 25°C to 55°C
The temperature for heating can be set as low as 15°C (see

"Field settings" on page 13

). However, the temperature for

heating should only be set lower than 25°C during
commissioning of the installation. When set lower than 25°C,
only the backup heater will operate (in case EKMBUHBA6V3
is installed). 
In order to avoid overheating, space heating is not operable
when the outdoor ambient temperature rises above a certain
temperature (as set through field setting [4-02], refer to 

"Field

settings" on page 13

).

Temperature range for cooling: 5°C to 22°C

3

Switch on the unit by pushing the 

y

 button.

The operation LED 

0

 lights up.

Selection and setting of domestic water heating (

w

)

1

Use the 

v

 button to activate domestic water heating (

w

).

Icon 

w

 appears on the display.

2

Use the 

wi

 or 

wj

 button to display the actual

temperature set point and subsequently, to set the correct
temperature.

The actual temperature set point only appears on the display
after pressing one of the buttons 

wi

 or 

wj

. If no button is

pressed for 5 seconds, the temperature set point will
automatically disappear from the display again.
Temperature range for domestic water heating: 30°C to 78°C

3

Press the 

v

 button to deactivate domestic water heating (

w

).

Icon 

w

 disappears from the display.

Selecting powerful domestic water heating operation

1

Press 

v

 for 5 seconds to activate powerful domestic water

heating operation.

Icons 

w

 and 

m

 start flashing.

Powerful domestic water heating is deactivated automatically
when the set point for the domestic hot water is reached.

Selecting quiet mode operation (

s

)

1

Use the 

s

 button to activate quiet mode operation (

s

).

Icon 

s

 appears on the display.

If the controller is set in permission level 2 or 3 (refer to 

"Field

settings" on page 13

), the 

s

 button will not be operable.

Selecting weather dependent set point operation (only in
heating mode)

1

Press the 

ba

 button to select weather dependent set point

operation.

Icon 

a

 appears on the display as well as the calculated water

temperature set point based on the outdoor temperature.

2

Use the 

bi

 or 

bj

 button to display the actual shift value

and subsequently, to set the correct value.

The shift value only appears on the display after pressing one of
the buttons 

bi

 or 

bj

. If no button is pressed for 5

seconds, the shift value will automatically disappear from the
display again.

Range for the shift value: –5°C to +5°C

CAUTION

The actual operation range depends on the values set on
field setting [9].

These values shall be determined based on the
application.

INFORMATION

In heating mode (

h

) or in cooling mode (

c

), the water

temperature set point can also be weather dependent (icon

a

 is shown).

This means that the controller calculates the water
temperature set point based on the outdoor temperature.

In this case the controller shows the calculated controller
set point. The 

bi

 button or 

bj

 button can be used to

display the actual "shift value" and subsequently, to set the
correct value. This shift value is the temperature difference
between the temperature set point calculated by the
controller and the real set point. E.g. a positive shift value
means that the real temperature set point will be higher
than the calculated set point.

INFORMATION

When the unit is connected to an external room
thermostat, buttons 

=

 and 

y

 are not operable and the

icon 

e

 is shown. In this case, the external room

thermostat switches the unit on or off and determines the
operation mode (space heating or space cooling).

INFORMATION

The domestic hot water set point set on the controller
is the actual domestic hot water set point ([4-03]=0, 1,
2, or 3) or the domestic hot water storage set point
([4-03]=4). See 

"Domestic water heating operation

(

w

)" on page 6

.

INFORMATION

Remark that pushing the 

y

 button has no influence on

the domestic water heating. Domestic water heating is only
switched on or off by means of the 

v

 button.

Summary of Contents for EKCBX008BBV3

Page 1: ...OPERATION MANUAL EKCBX008BBV3 EKCBH008BBV3 Unit for air to water heat pump system...

Page 2: ...manual speci ed for a certain product or application explaining how to install con gure and maintain it Operation manual Instruction manual speci ed for a certain product or application explaining how...

Page 3: ...er Refer to the operation manual of the indoor unit and to the installation manual of the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB...

Page 4: ...tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open ame or any electrical applia...

Page 5: ...9 OFF ICON x This icon indicates that the OFF action is selected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installatio...

Page 6: ...ing the clock 33 DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS wbi and wbj These buttons are used to adjust the current set point of the domestic hot water temperature only for 4 03 0 1 2 or 3 These b...

Page 7: ...unit will immediately heat up the domestic water tank untill domestic hot water storage set point upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a sc...

Page 8: ...isappears from the display Selecting powerful domestic water heating operation 1 Press v for 5 seconds to activate powerful domestic water heating operation Icons w and m start ashing Powerful domesti...

Page 9: ...t water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the y button The y button only overrules the schedule timer until the next p...

Page 10: ...e schedule timer remind Familiarise yourself with the icons and the buttons You will need them when programming Refer to Name and function of buttons and icons on page 4 Fill out the form at the very...

Page 11: ...8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the temperature by me...

Page 12: ...on time 8 Use the ba button to select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation Fo...

Page 13: ...e next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to selec...

Page 14: ...D SET MODE The icon 3 will be displayed The current selected eld setting code is indicated 2 with the set value displayed to the right 1 2 Press the bgi button to select the appropriate eld setting rs...

Page 15: ...rature Lo_A Note that the Lo_Ti value should be higher than Hi_Ti as for low outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing...

Page 16: ...g Scheduled domestic hot water storage The storage set point can be accessed directly using the wi and wj buttons 6 03 Scheduled storage de nes whether the scheduled domestic water heating storage dur...

Page 17: ...omestic hot water user interface set point 9 Heating and cooling set point ranges The purpose of this eld setting is to prevent the user from selecting a wrong i e too hot or too cold leaving water te...

Page 18: ...d settings of the weather dependent set point 1 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model...

Page 19: ...eating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting 04 Not applicable Do not change the...

Page 20: ...lated setting 05 Not applicable Do not change the default setting d Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting...

Page 21: ...li ed installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is dispo...

Page 22: ...NOTES NOTES...

Page 23: ......

Page 24: ...Copyright 2010 Daikin 4PW67442 1A 12 2010...

Reviews: