EKCBX/H008BBV3

Unit for air to water heat pump system

4PW67442-1A – 12.2010

Operation manual

16

Scheduled/continuous domestic hot water reheat

[6-05] Reheat: defines whether the scheduled domestic water
reheat during daytime is enabled (1) or continuous reheat is
enabled (2) or reheat is disabled (0)

[6-06] Scheduled reheat start time: time of the day at which the
domestic water should be heated.

[6-07] Domestic hot water reheat set point

[6-08] Domestic hot water reheat set point hysteresis

Example 1

: Scheduled storage [6-03]=1, scheduled reheat [6-05]=1,

disinfection function [2-01]=1 activated.

A Scheduled storage operation:

 activated at [6-04], heat 

up domestic hot water untill domestic hot water user 
interface set point T

DHW

 (e.g 55°C) is reached.

B Scheduled reheat operation

: activated at [6-06], heat up 

domestic hot water untill domestic hot water reheat set 
point [6-07] (e.g 45°C ) is reached. 

C Disinfection operation

 (if activated): activated at [2-02], 

heat up domestic hot water untill domestic hot water 
disinfection set point [2-03] (e.g 60°C) is reached. Refer to 

"[2] Disinfection function" on page 15

.

t

Time

T

Domestic hot water temperature

T

DHW

Domestic hot water user interface set point

Example 2

: Scheduled storage [6-03]=1, continuous reheat [6-05]=2,

disinfection function [2-01]=1 activated.

A Scheduled storage operation:

 activated at [6-04], heat 

up domestic hot water untill domestic hot water user 
interface set point T

DHW

 (e.g 55°C) is reached.

B Continuous reheat operation

: continues activated heat 

up domestic water till domestic hot water reheat set point 
[6-07] (e.g 45°C) is reached with a hysteresis of [6-08]. 

C Disinfection operation

 (if activated): activated at [2-02], 

heat up domestic hot water untill domestic hot water 
disinfection set point [2-03] (e.g 60°C) is reached. Refer to 

"[2] Disinfection function" on page 15

.

t

Time

T

Domestic hot water temperature

T

DHW

Domestic hot water user interface set point

[9] Heating and cooling set point ranges

The purpose of this field setting is to prevent the user from selecting a
wrong (i.e., too hot or too cold) leaving water temperature. Thereto
the heating temperature set point range and the cooling temperature
set point range available to the user can be configured.

[9-00] Heating set point upper limit: maximum leaving water
temperature for heating operation.

[9-01] Heating set point lower limit: minimum leaving water
temperature for heating operation.

[9-02] Cooling set point upper limit: maximum leaving water
temperature for cooling operation.

[9-03] Cooling set point lower limit: minimum leaving water
temperature for cooling operation.

A

B

C

T

t

[2-03]

T

DHW

[6-07]

[6-04]

[6-06]

[2-02]

A

B

C

[6-08]

B

T

t

[2-03]

[6-07]

T

DHW

[6-04]

[2-02]

INFORMATION

Make sure the domestic water is only heated up to the
domestic hot water temperature you require.
Start with a low domestic hot water storage
temperature set point, and only increase if you feel
that the domestic hot water supply temperature is not
sufficient for your needs (this depends on your water
using pattern).

Make sure the domestic water is not heated
unnecessary. Start with activating automatic storage
during night (default setting). If it seems that the
domestic hot water night storage operation is not
sufficient for your needs, an additional scheduled
reheat during daytime can be set.

NOTICE

The setting [4-03] shall not be modified. The installer
selected the proper setting for your application.

INFORMATION

The status of this setting is only mentioned to indicate
which settings and functions are applicable for your
application.

CAUTION

In case of a floor heating application, it is important to
limit the maximum leaving water temperature at
heating operation according to the specifications of
the floor heating installation.

In case of a floor cooling application, it is important to
limit the minimum leaving water temperature at
cooling operation (field setting of parameter [9-03]) to
16~18°C to prevent condensation on the floor.

Summary of Contents for EKCBX008BBV3

Page 1: ...OPERATION MANUAL EKCBX008BBV3 EKCBH008BBV3 Unit for air to water heat pump system...

Page 2: ...manual speci ed for a certain product or application explaining how to install con gure and maintain it Operation manual Instruction manual speci ed for a certain product or application explaining how...

Page 3: ...er Refer to the operation manual of the indoor unit and to the installation manual of the digital I O PCB for more information Refer to the wiring diagram or connection diagram for connecting this PCB...

Page 4: ...tap be turned on for several minutes at a sink basin or bath but not at a dishwasher clothes washer or other appliance During this procedure there must be no smoking open ame or any electrical applia...

Page 5: ...9 OFF ICON x This icon indicates that the OFF action is selected when programming the schedule timer 10 INSPECTION REQUIRED k and l These icons indicate that inspection is required on the installatio...

Page 6: ...ing the clock 33 DOMESTIC HOT WATER TEMPERATURE ADJUST BUTTONS wbi and wbj These buttons are used to adjust the current set point of the domestic hot water temperature only for 4 03 0 1 2 or 3 These b...

Page 7: ...unit will immediately heat up the domestic water tank untill domestic hot water storage set point upon user request 2 Reheat Scheduled The unit will heat up the domestic water tank starting from a sc...

Page 8: ...isappears from the display Selecting powerful domestic water heating operation 1 Press v for 5 seconds to activate powerful domestic water heating operation Icons w and m start ashing Powerful domesti...

Page 9: ...t water temperature INFORMATION Only use the pr button to enable or disable the schedule timer The schedule timer overrules the y button The y button only overrules the schedule timer until the next p...

Page 10: ...e schedule timer remind Familiarise yourself with the icons and the buttons You will need them when programming Refer to Name and function of buttons and icons on page 4 Fill out the form at the very...

Page 11: ...8 Use the button to select the action number you would like to program or to modify 9 Use the ba button to select For space heating x switch heating and the controller off 9 set the temperature by me...

Page 12: ...on time 8 Use the ba button to select For space cooling x switch cooling and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation Fo...

Page 13: ...e next day e g copy all programmed actions from 1 to 2 To copy programmed actions to the next day proceed as follows 1 Press the button The actual mode is blinking 2 Use the pi and pj buttons to selec...

Page 14: ...D SET MODE The icon 3 will be displayed The current selected eld setting code is indicated 2 with the set value displayed to the right 1 2 Press the bgi button to select the appropriate eld setting rs...

Page 15: ...rature Lo_A Note that the Lo_Ti value should be higher than Hi_Ti as for low outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing...

Page 16: ...g Scheduled domestic hot water storage The storage set point can be accessed directly using the wi and wj buttons 6 03 Scheduled storage de nes whether the scheduled domestic water heating storage dur...

Page 17: ...omestic hot water user interface set point 9 Heating and cooling set point ranges The purpose of this eld setting is to prevent the user from selecting a wrong i e too hot or too cold leaving water te...

Page 18: ...d settings of the weather dependent set point 1 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model...

Page 19: ...eating off temperature 00 Installation related setting 01 Installation related setting 02 Space heating off temperature 25 14 25 1 C 03 Installation related setting 04 Not applicable Do not change the...

Page 20: ...lated setting 05 Not applicable Do not change the default setting d Local shift value weather dependent 00 Installation related setting 01 Installation related setting 02 Installation related setting...

Page 21: ...li ed installer in accordance with relevant local and national legislation Units must be treated at a specialized treatment facility for re use recycling and recovery By ensuring this product is dispo...

Page 22: ...NOTES NOTES...

Page 23: ......

Page 24: ...Copyright 2010 Daikin 4PW67442 1A 12 2010...

Reviews: