Part 2. Troubleshooting
2. Error code based troubleshooting
19/07/16
Page 33
Daikin Altherma Monobloc CA
2.30. “H8-00” – Malfunction of compressor input (CT) system
2.31. “H9-00” – Outdoor air thermistor (R3T) abnormality
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).
Stop valve is closed.
Check stop valves.
Open stop valves when required.
Faulty or disturbance of the power supply.
(Imbalance > 10%) Power drop.
Short circuit.
Check if the power supply is conform with
regulations. No fluctuations in frequency.
Adjust power supply when required.
Power reset via outdoor unit.
Trigger
Effect
Reset
The compressor running frequency is
below 55 Hz, voltage is below 0.1V and
the input current is below 0.5A
Unit will stop operating
Auto-reset if it is does not occur a second
time within 60 seconds.
Possible cause
Check
Corrective action
Faulty compressor.
Check compressor (see page 91).
Check compressor connection and wiring.
Check expansion valve operation (liquid
back issue).
Check refrigerant charge (see page 106)
+ check for leaks.
Replace the compressor when required.
(see page 125).
Investigate the reason of breakdown.
Replace expansion valve when required
(see page 131).
Fix the possible leak.
Faulty or disturbance of the power supply.
(Imbalance > 10%) Power drop.
Short circuit.
Check if the power supply is conform with
regulations. No fluctuations in frequency.
Adjust power supply when required.
Power reset via outdoor unit.
Faulty outdoor inverter PCB.
Check outdoor inverter PCB (see
page 101).
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Adjust the power to the outdoor inverter
PCB.
Replace outdoor inverter PCB when
required (see page 122).
Trigger
Effect
Reset
Thermistor detects an abnormal value
(open or short circuit).
Unit stops operating.
Auto-reset when problem is solved.
Possible cause
Check
Corrective action
Faulty outdoor air thermistor.
Check outdoor unit thermistor (see
page 88).
Replace outdoor unit thermistor when
required (see page 124).
Faulty outdoor main PCB.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if the outdoor main PCB receives
power.
Adjust the power to the outdoor main
PCB.
Replace outdoor main PCB when alive led
is not blinking in regular intervals (see
page 119).