Part 2. Troubleshooting
2. Error code based troubleshooting
Page 20
19/07/16
Daikin Altherma Monobloc CA
2.2. “AC-00” – Booster heater thermal protector is open
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if hydro PCB A1P receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or
install correct spare part when required.
Faulty wiring between outdoor unit - Con-
trol box - DHW tank.
Check wiring (power supply, connections
between PCB’s, ...).
Adjust wiring when required.
Faulty backup heater.
Check booster heater (see page 69).
Replace the booster heater when required
(see Installer reference guide of the water
tank).
Water pressure is too low.
Check the water pressure on the pressure
gauge.
Increase water pressure till ~2 bar. Refer
to the Installer Reference Guide.
Check for possible water leaks.
Water flow is too low.
Check the minimum water flow required
for the system. Refer to Installer Refer-
ence Guide.
Adjust system to meet the water flow
requirements.
Faulty extension PCB A4P.
Check if the correct spare part is installed.
Replace extension PCB A4P when
required.
Trigger
Effect
Reset
Thermal protector Q2L/Q3L is activated
(open circuit).
Water temperature > 85°C.
Unit will immediately stop operation.
Manual reset via user interface.
Possible cause
Check
Corrective action
Wrong settings.
Check settings related to hot water tank (is
tank connected and is booster heater used).
Correct settings according to Installer Refer-
ence Guide.
Tank clixon Q2L tripped.
Check if relay K3M is open.
Reset the tank clixon.
Incorrect parameter of solar pump station.
Check maximum tank temperature of solar
pump station.
Set maximum tank temperature to a reason-
able value.
Air in water circuit/Booster heater
Check if all air purge valves are open.
Check if air purge valves are installed on all
highest points of the field installed water cir-
cuit.
Purge the unit and field supplied water sys-
tem and backup heater when required. Refer
to the Installer Reference Guide.
Increased water temperature by external
heat source.
Check if another heat source is installed on
the same water circuit.
Correct hydraulic field circuit. Refer to the
Installer Reference Guide.
Faulty thermal protector Q1L.
Check thermal protector booster heater
Q2L/Q3L (see page 69).
Replace thermal protector booster heater
when required
.
Faulty hydro PCB A1P.
Check if the alive led is blinking in regular
intervals.
Check if the correct spare part is installed.
Check if
hydro PCB A1P
receives power.
Adjust the power to the PCB.
Replace hydro PCB A1P when alive led is
not blinking in regular intervals.
Adjust software of hydro PCB A1P or install
correct spare part when required.
Faulty wiring between outdoor unit - Control
box - DHW tank.
Check wiring (power supply, connections
between PCB's, ...).
Adjust wiring when required.
Faulty booster heater.
Check booster heater (see page 69).
Replace the booster heater
when required
(see Installer reference guide of the water
tank).
Water pressure is too low.
Check the water pressure on the pressure
gauge.
Increase water pressure till ~2 bar. Refer to
the Installer Reference Guide.
Check for possible water leaks.
Water flow is too low.
Check the minimum water flow required for
the system. Refer to Installer Reference
Guide.
Adjust system to meet the water flow
requirements
Faulty extension PCB A4P.
Check if the correct spare part is installed.
Replace extension PCB A4P when
required.