6
x
Parameter settings
Daikin RoCon HP
Daikin Controller
008.1420844_13 – 02/2016
Operating instructions
47
Room Influence
Only if the room station
is connected and assigned to the heating circuit.
Setting of the impact the deviation of the room temperature measured by the
EHS157034 from the actual set value (see sections 3.4.3 and 3.4.4) has on the flow
temperature.
Off: Exclusively weather-controlled flow temperature regulation
0: Purely weather-controlled flow temperature regulation, but internal heat recircula-
tion pump continues to run until the next heating cycle following a heat demand during
the setback time.
1-20: Causes a correction of the set flow temperature (parallel shift of the heat curve)
by the set factor.
For example: If the measured temperature is 2 K below the set value, the set flow tem-
perature is raised 2-times the set value.
E
E
Off, 0 - 20
Off
1
T-Room Adj
Only if the room station
is connected and assigned to the heating circuit.
Individual adaptation of the room temperature relevant for control.
Should a systematic deviation of the room temperature as measured by the
EHS157034 from the actual temperature in the living area of this room be detected,
the measured value can be corrected by the set value.
E
E
-5.0 to +5.0 kW
0.0 K
1 K
T-Flow Day
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the heating time
when in operating mode: "Automatic 1", "Automatic 2", "Heating".
E
E
20 - 90 °C
40 °C
1 °C
T-Flow Night
Only if parameter [HC Function] = 1:
Setting the inflow target temperature for the heating circuit during the setback time
when in operating mode: "Automatic 1", "Automatic 2", "Reducing".
E
E
10 - 90 °C
10 °C
1 °C
Max T-Flow
The inflow temperature determined for the heating circuit is limited to the maximum
value set here.
If an additionally connected mixed heating circuit demands a higher temperature for
the Daikin Altherma EHS(X/H), this is taken into account. This means that the heat in-
ternal circulation pump for the Daikin Altherma EHS(X/H) runs all the time when this
is switched on. If the connected heating circuit supplies underfloor heating, a mechan-
ical temperature limiter must be fitted to prevent overheating the screed.
N
E
20 - 90 °C
55 °C
1 °C
Min T-Flow
The inflow temperature determined for the heating circuit is limited to the minimum val-
ue set here.
N
E
28 - 90 °C
28 °C
1 °C
HC Adaption
Only if the room station
is connected and assigned to the heating circuit.
Off: Deactivated
On: Activated = Start a one-off automatic adaptation of the heating curve.
Requirements:
- Outside temperature <8 °C
- Setting the operating mode: "Automatic 1" or "Automatic 2"
- Duration of the setback phase must be at least 6 hours
Function: At the start of the setback time the current room temperature is set as the
target value for the following 4 hours. The heating curve is determined by the Control-
ler from the inflow target temperatures that are necessary to maintain this room tem-
perature.
If the automatic adjustment of the heating curve is interrupted, the function pauses un-
til it is performed successfully on the next day or until it is ended by setting the param-
eter to "Off" or by changing the current operating mode.
The hot water generation and the heating-up optimisation are blocked during the au-
tomatic heating curve adapting.
N
E
Off
On
Off
-
Cooling (
Can be used only if the assigned heat generator has a cooling function.)
Start T-Out Cooling
Only if parameter [HC Function] = 0:
Setting from which outside temperature the cooling operation with the highest cooling
infeed target temperature [T-Flow Cooling start] starts (setting condition: operating
mode "Cooling").
E
E
15 - 45 °C
24 °C
1 °C
Max T-Out Cooling
Only if parameter [HC Function] = 0:
Setting to determine from which outdoor temperature the lowest cooling flow temper-
ature [T-Flow Cooling max] is stipulated (setting condition: operating mode "Cooling").
E
E
20 - 45 °C
35 °C
1 °C
T-Flow Cooling start Only if parameter [HC Function] = 0:
Setting the cooling inflow target temperature at the start of cooling mode (outside tem-
perature = parameter [Start T-Out Cooling]).
E
E
5 - 25 °C
18 °C
1 °C
T-Flow Cooling max Only if parameter [HC Function] = 0:
Setting the minimum cooling inflow target temperature. This is kept constant relative
to the outside temperature (parameter [Max T-Out Cooling]).
E
E
5 - 25 °C
8 °C
1 °C
Min T-Flow Cooling
Only if parameter [HC Function] = 0:
Setting the absolute lower limit of the cooling inflow target temperature. The limitation
is effective if a lower cooling inflow target temperature is determined based on other
parameter settings.
N
E
5 - 25 °C
18 °C
1 °C
T-Flow Cooling
Only if parameter [HC Function] = 1:
Setting the cooling inflow target temperature (fixed value) when cooling mode is ac-
tive.
E
E
8 - 30 °C
18 °C
1 °C
T_H/C Switch
Automatic activation of the cooling mode.
Off: Deactivated
10 - 40: If the outdoor temperature exceeds the set value, the operating mode
"Cooling" is set. If the outdoor temperature falls below the set value by 2 K, the system
automatically switches back to the previously activated operating mode.
N
E
Off, 10 - 40 °C
Off
1 °C
Cooling Setpoint adj Parallel displacement of the cooling characteristic curve to match the set value.
E
E
-5.0 to +5.0 kW
0.0 K
1 K
Tab. 6-3 Parameter in rotary switch setting "Configuration" level "HC Configuration"
Sub-
le
vel
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF