4.8. Water pump M1P
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Drain the water circuit.
3. Remove the 4 screws that fix the pump motor to the pump house.
4. Separate the pump motor from the pump house.
5. Inspect the rotor and check that it rotates smoothly.
6. After water pump assembly and filling the water circuit, check pump for leaks.
-
Replace the seal if the water pump leaks.
1. Switch off the Daikin Altherma GSHP via the user interface.
2. Remove the front panel, refer to
"Removing the front panel" on page 85
.
3. Open the Sound Insulation (Front Side Only), refer to
"Opening the sound insulation of the heat pump module (front side only)"
.
4. Power the Daikin Altherma GSHP.
5. Activate “Installer level” on the user interface, refer to “Installer Level Settings” on the user interface are available in the
Installer Reference Guide, paragraph To access the most used commands.
6. Select Actuator test run A.7.4.
7. Activate the water pump (A.7.4.6).
8. Check the LED on the water pump, it must light green.
Technical specification
Description
The water pump M1P is an inverter driven, variable speed pump (invertor signal
from PCB A9P, connector X25A).
The water pump M3P circulates the water in the
water circuit.
Location
Piping diagram
Switch box
Unit
Check procedure
Mechanical check
Electrical check