Daikin ECB2MUAW Installation Manual Download Page 4

Installation manual

2

EWWP045~06 ECB2+3MUAW

Packaged water-cooled water chillers

4PW61663-1A - 2012.04

O

PERATION

 

RANGE

M

AIN

 

COMPONENTS

 

(refer to the outlook diagram supplied

with the unit)

1

Compressor

2

Evaporator

3

Condenser

4

Switchbox

5

Chilled water in

6

Chilled water out

7

Condenser water out

8

Condenser water in

9

Evaporator entering water temperature sensor

10

Freeze-up sensor

11

Condenser entering water temperature sensor

12

Digital display controller

13

Power supply intake

S

ELECTION

 

OF

 

LOCATION

The units are designed for indoor installation and should be installed
in a location that meets the following requirements:

1

The foundation is strong enough to support the weight of the unit
and the floor is flat to prevent vibration and noise generation.

2

The space around the unit is adequate for servicing. 

3

There is no danger of fire due to leakage of inflammable gas.

4

Select the location of the unit in such a way that the sound
generated by the unit does not disturb anyone.

5

Ensure that water cannot cause any damage to the location in
case it drips out of the unit. 

The equipment is not intended for use in a potentially explosive
atmosphere.

I

NSPECTING

 

AND

 

HANDLING

 

THE

 

UNIT

At delivery, the unit should be checked and any damage should be
reported immediately to the carrier claims agent.

U

NPACKING

 

AND

 

PLACING

 

THE

 

UNIT

1

Cut the straps and remove the cardboard box from the unit.

2

Remove the four screws fixing the unit to the pallet.

3

Level the unit in both directions with the lifting lugs which are
delivered with the control box (ECB*MUAW).

4

Use four anchor bolts with M8 thread to fix the unit in concrete
(directly or using the floor standing supports).

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R407C

GWP

(1)

 value:

1652.5

(1)

 GWP = global warming potential

The refrigerant quantity is indicated on the unit name plate.

C

HECKING

 

THE

 

WATER

 

CIRCUIT

The units are equipped with water inlets and water outlets for connec-
tion to a chilled water circuit and to a hot water circuit. These circuits
must be provided by a licensed technician and must comply with all
relevant European and national regulations.

Before continuing the installation of the unit, check the following
points:

1

A circulation pump must be provided in such a way that it dis-
charges the water directly into the heat exchanger.

2

A flow switch must be installed in the water outlet pipe to prevent
the unit from operating at a water flow which is too low. A
terminal is provided in the switch box for the electrical
connection of the flow switch.

3

A wire mesh strainer (<1 mm) must be installed at the pump
suction as to protect the pump and the heat exchanger from
foreign matter.

4

Drain taps must be provided at all low points of the system to
permit complete drainage of the circuit during maintenance or in
case of shut down.

5

Air vents must be provided at all high points of the system. The
vents should be located at points which are easily accessible for
servicing.

6

Shut-off valves should be provided at the unit so that normal
servicing can be accomplished without draining the system.

7

Vibration eliminators in all water piping connected to the chiller
are recommended to avoid straining the piping and transmitting
vibration and noise.

LWC

Leaving water temperature condenser

LWE

Leaving water temperature evaporator

a

Glycol

b

Water

Continuous operation range

0

10

20

–10

–5

5

32

0

10

20

30

40

50

60

LWC

55

45

ZL

ZL

ZH

ZH

ZL

ZH

-2

-2

–2

a    b

a    b

a    b

The unit is only to be used in a closed water system.
Application in an open water circuit can lead to excessive
corrosion of the water piping.

Summary of Contents for ECB2MUAW

Page 1: ...INSTALLATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB2MUAW ECB3MUAW Packaged water cooled water chillers...

Page 2: ...B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Informatio...

Page 3: ...d features 1 Options Glycol application for leaving evaporator water down to 10 C or 5 C Low noise operation kit field installation Features Voltage free contacts general operation pumpcontact alarm R...

Page 4: ...ated greenhouse gases covered by the Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R407C GWP 1 value 1652 5 1 GWP global warming potential The refrigerant quantity is indicated...

Page 5: ...circuit must be provided for connection of the unit This circuit must be protected with the required safety devices i e a circuit breaker a slow blow fuse on each phase and an earth leak detector Rec...

Page 6: ...g site of the refrigeration system 1 European International Technical Standard setting the limits for voltage changes voltage fluctuations and flicker in public low voltage supply systems for equipmen...

Page 7: ...ircuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emergency...

Page 8: ......

Page 9: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 ANNEX Installing the control box 1 2 3...

Page 10: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 2 3 4 1...

Page 11: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 2 2 1 1 8 x 4 x 2 2 1 1 3 3 4 4 5 5...

Page 12: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 2 2 1 1 3 3 8 x 8 x 2 2 1 1 3 3 4 4 6 6 5 5...

Page 13: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 1 1 2 2 3 3 4 4 1 1 2 2 3 3 4 4...

Page 14: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 3 3 2 2 1 1...

Page 15: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 3 3 4 4 2 2 1 1...

Page 16: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 1 1 2 2 1 1 1 1 2 2 2 2...

Page 17: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 1 1 2 2 3 3 1 1 1 1 2 2 2 2 3 3 3 3...

Page 18: ...EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 Packaged water cooled water chillers Annex 1 1 5 5 4 4 3 3 2 2 50 Hz 3 x 400 V...

Page 19: ...Packaged water cooled water chillers Annex EWWP045 065KAW1M ECB2 3MUAW Installation manual 4PW61663 1A 2012 04 4 x 6 x...

Page 20: ...4PW61663 1A 2012 04 Copyright 2010 Daikin...

Reviews: