9
|
Electrical installation
Installer reference guide
110
EBLA04~E23V3 + EDLA04~E23V3
Daikin Altherma 3 M
4P685228-1A – 2022.05
2
Push the rear plate on each of the 4 spots where the snap-fits are located.
9.2.6 To connect the shut-off valve
INFORMATION
Shut-off valve usage example.
In case of one LWT zone, and a combination of
underfloor heating and heat pump convectors, install a shut-off valve before the
underfloor heating to prevent condensation on the floor during cooling operation.
Wires: 2×0.75 mm²
Maximum running current: 100 mA
230 V AC supplied by PCB
—
1
Access the electrical connections. See
"9.2.1 To connect the electrical wiring
95].
2
Connect the valve control cable to the appropriate terminals as shown in the
illustration below.
NOTICE
Only connect NO (normally open) valves.
X2M.4
X2M.3
M2S
(NO)