Troubleshooting for Outdoor Unit
SiAU18-715
398
Troubleshooting
7.35
Malfunction of Transmission between Central Remote
Controller and Indoor Unit
Remote
Controller
Display
UE
Applicable
Models
AII indoor unit models
Centralized controller
Method of
Malfunction
Detection
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Decision
Conditions
When transmission is not carried out normally for a certain amount of time
Supposed
Causes
Malfunction of transmission between optional controllers for centralized control and indoor
unit
Connector for setting master controller is disconnected.
Failure of PCB for centralized remote controller
Defect of indoor unit PCB